A branch-circuit breaker trips instantly every time it is reset, with nothing plugged in. Continuity from hot to ground reads near 0 ohms. What is the most likely fault?
a.Simple overload from too many appliances
b.An open neutral
c.A short circuit (hot-to-ground or hot-to-neutral) in the wiring
d.Undersized service transformer
Giải thích
Instant tripping with no load, plus a near-0 ohm hot-to-ground reading, points to a bolted short circuit providing a very low-resistance fault path. An overload (a) needs connected load and trips on a time delay, an open neutral (b) would not trip the breaker, and transformer sizing (d) does not cause instantaneous branch trips.
Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A 6 ohm and a 3 ohm resistor are connected in parallel. What total resistance should an ohmmeter read?
- During commissioning you want to confirm that a metal equipment enclosure is effectively bonded. Which check best verifies a low-impedance bond to ground?
- In a series circuit, 24 V is applied across a 4 ohm and an 8 ohm resistor in series. What voltage will a DMM read across the 8 ohm resistor?
- Three parallel loads on a 120 V circuit draw 4 A, 6 A, and 5 A respectively. What total current should a clamp meter read on the feeder conductor?
- A non-contact voltage tester (NCVT) does not light up near a conductor you must work on. Before treating the conductor as dead, what is the correct action?
- A single-phase load operates at 240 V and draws 20 A at unity power factor. What is its power in kilowatts?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-10 Electrical Trade Examination · Quy trình kiểm tra