Texas Air Conditioning and Refrigeration Contractor Exam — All Questions

24 questions

HVAC and HVACR Systems

In a split system, which components are in the outdoor section?

  • a.Metering device and evaporator
  • b.Furnace and filter rack
  • c.Evaporator coil and blower
  • d.Compressor and condenser coil✓

The condensing unit outdoors holds the compressor, condenser coil and condenser fan. The evaporator, metering device and blower are indoors, joined by the liquid and suction lines.

HVAC and HVACR Systems

A packaged rooftop unit differs from a split system in that:

  • a.It cannot be equipped with gas heat
  • b.It needs field-installed refrigerant lines
  • c.All refrigeration components are in one cabinet✓
  • d.The compressor is located indoors with the air handler

A package unit is factory charged and contains compressor, both coils and blower in one cabinet connected to the building by ducts. Many include gas heat.

HVAC and HVACR Systems

In heating mode, the indoor coil of an air-source heat pump acts as the:

  • a.Condenser✓
  • b.Accumulator
  • c.Evaporator
  • d.Receiver

In heating the reversing valve sends hot discharge gas to the indoor coil, which rejects heat to the house and is therefore the condenser. The outdoor coil becomes the evaporator.

HVAC and HVACR Systems

During the defrost cycle of an air-source heat pump, the system:

  • a.Runs in heating mode with the outdoor fan on
  • b.Runs the indoor blower with the compressor off
  • c.Shuts the compressor off until the ice melts
  • d.Runs in cooling mode with the outdoor fan off✓

Defrost reverses the cycle so hot gas goes to the outdoor coil, and the outdoor fan stops so the coil warms quickly. Auxiliary heat is energized to temper the cool air delivered indoors.

HVAC and HVACR Systems

A suction line that rises vertically from an evaporator below the compressor needs an oil trap at the bottom of the riser to:

  • a.Keep liquid refrigerant from reaching the evaporator
  • b.Stop vibration from travelling along the suction line
  • c.Help carry oil up the riser back to the compressor✓
  • d.Hold a reserve of refrigerant for periods of high load

Oil collects at the base of a vertical suction riser; a trap lets vapor velocity pick the oil up and carry it upward. Without proper velocity and trapping, oil stays in the low side and the compressor runs short.

HVAC and HVACR Systems

Horizontal suction lines are pitched slightly:

  • a.Toward the compressor, to help oil return✓
  • b.Upward at both ends, to form a liquid seal
  • c.Level in all cases, to keep the velocity even
  • d.Toward the evaporator, to drain the oil back

Sloping horizontal suction runs in the direction of flow lets gravity help move oil to the compressor. Pitching back to the evaporator would log oil in the coil.

HVAC and HVACR Systems

Which line of a split system is insulated, and why?

  • a.The suction line, to limit heat gain and stop sweating✓
  • b.The liquid line, to limit heat loss and stop sweating
  • c.The discharge line, to protect the outdoor fan motor
  • d.The condensate line, to keep the trap from drying out

The cold suction line would pick up heat, raising superheat and compressor temperature, and would drip condensation. The liquid line is normally left bare unless it runs through a very hot space.

HVAC and HVACR Systems

Which defrost method is commonly used on a medium-temperature walk-in cooler held at about 38°F?

  • a.Off-cycle defrost using box air✓
  • b.Electric defrost with a drain heater
  • c.Hot gas defrost with a reversing valve
  • d.Water defrost with a spray header

When the box is above freezing, simply stopping refrigeration with the evaporator fans running lets box air melt the frost. Low-temperature freezers need electric or hot gas defrost because the box air is below 32°F.

HVAC and HVACR Systems

On a low-temperature freezer evaporator with electric defrost, the fan delay control:

  • a.Keeps the fans on during defrost to speed the melting of ice
  • b.Keeps the fans off until the coil is cold again after defrost✓
  • c.Keeps the compressor off until the box reaches setpoint
  • d.Keeps the heaters on until the fans have reached full speed

After defrost the coil is warm and wet. The fan delay holds the fans off until the coil drops below freezing so warm air and water droplets are not blown onto the product.

HVAC and HVACR Systems

An evaporator pressure regulator (EPR) valve is installed to:

  • a.Keep head pressure from falling during cold weather
  • b.Keep liquid from flashing ahead of the metering device
  • c.Keep evaporator pressure from falling below a set point✓
  • d.Keep crankcase pressure from rising above a set point

An EPR sits in the suction line at the evaporator outlet and holds a minimum evaporator pressure, which lets a warmer evaporator share a compressor with colder ones. Limiting pressure at the compressor inlet is the job of a crankcase pressure regulator.

HVAC and HVACR Systems

A crankcase pressure regulator (CPR) valve protects the compressor by:

  • a.Limiting suction pressure at the compressor during a hot pull-down✓
  • b.Limiting discharge pressure at the compressor during a high ambient
  • c.Raising suction pressure at the compressor during a light load
  • d.Raising oil pressure at the compressor during a cold start

The CPR throttles the suction line near the compressor so the motor is not overloaded by high suction pressure after defrost or on start-up with a warm box.

HVAC and HVACR Systems

Hot gas bypass is used on some systems to:

  • a.Keep head pressure down at high load and prevent tripping
  • b.Recover heat from the discharge gas to warm domestic water
  • c.Return oil from the oil separator to the compressor crankcase
  • d.Keep suction pressure up at low load and prevent coil icing✓

Bypassing some discharge gas to the low side adds a false load so the compressor can keep running at light load without the evaporator dropping below freezing. It is a capacity control method.

HVAC and HVACR Systems

In a chilled-water system, the chiller's evaporator cools:

  • a.Water that is pumped to air handler coils✓
  • b.Air that is ducted directly to the rooms
  • c.Refrigerant returning from remote coils
  • d.Water that is pumped to the cooling tower

The chiller evaporator (cooler) chills water, typically from about 54°F to 44°F, and pumps circulate it to coils in air handlers and fan coils. The cooling tower handles condenser water, a separate loop.

HVAC and HVACR Systems

A cooling tower rejects heat mainly by:

  • a.Radiating heat from the tower's metal casing
  • b.Conducting heat to the makeup water supply
  • c.Evaporating a small part of the condenser water✓
  • d.Compressing water vapor inside the tower fill

Most of a tower's heat rejection is evaporative: as a small fraction of the water evaporates, it cools the rest. This is why tower performance depends on the entering air's wet-bulb temperature.

HVAC and HVACR Systems

Water enters a cooling tower at 95°F and leaves at 85°F when the entering air wet-bulb temperature is 78°F. The tower's approach is:

  • a.17°F
  • b.7°F✓
  • c.85°F
  • d.10°F

Approach is leaving water temperature minus entering wet-bulb: 85 minus 78 is 7°F. The 10°F difference between entering and leaving water is the range.

HVAC and HVACR Systems

A variable air volume (VAV) system controls space temperature by:

  • a.Cycling the supply fan on and off for each individual zone
  • b.Mixing hot and cold airstreams at each zone's terminal box
  • c.Varying the temperature of supply air delivered to each zone
  • d.Varying the amount of supply air delivered to each zone✓

A VAV box throttles airflow at a roughly constant supply air temperature. Varying supply temperature at constant volume describes a constant-volume reheat system, and mixing two airstreams describes a dual-duct system.

HVAC and HVACR Systems

In a variable refrigerant flow (VRF) system, capacity is matched to load mainly by:

  • a.Cycling a single-speed compressor on a room thermostat
  • b.Varying chilled-water flow with two-way control valves
  • c.Varying compressor speed and indoor unit refrigerant flow✓
  • d.Opening outdoor air dampers on each indoor unit

VRF systems use inverter-driven compressors and electronic expansion valves at each indoor unit to modulate refrigerant flow. They are direct-expansion systems and use no chilled water.

HVAC and HVACR Systems

A cascade refrigeration system is used to:

  • a.Reach higher efficiency by putting two condensers in series
  • b.Recover heat from one zone and deliver it to another
  • c.Serve several evaporators from one large compressor
  • d.Reach very low temperatures with two refrigerant circuits✓

In a cascade system the evaporator of the high-stage circuit cools the condenser of the low-stage circuit, so each compressor works at a reasonable compression ratio while reaching very low temperatures.

HVAC and HVACR Systems

Liquid line sight glass shows bubbles on a system with a receiver and a thermostatic expansion valve. This may indicate:

  • a.A high refrigerant charge or a dirty evaporator
  • b.A low refrigerant charge or a restriction upstream✓
  • c.A failed crankcase heater on the compressor
  • d.A high superheat setting at the expansion valve

Bubbles mean vapor in the liquid line, from a short charge or a pressure drop such as a plugged drier ahead of the glass. The sight glass's moisture indicator separately shows whether the system is dry.

HVAC and HVACR Systems

On a parallel-rack supermarket system, the compressors are staged to maintain:

  • a.A common discharge temperature
  • b.A common suction pressure✓
  • c.A common box temperature
  • d.A common oil temperature

Rack compressors share suction and discharge headers and are cycled or unloaded to hold suction pressure for the coldest evaporators in the group. Individual cases use EPR valves or solenoids for their own temperature control.

HVAC and HVACR Systems

After new refrigerant piping is brazed, why is the system evacuated before charging?

  • a.To remove flux and oxide scale
  • b.To test joints for strength
  • c.To remove air and moisture✓
  • d.To cool the brazed joints

A deep vacuum lowers the boiling point of water so moisture leaves as vapor and removes noncondensable air. Oxide scale is prevented by flowing nitrogen while brazing, and joint tightness is checked by a pressure test.

HVAC and HVACR Systems

Why is dry nitrogen flowed through copper tubing at low pressure while brazing?

  • a.To keep oxide scale from forming inside the tube✓
  • b.To blow excess filler metal out of the fitting
  • c.To test the completed joint for refrigerant leaks
  • d.To raise the temperature of the joint more quickly

Heating copper in air forms black copper oxide on the inside wall, which later flakes off and plugs driers and metering devices. A slow nitrogen purge displaces the oxygen.

HVAC and HVACR Systems

A hydronic heating system uses an expansion tank to:

  • a.Separate dissolved air from the water as it circulates
  • b.Absorb the increase in water volume as the water heats✓
  • c.Raise system pressure enough to lift water to the top
  • d.Store hot water for use at times of peak demand

Water expands when heated; the tank's air cushion takes up that volume so system pressure does not rise enough to open the relief valve. Air removal is the job of an air separator or vent.

HVAC and HVACR Systems

In most single-zone ductless mini-splits, the electronic expansion valve that meters refrigerant to the indoor unit is located:

  • a.In the outdoor unit, so both lines to the indoor unit are cold in cooling✓
  • b.In the indoor unit, so the liquid line to the indoor unit stays warm
  • c.At the service valve, so neither line needs to be insulated
  • d.In the branch box, so that only the larger suction line needs to be insulated

Most mini-splits meter at the outdoor unit, so the "liquid" line leaving it is already cold, low-pressure refrigerant. That is why both lines of a mini-split line set are insulated.