Texas Air Conditioning and Refrigeration Contractor Exam — All Questions
6 questions
Under IMC §504, the maximum length of a 4-inch clothes dryer exhaust duct, before deductions for fittings and absent manufacturer's instructions that allow more, is:
- a.50 feet
- b.15 feet
- c.25 feet
- d.35 feet✓
The code's default limit is 35 feet from the dryer connection to the outlet terminal, reduced for each elbow. A longer run is allowed only where the dryer manufacturer's instructions permit it.IMC §504
Why may sheet metal screws not protrude into a dryer exhaust duct more than 1/8 inch?
- a.They void the listing of the backdraft damper
- b.They corrode quickly in the hot, moist exhaust air
- c.They catch lint, which restricts flow and can ignite✓
- d.They loosen from vibration and let the joints leak
Fasteners sticking into the airstream snag lint. Built-up lint cuts airflow, lengthens drying time and is a fire hazard. Joints run in the direction of airflow for the same reason.IMC §504
A dryer exhaust duct must terminate:
- a.In the attic, at least 3 feet from the roof deck
- b.Outdoors, with a backdraft damper and no screen✓
- c.In the crawl space, with a lint trap at the end
- d.Outdoors, with a fine screen over the opening
Dryer exhaust goes to the outdoors and the termination has a backdraft damper. Screens are prohibited because they clog with lint. Discharging into an attic or crawl space adds moisture and lint to the building.IMC §504
A flexible transition duct between a dryer and the exhaust duct must be:
- a.A foil duct run through the floor to the crawl space vent
- b.Any plastic duct that is no longer than twelve feet overall
- c.Two listed lengths joined inside the wall behind the dryer
- d.A single listed length that is not concealed in construction✓
The transition duct is one listed and labeled piece, limited in length, and it may not be concealed within construction. The concealed portion of the run must be rigid metal duct.IMC §504
A Category I gas appliance vents with:
- a.Positive vent pressure and flue gas hot enough to avoid condensation
- b.Non-positive vent pressure and flue gas cool enough to condense
- c.Positive vent pressure and flue gas cool enough to condense
- d.Non-positive vent pressure and flue gas hot enough to avoid condensation✓
Category I appliances, such as draft-hood and fan-assisted 80% furnaces, operate with non-positive vent static pressure and do not condense in the vent, so Type B vent is used. Category IV appliances are positive pressure and condensing.IFGC §202
A single-wall or Type B vent connector from a draft-hood appliance must slope:
- a.Downward toward the vent at least 1/4 inch per foot
- b.Level, with a drip tee at the base of the vent
- c.Upward toward the vent at least 1/4 inch per foot✓
- d.Upward toward the appliance at least 1/8 inch per foot
Vent connectors rise toward the vent or chimney at not less than 1/4 inch per foot with no dips or sags, so buoyant flue gas flows upward and condensate does not pool.IFGC §503.10