Dịch vụ & Phân phốiCâu 48 / 521
A transformer has a primary full-load current of 40 A and uses primary-only overcurrent protection. What is the maximum standard primary OCPD (125% rule)?
a.40 A
b.60 A
c.45 A
d.50 A
Giải thích
40 A x 125% = 50 A, which is a standard size, so 50 A is the maximum per Table 450.3(B). 40 A ignores the 125% factor, while 45 A undersizes and 60 A exceeds the calculated maximum.
Trích dẫn luật: 2023 NEC §450.3(B)Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- What is the full-load secondary current of a 45 kVA, 3-phase, 208 V transformer?
- What is the full-load primary current of a 75 kVA, 3-phase, 480 V transformer?
- For a transformer over 1000 V or with primary-only protection under 450.3(B), where primary current is 9 A or more, the primary OCPD generally may not exceed what percentage of primary full-load current?
- Conductors are connected to a transformer secondary without an OCPD at the secondary terminals. What set of rules governs their length and sizing?
- Why must ventilating openings of a dry-type transformer be kept clear of walls and obstructions?
- For a single service, what is the maximum number of service disconnecting means permitted (for one set of service-entrance conductors)?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-10 Electrical Trade Examination · Quy trình kiểm tra