Kiểm tra & Khắc phục sự cốCâu 520 / 521
During commissioning of a new bathroom circuit, how should you verify a GFCI receptacle provides ground-fault protection?
a.Press the built-in TEST button (and/or use a GFCI tester) and confirm it trips and removes power, then RESET
b.Measure 120 V hot-to-neutral only and assume it works
c.Check that the LED is lit and skip tripping it
d.Short the hot to ground with a screwdriver to force a trip
Giải thích
The correct functional test is to operate the built-in TEST button (or an external GFCI tester that injects a small fault) and confirm the device trips and de-energizes the outlet, then reset it. A normal voltage reading (b) or a lit indicator (c) does not prove the ground-fault sensing works. Deliberately shorting to ground (d) is dangerous and unnecessary.
Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Why does over-torquing a lug or terminal screw create a hazard, even though the connection feels 'extra tight'?
- A homeowner reports that throughout the house, some lights dim while others brighten, and the effect shifts as loads switch on and off. Which service-level fault best explains this?
- Two meters are both marked CAT III, but one is rated 600 V and the other 1000 V. What does the voltage number add to the CAT rating?
- By mistake you clamp your ammeter around BOTH the hot and neutral conductors of a single-phase 120 V branch circuit that is drawing 8 A. What will the clamp meter most likely read?
- A motor-control resistor of 15 ohms must carry 2 A during operation. What voltage drop will a DMM read across it?
- A 120 V heater is rated 600 W. What is the operating resistance of its element (assume purely resistive)?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-10 Electrical Trade Examination · Quy trình kiểm tra