1. The detailed federal regulations that carry out Clean Air Act Section 608 are found in which part of the Code of Federal Regulations?
a.29 CFR Part 1910 (OSHA)
b.21 CFR Part 110 (FDA)
c.49 CFR Part 172 (DOT)
d.40 CFR Part 82, Subpart F✓

The refrigerant management regulations that implement Section 608 are codified in 40 CFR Part 82, Subpart F, titled Recycling and Emissions Reduction. 29 CFR is OSHA workplace safety, 49 CFR is DOT hazardous materials transport, and 21 CFR is FDA food rules. Knowing the correct citation helps technicians look up specific requirements.

40 CFR Part 82 Subpart F
2. A technician is caught knowingly venting refrigerant. Under the Clean Air Act, EPA may assess civil penalties of up to how much per day, per violation?
a.Up to $124,426 per day✓
b.Up to $100 total
c.There are no monetary penalties
d.Up to $500 per day

The Clean Air Act penalty in 42 U.S.C. §7413(b) is adjusted for inflation every year; 40 CFR §19.4 sets it at $124,426 per day, per violation, for penalties assessed on or after January 8, 2025. Older study guides still print $37,500, which is the pre-2016 figure. $500 per day and $100 total badly understate the risk, and 'no monetary penalties' is simply false. EPA may also pay an award to a person whose information leads to a penalty.

42 U.S.C. §7413(b); 40 CFR §19.4
3. Under the post-2019 leak repair rules, what is the annual leak rate threshold that triggers required repairs for a comfort-cooling appliance containing 50 or more pounds?
a.35 percent
b.5 percent
c.10 percent✓
d.20 percent

For comfort-cooling appliances with a full charge of 50 or more pounds, the leak rate threshold that triggers required repairs is 10 percent per year under the rules effective January 1, 2019. Commercial refrigeration is 20 percent and industrial process refrigeration is 30 percent, so 35 percent and 20 percent are the wrong category or the older standard. Exceeding the threshold starts the 30-day repair clock.

40 CFR §82.157
4. A refrigerated warehouse uses a commercial refrigeration system with 300 pounds of refrigerant. What annual leak rate threshold applies to commercial refrigeration under the current rules?
a.30 percent
b.50 percent
c.20 percent✓
d.10 percent

Commercial refrigeration appliances have a leak rate threshold of 20 percent per year, higher than the 10 percent for comfort cooling but lower than the 30 percent for industrial process refrigeration. A 50 percent threshold does not exist under the rule. Once the calculated annual leak rate exceeds 20 percent, repairs must generally be completed within 30 days.

40 CFR §82.157
5. An industrial process refrigeration system in a chemical plant contains 1,000 pounds of refrigerant. Which annual leak rate threshold applies?
a.15 percent
b.20 percent
c.30 percent✓
d.10 percent

Industrial process refrigeration has the highest leak rate threshold at 30 percent per year, reflecting the large charges and specialized nature of these systems. Comfort cooling is 10 percent and commercial refrigeration is 20 percent, while 15 percent was part of the older pre-2019 framework. Exceeding 30 percent triggers the repair and, if needed, retrofit or retirement requirements.

40 CFR §82.157
6. A technician stores refrigerant cylinders in a work van during summer. To avoid dangerous pressure buildup, cylinders should not be exposed to temperatures above:
a.125°F✓
b.300°F
c.212°F
d.500°F

Refrigerant cylinders should never be exposed to temperatures above 125°F, because heat raises the internal pressure and can cause the cylinder to rupture or activate its relief device. 212°F, 300°F, and 500°F are far beyond safe limits. Cylinders should be kept in a cool, shaded, ventilated place and secured upright.

7. A technician is servicing a chiller in a small equipment room with poor ventilation. Which hazard is the greatest immediate concern if refrigerant leaks in that confined space?
a.The refrigerant catching fire from the light switch
b.Electric shock from the refrigerant
c.Oxygen displacement leading to asphyxiation✓
d.The room becoming too humid to work

Most refrigerants are heavier than air and can accumulate in low or confined spaces, displacing oxygen and causing asphyxiation, which is the greatest immediate danger in a poorly ventilated room. Refrigerants do not conduct a shock hazard on their own, most common refrigerants are not readily flammable, and humidity is not the concern. Proper ventilation and refrigerant monitors help protect against oxygen displacement.

8. While transferring liquid refrigerant, a technician gets a splash on bare skin. What injury is most likely, and what is the correct first aid?
a.No injury; liquid refrigerant is harmless on skin
b.Frostbite; flush with lukewarm water, get care✓
c.A chemical burn; rinse with vinegar
d.An electrical burn; apply ice directly

Liquid refrigerant evaporates rapidly and absorbs heat from the skin, causing frostbite, so the correct first aid is to flush the area with plenty of lukewarm (not hot) water and seek medical attention. Vinegar is for chemical exposures, ice would worsen frostbite, and liquid refrigerant is definitely not harmless. Wearing gloves and safety glasses prevents most of these injuries.

9. Which personal protective equipment (PPE) is most appropriate whenever a technician handles pressurized refrigerant?
a.Safety glasses and protective gloves✓
b.A hard hat only
c.No PPE is needed for HFCs
d.Sandals and short sleeves for comfort

Because pressurized refrigerant can cause frostbite and eye injury, technicians should wear safety glasses or goggles and refrigerant-rated gloves whenever handling it. A hard hat alone does not protect eyes or hands, sandals and short sleeves leave skin exposed, and PPE is still needed for HFCs. Proper PPE is a basic safe-handling requirement for all refrigerants.

10. A technician needs to warm a refrigerant cylinder to raise its pressure during charging. Which method is safe?
a.Use a propane torch on the cylinder base
b.Heat it with an electric heat gun on high
c.A bucket of warm water, about 90°F max✓
d.Place the cylinder over an open flame

The safe way to warm a cylinder is to place it in a bucket of warm water no hotter than about 90°F, which gently raises pressure without overheating. A torch, open flame, or high-heat gun can create dangerous pressure and can thermally decompose refrigerant into toxic gases. Never apply direct flame or concentrated heat to any refrigerant cylinder.

11. A technician is brazing near a line that still contains R-22 vapor. Why is exposing refrigerant to an open flame or very high heat dangerous?
a.It can decompose into toxic gases such as phosgene and HCl✓
b.It turns the refrigerant into harmless water vapor
c.It permanently improves the refrigerant's cooling ability
d.It has no effect because refrigerants are inert

When refrigerant contacts an open flame or very high heat, it can thermally decompose into toxic and corrosive gases such as phosgene, hydrogen chloride, and hydrogen fluoride, which are hazardous to breathe. It does not become harmless water vapor, improve performance, or stay inert. Systems should be recovered and purged before any hot work is performed nearby.

12. Which toxic gas is a well-known decomposition product formed when a chlorinated refrigerant contacts a flame?
a.Nitrogen
b.Oxygen
c.Helium
d.Phosgene✓

Phosgene is a highly toxic gas that can form when a chlorinated refrigerant such as R-22 contacts an open flame or hot surface, and even small amounts are dangerous to inhale. Oxygen, helium, and nitrogen are not toxic decomposition products of refrigerant. The presence of a sharp, acrid odor near hot work is a warning sign to stop and ventilate.

13. A technician is filling a recovery cylinder with liquid refrigerant and it is approaching the 80 percent mark. Why must the cylinder never be overfilled?
a.The refrigerant will lose its color
b.It only matters for disposable cylinders
c.Warming liquid expands and can burst it✓
d.Overfilling improves recovery speed with no risk

Liquid refrigerant expands significantly as temperature rises, so a cylinder filled beyond 80 percent can become hydrostatically full (completely liquid) and rupture with tremendous force. Overfilling does not affect color and is never risk-free, and the 80 percent limit applies to recovery cylinders, not only disposables. A scale should be used to prevent overfilling by weight.

14. To avoid overfilling a recovery cylinder past 80 percent, the most reliable method is to:
a.Estimate the level by shaking the cylinder
b.Weigh it on a refrigerant scale✓
c.Fill until the hose feels cold
d.Fill for a fixed number of minutes

The reliable way to stay within the 80 percent limit is to place the cylinder on a refrigerant scale and monitor the net weight against the cylinder's rated capacity, because the limit is defined by weight. Shaking, feeling the hose temperature, or timing the fill cannot accurately measure the charge. A float device or scale with automatic shutoff adds further protection.

15. A technician receives 'empty' return cylinders from a job. Which practice is safe and legal?
a.Refill disposable (DOT-39) cylinders to save money
b.Store cylinders lying down next to a furnace
c.Remove the pressure relief device to fit more refrigerant
d.Recover the heel; use only in-date, sound cylinders✓

Safe, legal practice is to recover any remaining refrigerant heel and to use only reusable recovery cylinders that are undamaged and within their required hydrostatic test interval. Disposable DOT-39 cylinders must never be refilled, cylinders should not be stored near heat sources, and pressure relief devices must never be removed. Damaged or out-of-date cylinders should be taken out of service.

16. How should refrigerant cylinders be secured during transport in a service vehicle?
a.Laid loose in the bed so they can roll freely
b.Left with the valve caps off for quick access
c.Upright and secured, valve caps on✓
d.Stacked horizontally without restraint

Cylinders should be transported secured in an upright position and restrained so they cannot fall or roll, with valve protection caps installed to protect the valve. Letting cylinders roll loose or stacking them unrestrained risks valve damage and a dangerous release, and caps should stay on until the cylinder is in use. A snapped-off valve can turn a cylinder into a dangerous projectile.

17. DOT-approved refillable refrigerant cylinders generally must undergo hydrostatic testing (requalification) at what interval?
a.They never need retesting
b.Every 6 months
c.Every 20 years
d.Every 5 years✓

Refillable DOT cylinders generally must be hydrostatically tested, or requalified, every 5 years to confirm they can safely hold pressure, and the test date is stamped on the cylinder. Testing every 6 months is unnecessary, 20 years is far too long, and cylinders do require periodic retesting. A cylinder past its test date should not be filled or transported until requalified.

18. Reclaimed refrigerant that will be resold must be reprocessed to meet which purity standard?
a.NFPA 70
b.AHRI 700✓
c.ASHRAE 15
d.UL 1995

Refrigerant intended for resale must be reclaimed to the AHRI 700 purity standard (historically called ARI 700), which sets the required purity for reclaimed product. ASHRAE 15 addresses refrigeration system safety, UL 1995 covers HVAC equipment safety, and NFPA 70 is the National Electrical Code. Meeting AHRI 700 is what allows used refrigerant to be legally sold to a new owner.

19. During an EPA inspection, an inspector asks a technician to show proof of certification. What must the technician be able to provide?
a.A driver's license only
b.A receipt for their recovery machine
c.A high school diploma
d.Their 608 certification card✓

Certified technicians must be able to demonstrate their certification, so keeping a copy of the Section 608 certification card or record available is important during inspections. A diploma, driver's license, or equipment receipt does not prove EPA certification. Employers must also keep records showing that technicians who handle refrigerant are certified.

40 CFR §82.161
20. A shop owner hires technicians who recover refrigerant. What certification recordkeeping does the owner need to keep on file?
a.Nothing; only the technician keeps records
b.Proof that each technician is certified✓
c.Only the recovery equipment serial numbers
d.Only the shop's business license

Employers must maintain records demonstrating that each technician who handles refrigerant holds a valid EPA Section 608 certification, and these records support compliance during inspections. A business license alone or equipment serial numbers do not satisfy this requirement, and the burden is not solely on the technician. Keeping proof of certification on file protects both the technician and the employer.

40 CFR §82.161
21. A recovery or recycling machine used on high-pressure appliances must generally be certified to meet standards set by which organization on behalf of EPA?
a.The state DMV
b.AHRI✓
c.The local fire department
d.The utility company

Recovery and recycling equipment must be certified to meet EPA-referenced performance standards, which are developed and administered by AHRI (formerly ARI). The fire department, DMV, and utility company have no role in certifying recovery equipment. Using certified equipment is required so recovery reaches the mandated evacuation levels.

40 CFR §82.161
22. A technician notices the pressure relief valve on a recovery cylinder is corroded and weeping refrigerant. What is the correct action?
a.Increase the fill amount to use it up faster
b.Plug the relief valve so it stops leaking
c.Paint over the corrosion and keep using it
d.Retire it and transfer its contents✓

A damaged or leaking pressure relief valve makes a cylinder unsafe, so it must be taken out of service and its contents recovered into a sound, approved cylinder. Plugging or bypassing a relief valve is extremely dangerous because it removes overpressure protection, and painting over corrosion or overfilling does not fix the hazard. Compromised cylinders should never be filled or transported.

23. Why is it important to never mix different refrigerants in the same recovery cylinder?
a.There is no problem mixing refrigerants
b.Mixed refrigerant usually cannot be reclaimed and must be destroyed✓
c.Mixed refrigerants weigh less and are easier to carry
d.Mixing improves the resale value

Mixing different refrigerants in one cylinder generally makes the mixture impossible to reclaim to a purity standard, so it often must be destroyed, which is costly and wasteful. Mixing does not reduce weight, improve resale value, or come without consequences. Technicians should dedicate cylinders to a single refrigerant and label them clearly.

24. A technician is about to recover refrigerant in a mechanical room. Which safety step best protects against oxygen displacement?
a.Ensuring ventilation and using an oxygen monitor in confined spaces✓
b.Turning off the lights to see leaks better
c.Closing all doors to keep the refrigerant contained
d.Wearing tinted sunglasses

Because refrigerant can displace oxygen, the best protection is adequate ventilation and, in confined spaces, a refrigerant or oxygen-level monitor that alarms before conditions become dangerous. Sunglasses do not help, closing all doors would trap leaking refrigerant, and turning off lights does not improve safety. Never enter a space suspected of high refrigerant concentration without ventilation and monitoring.

25. After exceeding the leak rate threshold on a 50-plus-pound appliance and repairing the leak, the owner is generally required to:
a.Do nothing further
b.Immediately replace the entire system
c.Report the leak to local police
d.Run a follow-up verification test✓

After repairing a leak that exceeded the threshold, the owner is generally required to conduct follow-up verification tests (an initial and a follow-up leak test) to confirm the repair worked. Doing nothing is not acceptable, replacing the whole system is not automatically required, and the leak is reported to EPA-related recordkeeping rather than local police. Verification testing documents that the appliance is no longer leaking above the threshold.

40 CFR §82.157
26. Which practice is safest when pressure-testing a system for leaks?
a.Regulated dry nitrogen, never oxygen or air✓
b.Pressurize with acetylene for faster results
c.Use the refrigerant charge itself at maximum pressure
d.Use pure oxygen for a stronger test

Leak testing should be done with regulated dry nitrogen because it is inert and will not react, and oxygen or acetylene must never be used since they can cause a violent reaction or explosion in the presence of oil or refrigerant. Compressed air can introduce moisture and, mixed with refrigerant under heat, form combustible conditions. Always use a pressure regulator so the system is not over-pressurized.

27. A technician witnesses a coworker intentionally venting refrigerant to save time. Under EPA enforcement, what may EPA offer to individuals who report a violation?
a.A tax deduction
b.A free certification upgrade
c.A monetary award✓
d.Nothing; reporting is discouraged

EPA is authorized to pay a monetary reward, sometimes called a bounty, to individuals who supply information that leads to a successful enforcement action for refrigerant violations. It is not a certification upgrade or a tax deduction, and reporting violations is encouraged, not discouraged. This provision helps EPA detect illegal venting and other violations.

Clean Air Act §608
28. A technician charging a high-pressure R-410A system should be especially aware that, compared with R-22, R-410A operates at:
a.Lower pressures that pose no equipment concern
b.The same pressures as R-22
c.Much lower pressures, so standard R-22 gauges are fine
d.Much higher pressures, requiring gauges and hoses rated for them✓

R-410A operates at significantly higher pressures than R-22, roughly 50 to 70 percent higher, so technicians must use gauges, hoses, and recovery equipment rated for those pressures. Using R-22-rated equipment on R-410A is unsafe because it may not withstand the higher pressure. Matching equipment ratings to the refrigerant is a basic pressure-hazard precaution.

29. Where should refrigerant cylinders be stored to remain safe?
a.Near a boiler to keep them warm
b.Cool, dry, ventilated, upright✓
c.In direct sunlight on a rooftop
d.Lying down under a stairwell exit

Cylinders should be stored in a cool, dry, well-ventilated area away from heat and ignition sources and secured upright so they cannot fall. Storing them near a boiler or in direct sunlight raises pressure dangerously, and blocking an exit path creates an additional hazard. Proper storage reduces the risk of overpressure, valve damage, and leaks.

30. A supply house offers small cans of R-134a to a walk-in DIY customer for a home refrigerator. Under Section 608 sales rules, what is the technician-buyer situation for such small-can HFC sales in stationary refrigeration?
a.Anyone may buy any size container of stationary refrigerant
b.Only certified technicians may buy it, any can size✓
c.Refrigerant sales have no restrictions at all
d.Only 30-pound cylinders are restricted; small cans are unrestricted

For stationary refrigeration and air conditioning, sales of substitute refrigerants such as HFCs are restricted to EPA Section 608-certified technicians or their employers, and this restriction is not waived just because the container is small. Only a narrow exception exists for very small cans of R-134a sold for motor vehicle air conditioning (which involves Section 609), not stationary equipment. A general DIY customer cannot buy restricted stationary refrigerant.

31. A technician plans to braze on a system. What is the correct sequence regarding the refrigerant charge before applying heat?
a.Recover the charge first, then braze✓
b.Vent the refrigerant quickly, then braze
c.Leave the charge in place; the heat will help it flow
d.Braze first, then recover whatever is left

Before brazing, the technician must recover the refrigerant and relieve system pressure so that no refrigerant remains where the flame will be applied, preventing toxic decomposition and dangerous pressure. Brazing first, leaving the charge in, or venting the refrigerant are all unsafe or illegal. Purging with dry nitrogen while brazing is also good practice to prevent oxidation inside the tubing.

32. A technician notices a disposable refrigerant cylinder labeled 'DOT-39.' What does this designation mean for handling?
a.It must be hydrostatically retested every 5 years
b.It may be refilled up to five times
c.It is a single-use cylinder, and it must never be refilled✓
d.It can be pressurized higher than a refillable cylinder

A DOT-39 cylinder is a single-use, non-refillable container, so it must never be refilled with recovered or virgin refrigerant. It is not requalified like a refillable DOT cylinder and refilling it is both dangerous and illegal. After the refrigerant heel is recovered, the empty cylinder should be disposed of according to local rules.

33. A technician recovering R-404A from a walk-in freezer notices the recovery cylinder is getting cold and recovery has slowed. What technique safely speeds recovery?
a.Vent some vapor to make room
b.Heat the recovery cylinder with a torch
c.Cool the recovery cylinder✓
d.Disconnect and let it finish on its own overnight

Recovery slows as the recovery cylinder warms and its pressure rises, so cooling the recovery cylinder and recovering liquid where possible lowers cylinder pressure and speeds the process. Using a torch is dangerous, venting vapor is illegal, and simply walking away does not complete recovery. Keeping the recovery cylinder cooler than the source lowers the pressure differential the machine must overcome.

34. A service company keeps invoices showing refrigerant added to and recovered from customer appliances. Under Section 608, these records are important because:
a.They are only used for marketing
b.They are optional and have no regulatory value
c.They must be destroyed after 30 days
d.EPA may request them to check compliance✓

Refrigerant service records let owners of appliances with 50 or more pounds calculate annual leak rates and let EPA verify compliance during inspections, so they carry real regulatory weight. They are not merely marketing documents, they are retained (generally three years) rather than destroyed after 30 days, and they are not optional for covered equipment. Accurate records protect both the owner and the servicing technician.

40 CFR §82.166
35. A technician is working with an A2L refrigerant such as R-32 or R-1234yf. What added safety consideration applies compared with older non-flammable HFCs?
a.They require no leak detection at all
b.No difference; treat them exactly like R-22
c.They are mildly flammable; control ignition✓
d.A2L refrigerants can be vented safely because they burn off

A2L refrigerants are mildly flammable, so technicians must keep ignition sources away, ensure ventilation, and follow the manufacturer's and applicable code safety requirements. Being flammable does not make them safe to vent, and they cannot be treated exactly like non-flammable R-22, nor do they excuse skipping leak detection. Proper handling of low-GWP flammable refrigerants is increasingly important as they replace higher-GWP HFCs.

36. A technician using self-contained (active) recovery equipment on a high-pressure system should connect and operate it so that:
a.Refrigerant is captured and the required vacuum reached✓
b.Oil and refrigerant are blown out to atmosphere first
c.Refrigerant vents through the machine to the outdoors
d.The machine runs without any recovery cylinder attached

Self-contained recovery equipment must be set up so recovered refrigerant is captured in an approved recovery cylinder and the appliance is evacuated to the level required for that equipment type. Venting through the machine, running with no cylinder attached, or blowing out oil and refrigerant would all release refrigerant illegally. Following the recovery machine's procedure ensures both compliance and safety.

40 CFR §82.156
37. Which statement about refrigerant and human health is correct?
a.Refrigerant vapor is nutritious and harmless to breathe
b.Dizziness and asphyxiation at high levels✓
c.Refrigerant improves lung function
d.Only liquid refrigerant is a concern, never the vapor

In high concentrations, refrigerant vapor displaces oxygen and can cause dizziness, loss of coordination, and asphyxiation, which is why ventilation and monitoring matter. Refrigerant vapor is not nutritious, does not improve lung function, and both vapor (asphyxiation) and liquid (frostbite) present hazards. Cardiac sensitization is another reason to avoid breathing high concentrations.

38. During a compressor burnout, a system contains acid-contaminated refrigerant. What is the proper handling?
a.Reuse it immediately without cleaning
b.Pour it down a floor drain
c.Recover it; then reclaim or destroy it✓
d.Vent it because contaminated refrigerant is exempt

Contaminated refrigerant is still regulated and must be recovered into a recovery cylinder rather than vented, then reclaimed to standard or destroyed as appropriate. It is not exempt from the venting prohibition, must never be poured down a drain, and should not be reused without proper cleaning that meets the purity standard. Acid-laden refrigerant from a burnout requires special filter-driers and often reclamation.

40 CFR §82.154
39. A large industrial owner chronically exceeds the leak rate threshold and cannot repair the system. Beyond repairs, what may the regulations require?
a.Only a verbal warning with no further action
b.Permission to vent until convenient
c.Doubling the refrigerant charge to compensate
d.A plan to retrofit or retire it✓

When repairs cannot bring a chronically leaking appliance below the threshold, the owner may be required to develop and follow a retrofit or retirement plan within a set timeframe to stop the ongoing emissions. A verbal warning, permission to vent, or overcharging the system are not acceptable outcomes. The rules aim to end chronic leaks rather than allow continued refrigerant loss.

40 CFR Part 82 Subpart F
40. A technician finishes a job and must dispose of used filter-driers and rags soaked with refrigerant oil. What is the responsible practice?
a.Pour any residual oil down a storm drain
b.Dispose of them under waste rules✓
c.Burn them on-site to save space
d.Toss them in the regular trash immediately

Used filter-driers and oil-soaked materials can be contaminated and must be handled and disposed of according to hazardous-waste and local regulations, not simply thrown in the trash. Burning them or pouring oil into a storm drain releases harmful substances into the environment. Following proper disposal rules protects both the technician and the public, complementing the refrigerant recovery requirements.

最近核对: · 审核流程

PrepPass 团队 · 依据官方资料核对 Clean Air Act §608 / 40 CFR Part 82 · 我们如何核对

EPA Section 608 Technician Certification Exam (Core, Type I, Type II, Type III / Universal) 考什么?

EPA Section 608 Technician Certification Exam (Core, Type I, Type II, Type III / Universal) 由 U.S. Environmental Protection Agency (EPA) 主办。下面的主题权重是 PrepPass 的估算,并非 U.S. Environmental Protection Agency (EPA) 公布的数字。

题目数量
50–100 道题
考试时限
US EPA 未公布
及格标准
70%

以上每项数字均附来源文件与查阅日期 →

考试大纲(按权重)

  • 25%
    Type I — Small Appliances
  • 25%
    Type II — High-Pressure
  • 25%
    Type III — Low-Pressure
  • 9%
    Core (Universal)
  • 8%
    Regulations & Safety
  • 8%
    Recovery & Recycling
PrepPass 团队 · 依据官方资料核对 U.S. Environmental Protection Agency (EPA) · 我们如何核对

这门考试有多难?

中等难度。EPA 608 分科目考——Core 加 Type I/II/III,每科 25 题,闭卷监考,70% 通过每一科。Core 偏概念(臭氧、法规),Type 各科考制冷剂实操。

推荐学习时间
10-25 小时;Universal(四科全考)复习量最大。
通过率
我们在 2026 年 9 月查阅了 EPA 自己公布的材料,其中没有通过率。它也无从公布:「EPA 不组织考试,也不签发成绩或认证卡。」考试由 EPA 认可的认证机构举办,因此没有任何联邦机构会看到可供统计的成绩。来源: EPA — Refrigerant Management Program: Questions and Answers for Section 608 Certified Technicians · EPA — Certification Programs for Section 608 Technicians
重点学习方向
Core 法规(臭氧、清洁空气法、回收)+ Type II 高压回收/抽真空——最常重考的科目。

费用与薪资为近似值,会随时间变动。上方的通过率引自旁边链接的来源,并限于该来源覆盖的期间——凡是我们尚未核实来源的,都会直接说明并且不给数字。

常见问题

How many EPA 608 practice questions are here?+

240 original practice questions across all four sections — Core, Type I (small appliances), Type II (high-pressure), and Type III (low-pressure) — plus recovery/recycling, in English and Español, with a 40 CFR Part 82 or Clean Air Act §608 citation on most answers.

Is this EPA 608 practice test free?+

Yes — completely free, no signup. Unlimited rounds, a full timed mock exam, and explanations included. The official EPA 608 certification exam (about $20-$100) is taken separately through an EPA-approved organization.

Are these real EPA 608 exam questions?+

No. All 240 questions are original prose written from the public-domain Clean Air Act Section 608 and 40 CFR Part 82. We never copy from any prep provider or the real exam.

How is the EPA 608 exam structured and what's the passing score?+

It has four sections — Core plus Type I, II, and III — 25 questions each, and you need 70% (about 18 of 25) to pass each. Passing Core plus all three types earns Universal certification. Core and the Type sections are proctored.

Does the EPA 608 certification expire?+

No — EPA Section 608 technician certification is valid for life and never expires.