Kiểm tra & Khắc phục sự cốCâu 510 / 521
Three parallel loads on a 120 V circuit draw 4 A, 6 A, and 5 A respectively. What total current should a clamp meter read on the feeder conductor?
a.5 A
b.15 A
c.120 A
d.1.6 A
Giải thích
Currents in parallel branches add: 4 + 6 + 5 = 15 A on the common feeder. Option a is only one branch, c confuses voltage with current, and d inverts the sum. This is why the feeder must be sized for the combined load.
Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- During commissioning you want to confirm that a metal equipment enclosure is effectively bonded. Which check best verifies a low-impedance bond to ground?
- In a series circuit, 24 V is applied across a 4 ohm and an 8 ohm resistor in series. What voltage will a DMM read across the 8 ohm resistor?
- A branch-circuit breaker trips instantly every time it is reset, with nothing plugged in. Continuity from hot to ground reads near 0 ohms. What is the most likely fault?
- A non-contact voltage tester (NCVT) does not light up near a conductor you must work on. Before treating the conductor as dead, what is the correct action?
- A single-phase load operates at 240 V and draws 20 A at unity power factor. What is its power in kilowatts?
- Before connecting a three-phase motor to a new feeder, why would you use a phase-rotation (phase-sequence) meter on the supply?