A technician recovering from a small appliance notices the recovery cylinder is not pulling below atmospheric pressure. Which factor most likely prevents reaching the 4 inches Hg vacuum alternative?

a.The refrigerant is an HFC and cannot be recovered
b.Small appliances are exempt from vacuum requirements
c.A restriction, a closed valve, or a saturated cylinder is blocking full evacuation
d.The 4 inches Hg vacuum only applies to low-pressure chillers

解析

If a system will not pull into a vacuum, the usual causes are a restriction in the access path, a closed or partially opened valve, or a recovery cylinder that is full or at high pressure. The technician should check the connections, valves, and cylinder before assuming the appliance is empty. The 4 inches Hg vacuum is a valid recovery alternative for small appliances regardless of refrigerant type.

法律依据: 40 CFR §82.156

免费刷完整 240 道题库 — 无需注册。

同考点相关题目

最近核对: · 审核流程

PrepPass 编辑团队 · 依据官方资料核对 EPA Section 608 Technician Certification Exam · 我们如何核对
反馈