Texas Air Conditioning and Refrigeration Contractor Exam — All Questions
18 questions
In a vapor-compression system, the refrigerant leaves the compressor as a:
- a.High-pressure, low-temperature subcooled liquid
- b.Low-pressure, low-temperature saturated vapor
- c.Low-pressure, high-temperature superheated liquid
- d.High-pressure, high-temperature superheated vapor✓
The compressor raises the pressure and temperature of vapor, so discharge gas is high-pressure superheated vapor. Subcooled liquid is found leaving the condenser, and low-pressure vapor is what enters the compressor.
The main job of the condenser is to:
- a.Raise the pressure of the vapor leaving the evaporator
- b.Drop the pressure of the liquid ahead of the evaporator
- c.Reject heat so the high-pressure vapor becomes a liquid✓
- d.Absorb heat so the low-pressure liquid becomes a vapor
The condenser desuperheats, condenses and usually subcools the refrigerant by rejecting heat to air or water. Absorbing heat is the evaporator's job, dropping pressure is the metering device's, and raising pressure is the compressor's.
Which metering device modulates refrigerant flow to hold a set superheat at the evaporator outlet?
- a.Thermostatic expansion valve✓
- b.Capillary tube
- c.Automatic (constant-pressure) expansion valve
- d.Fixed-bore piston
A thermostatic expansion valve senses suction line temperature with its bulb and adjusts flow to maintain superheat. Capillary tubes and pistons are fixed restrictions, and an automatic expansion valve holds a constant evaporator pressure rather than superheat.
Where is the sensing bulb of a thermostatic expansion valve mounted?
- a.On the discharge line at the compressor
- b.On the distributor at the evaporator inlet
- c.On the liquid line at the condenser outlet
- d.On the suction line at the evaporator outlet✓
The bulb reads the temperature of vapor leaving the evaporator so the valve can control superheat. It must be clamped tight to clean suction line and insulated; mounting it anywhere else gives the valve a false signal.
An externally equalized expansion valve is used on an evaporator that has:
- a.A very small pressure drop, such as a short single-circuit coil
- b.A significant pressure drop, such as a coil with a distributor✓
- c.A flooded design with a low-side float and a surge drum
- d.A capillary tube feeding each of its parallel circuits
The external equalizer line brings evaporator outlet pressure to the underside of the diaphragm so that pressure drop through the distributor and coil does not make the valve starve the coil. Small single-circuit coils work with internal equalization.
Which compressor type compresses vapor between one fixed and one orbiting spiral?
- a.Rotary vane
- b.Centrifugal
- c.Reciprocating
- d.Scroll✓
A scroll compressor traps gas in pockets between a stationary and an orbiting scroll and squeezes it toward the center. Reciprocating compressors use pistons, rotary compressors use a rolling piston or vanes, and centrifugal machines use impeller speed.
Why is liquid refrigerant returning to a reciprocating compressor harmful?
- a.Liquid lowers the discharge pressure and stalls the motor at start-up
- b.Liquid raises the superheat and overheats the windings
- c.Liquid freezes in the cylinders and blocks the valves
- d.Liquid cannot be compressed and it washes oil from the bearings✓
Liquid floodback dilutes and washes away oil, and a slug of liquid in a cylinder can break valves, rods or the crankshaft because liquid does not compress. Floodback shows up as low or zero superheat, not high superheat.
The purpose of a crankcase heater is to:
- a.Warm the suction gas to raise the superheat at start-up
- b.Dry any moisture out of the motor windings before start
- c.Keep refrigerant from condensing in the oil during the off cycle✓
- d.Keep the oil thin enough to be pumped back through the suction line
During the off cycle refrigerant migrates to the coldest part of the system, often the compressor crankcase. The heater keeps the oil warmer than the rest of the system so refrigerant does not collect there and cause foaming and a flooded start.
A filter-drier in the liquid line removes:
- a.Moisture, acid and solid particles✓
- b.Flash gas ahead of the metering device
- c.Oil, wax and excess refrigerant
- d.Air and other noncondensable gases
The desiccant core adsorbs moisture and acid and the filter traps solids. A drier does not remove noncondensables, which must be evacuated or purged, and it does not remove oil, which has to circulate.
Where does a suction line accumulator sit, and what does it do?
- a.Between condenser and metering device; it stores liquid for varying loads
- b.Between metering device and evaporator; it divides flow among circuits
- c.Between compressor and condenser; it separates oil from discharge vapor
- d.Between evaporator and compressor; it traps liquid so only vapor returns✓
The accumulator is in the suction line and catches liquid refrigerant, metering it back as vapor with oil. A receiver stores liquid after the condenser, an oil separator is in the discharge line, and a distributor feeds evaporator circuits.
A liquid receiver is normally found on systems that use:
- a.A capillary tube
- b.A thermostatic expansion valve✓
- c.A fixed-orifice piston
- d.A critically charged fixed-restriction coil
Expansion valve systems vary the amount of refrigerant in the evaporator with load, and the receiver stores the difference. Fixed-restriction systems are critically charged and normally have no receiver, since extra liquid would flood the evaporator.
In a heat pump, the component that changes the system between heating and cooling is the:
- a.Four-way reversing valve✓
- b.Check valve at the piston
- c.Bi-flow filter-drier
- d.Defrost control board
The reversing valve redirects discharge gas to either the outdoor or indoor coil, swapping which one is the condenser. Check valves and bi-flow driers let the system work in both directions, and the defrost board decides when to switch, but the valve does the switching.
R-410A is classed by ASHRAE Standard 34 as A1. What do the letter and number indicate?
- a.Lower toxicity and no flame propagation✓
- b.Higher toxicity and no flame propagation
- c.Higher toxicity and higher flammability
- d.Lower toxicity and lower flammability
In the safety classification, A means lower toxicity and B higher toxicity; 1 means no flame propagation, 2L and 2 lower flammability, and 3 higher flammability. A1 is therefore the least hazardous group.ASHRAE Standard 34
R-32 and R-454B, used in newer comfort cooling equipment, carry which ASHRAE Standard 34 safety classification?
- a.A1
- b.B2L
- c.A3
- d.A2L✓
R-32 and R-454B are A2L: lower toxicity with lower flammability and a low burning velocity. A1 refrigerants such as R-410A do not propagate flame, B2L includes ammonia, and A3 covers hydrocarbons such as propane.ASHRAE Standard 34
A blended refrigerant with a noticeable temperature glide should be charged into a system:
- a.As a liquid or a vapor, since the blend does not separate
- b.As a vapor, so the blend's composition does not change
- c.As a vapor, so the compressor is not slugged at start-up
- d.As a liquid, so the blend's composition does not change✓
Zeotropic blends fractionate: vapor leaving the cylinder is richer in the more volatile components. Removing liquid keeps the composition correct. Liquid is throttled into the suction side to protect the compressor.
What is the effect of a dirty air-cooled condenser coil?
- a.Head pressure and compressor amperage both rise✓
- b.Head pressure and compressor amperage both fall
- c.Head pressure falls and suction pressure rises
- d.Head pressure rises and compressor amperage falls
A dirty condenser cannot reject heat, so condensing temperature and pressure climb. The compressor works against a higher pressure, draws more current, and loses capacity.
An evaporator used for comfort cooling in which refrigerant boils inside the tubes and is fully vaporized before the outlet is called a:
- a.Plate heat exchanger
- b.Direct-expansion evaporator✓
- c.Flooded evaporator
- d.Shell-and-tube water-cooled condenser
A direct-expansion (dry) evaporator is fed by a metering device and has superheated vapor at its outlet. A flooded evaporator keeps the tubes wet with liquid and uses a float or level control.
On a water-cooled condensing unit, a water regulating valve controls flow in response to:
- a.Suction pressure
- b.Oil pressure
- c.Water pressure
- d.Head pressure✓
The valve opens as head pressure rises and closes as it falls, holding condensing pressure and saving water. It shuts when the compressor stops and head pressure drops.