CSLB HVAC (C-20) Trade — All Questions

这些题目考的数字,按章节排在可打印的彩色高密度页面上: 速记册,$9.99 →

拥有完整的 CSLB C-20 HVAC 学习指南 —— PDF + EPUB,$14.99 →

← Back to practice

64 questions

Safety & Codes

Why must return air not be drawn from a bathroom, closet, or garage?

  • a.Because moisture, contaminants, or vehicle exhaust would be distributed through the house✓
  • b.Because those rooms rarely have a supply register to balance against
  • c.Because those spaces are usually too small to supply enough air
  • d.Because the return grille would violate the room's fire rating

Air pulled from these spaces carries moisture, chemicals, or combustion products into the return and then into every room the system serves. Room size is a design consideration but not the reason for the prohibition. Whether a supply register exists does not change the contaminant issue. And most such rooms are not fire rated, so a rating violation is not the basis of the rule.

Safety & Codes

A technician needs to enter a crawl space to service ductwork. What hazard assessment applies?

  • a.It is a permit-required confined space in every case
  • b.It may be a confined space, requiring evaluation of atmosphere and access✓
  • c.It is only a confined space when standing water is present
  • d.It is exempt from any evaluation because it is underneath the customer's home

A crawl space has limited entry and exit and is not designed for continuous occupancy, so it must be evaluated for atmospheric hazards, engulfment, and access before entry. Being residential does not exempt a space from evaluation. Not every crawl space rises to permit-required status; that depends on the hazards found. And standing water is one possible hazard among several, not the sole test.

Safety & Codes

What must be tested before entry into a permit-required confined space?

  • a.Ambient noise level and lighting adequacy
  • b.Relative humidity and dew point of the space
  • c.Oxygen content, flammable gases, and toxic contaminants✓
  • d.Structural load capacity of the floor joists and the decking

Atmospheric testing checks oxygen level first, then flammable gas concentration, then toxic contaminants, in that order. Noise and lighting are working conditions but not atmospheric hazards. Structural capacity matters for access planning, not atmospheric testing. And humidity is a comfort parameter with no bearing on the entry hazard.

Safety & Codes

A technician must take a voltage reading inside an energized panel. What practice reduces the risk?

  • a.Remove watches and rings only, since jewelry is the main hazard
  • b.Use rated meter leads and PPE, keep one hand clear, and stand on a dry surface✓
  • c.Have a helper hold the panel cover to improve visibility
  • d.Work quickly so exposure time is minimized

Properly rated test equipment, appropriate protective equipment, avoiding a hand-to-hand current path, and standing on a dry insulating surface together address shock and arc hazards. Removing jewelry helps but is only one small piece. Speed does not reduce the severity of a fault. And a helper holding a metal cover adds a second person into the hazard zone.

Safety & Codes

What does an arc flash hazard in an electrical panel primarily produce?

  • a.A slow buildup of heat that trips the breaker well before injury occurs
  • b.A magnetic field that damages test instruments
  • c.A sustained current path through the equipment ground
  • d.An intense release of heat and pressure that can burn a nearby worker✓

An arc flash releases enormous energy in milliseconds, producing burns, blast pressure, and molten metal well beyond the point of the fault. Breakers do not always clear fast enough to prevent injury. Magnetic effects exist but are not the injury mechanism. And a sustained ground path describes a ground fault, not the arc flash event itself.

Safety & Codes

A technician is cutting an opening in an old plaster ceiling for a return grille and creates heavy dust. What hazard should be considered?

  • a.Static electricity generated by the cutting tool
  • b.Only the risk of damage to the customer's furnishings and floors
  • c.Respirable dust that may contain silica or lead-based paint✓
  • d.Only the risk of eye irritation from large particles

Old building materials can contain crystalline silica and lead-based paint, and the fine airborne fraction is what reaches the lungs or is ingested. Eye irritation is real but is the least of the health concerns. Protecting furnishings is a workmanship matter, not a health hazard. And static from a cutting tool is not a recognized hazard in this task.

Safety & Codes

Where does a technician find the health hazards and handling requirements for a chemical coil cleaner?

  • a.On the product's safety data sheet✓
  • b.On the equipment manufacturer's installation instructions
  • c.On the CSLB's license classification page
  • d.In the California Mechanical Code appendix

A safety data sheet lists composition, health effects, protective equipment, first aid, and disposal for that specific product, and it must be available to workers who use it. Equipment installation instructions cover the appliance, not the chemicals a technician brings. The mechanical code regulates installations, not chemical products. And license classification pages describe scope of work.

Safety & Codes

A supply duct penetrates a garage ceiling that separates the garage from the dwelling. What construction requirement applies?

  • a.The duct must include a manual damper at the penetration
  • b.The duct must be lined with fiberglass on the interior surface
  • c.The duct must be of a material and construction that maintains the required separation✓
  • d.The duct must be increased one size where it passes through

Ducts crossing the garage separation must be constructed so the separation between the garage and the dwelling is maintained, and no openings may be made into the garage. Interior lining is an acoustic or thermal choice with no bearing on the separation. A manual damper is a balancing device, not a rated assembly. And upsizing at a penetration serves no code purpose.

Safety & Codes

Why is it prohibited to install a supply or return opening in a garage that connects to the dwelling's duct system?

  • a.Because the garage door creates pressure fluctuations in the duct
  • b.Because vehicle exhaust and stored chemicals could be carried into living areas✓
  • c.Because garage temperatures would damage the ductwork over time
  • d.Because the garage is not conditioned space and would waste energy

Any opening between the garage and the duct system provides a direct path for carbon monoxide and chemical vapors to reach bedrooms and living spaces. Energy waste is a real but secondary consequence. Garage temperature swings do not damage properly installed duct. And door movement creates minor pressure changes that are not the basis of the prohibition.

Safety & Codes

A technician plans to work alone servicing rooftop units at a vacant commercial building. What safety provision matters most?

  • a.A check-in procedure so someone knows the location and expected return✓
  • b.Parking the service vehicle where it is clearly visible from the street
  • c.Bringing a second set of gauges in case one fails
  • d.Wearing a company uniform so occupants can identify the worker

Working alone at height with energized equipment and refrigerant means an injury will go undiscovered unless someone knows where the technician is and when to expect contact, so a scheduled check-in is the provision that actually shortens response time. Backup gauges address downtime, not injury. Vehicle placement does not summon help if the technician is unconscious on a roof. And a company uniform aids identification in an occupied building, which this one is not.

Safety & Codes

An HVAC company must maintain workers' compensation coverage under California contractor law. What does that coverage do?

  • a.It pays medical costs and lost wages for employees injured on the job✓
  • b.It insures the customer against defective workmanship
  • c.It covers property damage the contractor causes on a job
  • d.It replaces the contractor's bond obligation to the CSLB

Workers' compensation is employee injury coverage, paying medical treatment and wage replacement without regard to fault. The contractor's bond is a separate financial security posted with the board. Workmanship defects are addressed by contract, warranty, and the bond. And third-party property damage falls under general liability insurance.

Safety & Codes

A customer signs a residential change-out contract at their kitchen table. What consumer protection generally applies?

  • a.A requirement that the contractor finance the project at no interest
  • b.An automatic extension of the manufacturer's warranty to ten years
  • c.A guarantee that the equipment will be installed within ten days
  • d.A right to cancel the contract within a defined period after signing✓

Home solicitation contracts signed away from the contractor's place of business carry a statutory right to cancel within a defined window, and the notice must be given to the buyer. No law fixes a ten-day installation deadline. Warranty length is set by the manufacturer and the contract. And there is no requirement that a contractor provide interest-free financing.

Safety & Codes

Why must a technician verify that the correct refrigerant is being added to a system?

  • a.Because mixing refrigerants voids the equipment's efficiency rating
  • b.Because mixed refrigerants cannot be recovered or reclaimed and change system pressures✓
  • c.Because different refrigerants require different gauge hose colors
  • d.Because the wrong refrigerant will not pass through the metering device

A cross-charged system produces unpredictable pressures and creates a mixture that no reclaimer will accept, so the entire charge becomes waste. Efficiency ratings are a secondary concern next to the safety and disposal problem. Hose color is a convention, not a technical requirement. And the wrong refrigerant flows through a metering device perfectly well, which is exactly why the error is not self-correcting.

Safety & Codes

A technician is asked to sign off on a job installed by someone else without inspecting it. What is the professional obligation?

  • a.Sign if the customer accepts responsibility for the work in writing
  • b.Sign and note on the invoice that the work was not observed
  • c.Sign if the other installer is also licensed under the same classification
  • d.Decline unless the work is actually inspected and verified✓

Certifying work means attesting to its condition, which cannot be done without inspecting it, and a false certification exposes both the public and the license. Another person's license does not transfer verification responsibility. A customer cannot waive a safety certification obligation. And a disclaimer on an invoice does not cure a certification that was never based on observation.