Chapter 2 of 14

Air Distribution

Air distribution is the largest area on the Environmental Air exams. It covers airflow arithmetic, duct sizing with a duct calculator and Manual D, static pressure, filters, grilles and the code rules for ducts and plenums.

The arithmetic

Velocity is airflow divided by duct area in square feet. Sensible heat is 1.08 times CFM times the temperature difference for standard air. Total external static pressure is the supply and return readings added without regard to sign. The fan laws say airflow follows speed, pressure follows speed squared, and power follows speed cubed.

Friction rate
Available static pressure times 100, divided by total effective length. Available static pressure is the blower's external static pressure less the coil, filter, grille and other component drops.
ACCA Manual D
Total effective length
Measured straight length of the longest supply and return runs plus the equivalent length of every fitting in them.
ACCA Manual D

Code points

Return air may not be drawn from bathrooms, kitchens, garages, closets or mechanical rooms. Materials exposed in plenums are limited by flame spread and smoke-developed indexes. Tapes and mastics on flexible duct must be listed to UL 181B. A return air smoke detector is required above a stated system capacity. Look these up by section number rather than relying on memory.

Return air sources
Prohibited locations are listed in the return air section.
IMC §601.5
Smoke detection
Required in return air systems with a design capacity greater than 2,000 CFM.
IMC §606.2.1