Chapter 3 of 14

Basic Refrigeration Components

The four parts every system has are the compressor, condenser, metering device and evaporator. Questions ask what each one does, what state the refrigerant is in at each point, and what the accessories around them are for.

Follow the refrigerant

High-pressure superheated vapor leaves the compressor, becomes subcooled liquid in the condenser, drops in pressure through the metering device, and boils in the evaporator before returning as superheated vapor. A thermostatic expansion valve controls superheat using a bulb on the suction line at the evaporator outlet; capillary tubes and pistons are fixed restrictions. Receivers store liquid on expansion valve systems, accumulators protect the compressor from liquid, and filter-driers remove moisture, acid and solids.

Refrigerant safety groups
Letter A or B is toxicity; 1, 2L, 2 or 3 is flammability. R-410A is A1; R-32 and R-454B are A2L. Texas reads the adopted codes with the 2024 editions of ASHRAE 15 and 34.
ASHRAE Standard 34; 16 TAC §75.110(c)