Type III — Low-Pressure第 187 / 240 题

During leak testing, some technicians raise the pressure in a low-pressure chiller just above atmospheric so that:

a.The rupture disk will vent
b.The refrigerant condenses faster
c.An electronic detector or bubble test can find the leak
d.The purge unit can be shut off permanently

解析

Because the chiller normally runs in a vacuum, a leak pulls air in rather than out, so a detector cannot sense escaping refrigerant. Raising pressure slightly above atmospheric, staying under 10 psig, makes refrigerant flow outward at the leak so it can be found. The pressure must never approach the rupture-disk setting.