Why does over-torquing a lug or terminal screw create a hazard, even though the connection feels 'extra tight'?
a.Over-torque improves conductivity and is always safer
b.Over-torque can crush strands, deform the lug, and damage threads, raising resistance and causing a hot connection or eventual failure
c.Over-torque only matters on aluminum, never copper
d.Torque has no effect on connection reliability
Giải thích
Both under- and over-torque are harmful: over-torquing can crack lugs, crush or shear conductor strands, and strip threads, increasing contact resistance and heat over time. That is why the NEC requires using the manufacturer's specified value with a calibrated tool. It applies to copper and aluminum alike (c), and torque very much affects reliability (d).
Trích dẫn luật: 2023 NEC §110.14(D)Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A single-phase load operates at 240 V and draws 20 A at unity power factor. What is its power in kilowatts?
- Before connecting a three-phase motor to a new feeder, why would you use a phase-rotation (phase-sequence) meter on the supply?
- Using the rule of thumb of 1 megohm minimum per 1,000 V of rating, what is the minimum acceptable insulation resistance for a 4,160 V motor?
- A homeowner reports that throughout the house, some lights dim while others brighten, and the effect shifts as loads switch on and off. Which service-level fault best explains this?
- Two meters are both marked CAT III, but one is rated 600 V and the other 1000 V. What does the voltage number add to the CAT rating?
- By mistake you clamp your ammeter around BOTH the hot and neutral conductors of a single-phase 120 V branch circuit that is drawing 8 A. What will the clamp meter most likely read?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-10 Electrical Trade Examination · Quy trình kiểm tra