Type I — Small Appliances第 99 / 240 题
A vending machine repair company sends technicians to recover refrigerant from beverage coolers in the field. These sealed factory-charged coolers hold about 2 pounds of R-134a. Under Section 608 they are treated as:
a.Type II high-pressure appliances requiring 10 inches Hg vacuum
b.Small appliances subject to the 80%/90% (or 4 inches Hg) recovery rules
c.Low-pressure appliances requiring 25 mm Hg absolute
d.Motor vehicle air conditioners under Section 609
解析
Factory-sealed beverage vending machines and coolers holding five pounds or less of refrigerant are small appliances. Recovery must reach 80% (compressor off) or 90% (compressor on), or the alternative of 4 inches Hg vacuum. They are not Type II, Type III, or motor vehicle appliances.
法律依据: 40 CFR §82.156免费刷完整 240 道题库 — 无需注册。
同考点相关题目
- A technician is recovering from a small appliance using passive (system-dependent) equipment. To meet the required level, what must be achieved when the compressor is not operating?
- Which EPA technician certification allows a person to service and dispose of small appliances?
- A technician recharges a small window air conditioner after repair. Which practice helps ensure an accurate charge on a small sealed system?
- A technician connects recovery equipment to both the high and low sides of a small appliance during recovery. What is the main advantage of accessing both sides?
- Which appliance would NOT be recovered under the small-appliance rules?
- A technician recovering from a small appliance notices the recovery cylinder is not pulling below atmospheric pressure. Which factor most likely prevents reaching the 4 inches Hg vacuum alternative?