Air Distribution
Which return air location does the mechanical code prohibit for a residential forced-air system (IMC §601.5)?
- AA living room
- BA bathroomCorrect
- CA dining room
- DA hallway
Why: Return air may not be taken from a bathroom, toilet room, kitchen, garage, closet, mechanical room, or boiler room, because odors, moisture, or combustion products would be spread through the building. Hallways and living areas are normal return locations.IMC §601.5
Texas Laws and Rules
A contractor holds a Class B license with the environmental air conditioning endorsement. Under Occupations Code §1302.253, which single cooling unit is the largest this contractor may install?
- AA unit of 50 tons cooling capacity
- BA unit of 15 tons cooling capacity
- CA unit of 25 tons cooling capacityCorrect
- DA unit of any cooling capacity
Why: §1302.253 limits a Class B license to cooling systems of 25 tons or less and heating systems of 1.5 million Btu/h or less. Fifteen tons is allowed but is not the ceiling, 50 tons is beyond it, and work on a unit of any size is what a Class A license allows.Tex. Occ. Code §1302.253