Branch Circuits, Feeders, Conductor Sizing and Overcurrent Protection
This is the largest and most calculation-heavy block on the journeyman exam, and almost every question comes down to the same chain of reasoning: find the load, apply the continuous-load multiplier, pick a conductor from the ampacity table, adjust it for heat, then choose an overcurrent device. Master that sequence and you will answer branch-circuit, feeder and voltage-drop questions with the same handful of moves.
Loads, Continuous Loads and the 125 Percent Rule
A continuous load is one expected to run at its maximum current for three hours or more, which describes most commercial lighting, sign circuits and electric heat. Both the conductor and the overcurrent device must be sized at the noncontinuous load plus 125 percent of the continuous load, because standard breakers and terminations are not tested to carry their full rating indefinitely. Noncontinuous loads are added in at 100 percent, so a mixed circuit gets the multiplier applied only to the continuous portion.
Reading the Ampacity Table and Respecting Termination Temperature
Table 310.16 gives the allowable ampacity of insulated conductors in a raceway, cable or earth at a 30 degrees C ambient with not more than three current-carrying conductors. The column you finish in is set by the temperature rating of the terminations, not by the insulation printed on the wire, so a 90 degrees C THHN conductor landing on a 75 degrees C lug is limited to the 75 degrees C column. The higher column may still be used as the starting point for derating calculations, which is the single most misunderstood idea in conductor sizing.
Derating: Ambient Temperature and More Than Three Conductors
Two independent penalties can apply to the same run, and when both apply you multiply them together against the ampacity read from the column matching the conductor insulation. Ambient correction handles hot attics, boiler rooms and rooftops, while the adjustment factor handles the heat that conductors bundled in one raceway impose on each other. After multiplying, the result must still be checked against the termination temperature limit and against the small-conductor protection rules.
Voltage Drop Calculations
Voltage drop is not an enforceable requirement for most branch circuits, but it is a heavily tested calculation because it is the one place the exam asks you to work with conductor resistance directly. The standard approach uses the constant K, roughly 12.9 for copper and 21.2 for aluminum, together with the circular-mil area of the conductor from Chapter 9, Table 8. The recommended targets are 3 percent on a branch circuit and 5 percent for the combined feeder and branch circuit.
Dwelling Branch-Circuit Requirements
Residential branch-circuit questions test a small set of memorized numbers rather than calculations, and they show up on every exam. The theme is that certain rooms get dedicated circuits so that a single appliance cannot black out the rest of the house, and that receptacles are spaced so a 6-foot cord always reaches. GFCI and AFCI requirements have expanded steadily and now cover most of a dwelling.
Last updated: July 2026