Which statement about pressurizing a low-pressure appliance for leak detection is correct?
a.The higher the pressure, the safer the test
b.Keep pressure at or below 10 psig at all times
c.Pressure up to the rupture-disk setting is fine
d.Use compressed air for convenience
解析
Leak-test pressure must stay at or below 10 psig to remain safely under the roughly 15 psig rupture disk. Approaching the disk setting or using compressed air is dangerous. Only dry nitrogen, sometimes with a trace of refrigerant, should be used.
免费刷完整 240 道题库 — 无需注册。
Own the complete EPA Section 608 Certification guide — PDF + EPUB, $14.99 →
同考点相关题目
- HCFC-123 requires good ventilation during service primarily because it:
- Before opening a low-pressure chiller to replace a failed tube bundle, the technician must:
- R-1233zd is increasingly used in modern low-pressure chillers because it:
- A recovery cylinder used for a large low-pressure chiller should be:
- During leak testing, some technicians raise the pressure in a low-pressure chiller just above atmospheric so that:
- Low-loss fittings on recovery hoses are important on low-pressure work because they: