Air Distribution
Air distribution is the largest area on the Environmental Air exams. It covers airflow arithmetic, duct sizing with a duct calculator and Manual D, static pressure, filters, grilles and the code rules for ducts and plenums.
The arithmetic
Velocity is airflow divided by duct area in square feet. Sensible heat is 1.08 times CFM times the temperature difference for standard air. Total external static pressure is the supply and return readings added without regard to sign. The fan laws say airflow follows speed, pressure follows speed squared, and power follows speed cubed.
Code points
Return air may not be drawn from bathrooms, kitchens, garages, closets or mechanical rooms. Materials exposed in plenums are limited by flame spread and smoke-developed indexes. Tapes and mastics on flexible duct must be listed to UL 181B. A return air smoke detector is required above a stated system capacity. Look these up by section number rather than relying on memory.