An indoor dry-type transformer rated 45 kVA with standard (Class 105) insulation must maintain what minimum separation from combustible material unless otherwise protected?

  • a.18 in
  • b.3 in
  • c.12 in✓
  • d.6 in

2023 NEC 450.21(A): dry-type transformers 112.5 kVA and under must be separated at least 12 in from combustible material unless the unit has a listed fire-resistant barrier or Class 155 (or higher) insulation.

Advanced Wiring

Which value from a motor nameplate must be used with the tables to size branch-circuit short-circuit protection and conductors, per 430.6(A)?

  • a.the nameplate full-load amperes
  • b.the service-factor amps
  • c.the locked-rotor current
  • d.the table full-load current, not the nameplate current rating✓

2023 NEC 430.6(A)(1): for general motor applications, the full-load current values in Tables 430.247-430.250 (not the nameplate FLA) are used to size conductors and short-circuit/ground-fault protection. Overload protection uses the nameplate FLA.

Advanced Wiring

The disconnecting means for air-conditioning or refrigerating equipment with a motor-compressor must be located:

  • a.only at the main service panel
  • b.inside a locked mechanical room only
  • c.at least 25 ft away
  • d.within sight from and readily accessible from the equipment✓

2023 NEC 440.14: the disconnect must be within sight from, and readily accessible from, the air-conditioning or refrigerating equipment.

Advanced Wiring

How many overload (running-protection) units are required for a three-phase alternating-current motor?

  • a.one
  • b.three✓
  • c.four
  • d.two

2023 NEC Table 430.37: a three-phase AC motor requires three overload units, one in each phase.

Advanced Wiring

In patient care spaces, grounding of receptacles and fixed electrical equipment must be accomplished by:

  • a.an isolated ground only
  • b.the metal raceway alone as the only ground path
  • c.the grounded (neutral) conductor
  • d.an insulated copper equipment grounding conductor plus a metal raceway or cable armor (redundant ground)✓

2023 NEC 517.13: patient care spaces require redundant grounding - an insulated copper EGC AND a metallic raceway or cable that itself qualifies as a grounding path.

Advanced Wiring

The disconnecting means for a motor must have an ampere rating of at least what percentage of the motor full-load current?

  • a.115%✓
  • b.125%
  • c.100%
  • d.110%

2023 NEC 430.110(A): the disconnecting means for a motor circuit must be rated at least 115% of the motor full-load current.

这门考试有多难?

电工技师(Master)执照由各州主办、以 NEC 为依据,因此格式因州而异。例如在德州,考试分两个开卷部分(2023 NEC)——75 道 NEC 知识题与 33 道计算题(共 108 题)——各须 70% 方可通过,费用 78 美元。电工年薪中位数约 62,350 美元(BLS,2024 年 5 月)。

推荐学习时间
多数人 80-150 小时——技师考试比熟练工增加更重的计算与规范应用深度。
官方公布的通过率
19.08% (来源未说明统计的是哪些考次)(n = 3,946);22.21% (来源未说明统计的是哪些考次)(n = 3,472) —— Texas TDLR,FY 2025。请把它们看作两场考试而非一场:TDLR 并没有名为「Master Electrician」的行,只有「Master Calculations」(第一个数字)和「Master NEC」(第二个数字)。任何引用单一「德州 master 通过率 19%」的说法,都悄悄丢掉了一半考试。执照按州发放,因此这只适用于德州。来源: Texas TDLR — Electrician Exam Statistics, Fiscal Year 2025
重点学习方向
服务、服务设备与单独派生系统是最重的板块之一(德州约 18%),外加负载计算部分。