During recovery from a small appliance with a working compressor, a technician can only reach 82% recovery before the unit stops pulling down. What should the technician do to comply?

a.Stop, because 82% already exceeds the 80% minimum for this case
b.Continue with self-contained equipment until at least 90% is recovered or 4 inches Hg vacuum is reached
c.Vent the remaining refrigerant since it is below 5 pounds
d.Recover only to 75% and record it as complete

解析

With the compressor operating, the required recovery level for a small appliance is 90%, not 80%, so 82% is not enough. The technician should keep recovering with self-contained equipment until 90% is achieved or the alternative 4 inches Hg vacuum is reached. Venting any remaining refrigerant is prohibited regardless of the small charge.

法律依据: 40 CFR §82.156