Texas Air Conditioning and Refrigeration Contractor Exam — All Questions

18 questions

Safety

Under 29 CFR 1904.39, an employer must report a work-related fatality to OSHA within:

  • a.8 hours✓
  • b.7 days
  • c.48 hours
  • d.24 hours

A fatality must be reported within 8 hours. Twenty-four hours is the deadline for an inpatient hospitalization, amputation or loss of an eye; seven calendar days is the time allowed to enter a recordable case on the log.29 CFR 1904.39

Safety

An employee is admitted to the hospital as an inpatient after a fall from a rooftop unit. Under 29 CFR 1904.39, the employer must report it to OSHA within:

  • a.24 hours✓
  • b.30 days
  • c.8 hours
  • d.72 hours

Inpatient hospitalization, amputation, and loss of an eye are reported within 24 hours of the employer learning of them. The 8-hour limit applies to a fatality.29 CFR 1904.39

Safety

Which OSHA form is the Log of Work-Related Injuries and Illnesses?

  • a.Form 170
  • b.Form 300✓
  • c.Form 301
  • d.Form 300A

Form 300 is the log, Form 300A is the annual summary that is posted, and Form 301 is the incident report completed for each recordable case.29 CFR 1904.29

Safety

Under 29 CFR 1904.32, the annual summary (Form 300A) must be posted in the workplace from:

  • a.January 1 through March 31
  • b.March 1 through May 31
  • c.January 1 through December 31
  • d.February 1 through April 30✓

The summary of the previous year's cases is posted from February 1 to April 30 where employee notices are normally placed, after a company executive certifies it.29 CFR 1904.32

Safety

Under 29 CFR 1904.33, the OSHA 300 log and related records must be kept for:

  • a.5 years after the year they cover✓
  • b.3 years after the year they cover
  • c.1 year after the year they cover
  • d.10 years after the year they cover

Records are saved for five years following the end of the calendar year they cover, and the log is updated during that time if cases change.29 CFR 1904.33

Safety

Under 29 CFR 1904.29, a recordable injury must be entered on the OSHA 300 log within:

  • a.7 calendar days of learning of it✓
  • b.8 hours of learning of it
  • c.30 calendar days of learning of it
  • d.24 hours of learning of it

The employer has seven calendar days after receiving information that a recordable case occurred. The 8-hour and 24-hour limits are reporting deadlines for severe events, not log entry deadlines.29 CFR 1904.29(b)(3)

Safety

Under 29 CFR 1904.1, a company is partially exempt from keeping OSHA injury and illness records if, at all times in the last calendar year, it had no more than:

  • a.50 employees
  • b.100 employees
  • c.10 employees✓
  • d.25 employees

Companies with ten or fewer employees at all times during the previous year need not keep the records unless OSHA or the Bureau of Labor Statistics asks in writing. They must still report fatalities and severe injuries.29 CFR 1904.1

Safety

Which case is recordable on the OSHA 300 log under 29 CFR 1904.7?

  • a.A cut that is cleaned and bandaged on site
  • b.A bruise treated with an ice pack at the shop
  • c.A visit to a doctor for observation only
  • d.A cut that requires stitches at a clinic✓

A work-related injury is recordable when it results in medical treatment beyond first aid, days away, restricted work, loss of consciousness, or death. Sutures are medical treatment; bandages, cold packs and observation visits are first aid or diagnostic.29 CFR 1904.7

Safety

A refillable recovery cylinder must not be filled beyond what percent of its capacity by weight?

  • a.100%
  • b.80%✓
  • c.90%
  • d.60%

Liquid refrigerant expands as it warms. Leaving 20% vapor space keeps the cylinder from becoming liquid-full and rupturing. A scale or a float switch is used to control the fill.

Safety

Which gas must never be used to pressurize a refrigeration system for leak testing?

  • a.Nitrogen
  • b.Oxygen✓
  • c.Helium
  • d.Carbon dioxide

Oxygen or compressed air mixed with refrigerant oil under pressure can explode. Dry nitrogen through a pressure regulator, with a relief valve downstream, is the standard test gas.

Safety

Why must a pressure regulator be used when charging a system with nitrogen from a cylinder?

  • a.Cylinder pressure is under 100 psi, too low for a system leak test
  • b.Nitrogen is flammable when it leaves the cylinder at full flow
  • c.Cylinder pressure is over 2,000 psi, far above system test pressure✓
  • d.Nitrogen is toxic when it is released in an open equipment room

A full nitrogen cylinder holds well over 2,000 psi, which would burst system components. The regulator, and a relief valve in the line, limit pressure to the test value. Nitrogen is neither flammable nor toxic, though it can displace oxygen.

Safety

Acetylene should never be used at a hose pressure above:

  • a.30 psig
  • b.50 psig
  • c.15 psig✓
  • d.5 psig

Acetylene becomes unstable above 15 psig and can decompose explosively. Cylinders are also kept upright so the acetone that stabilizes the gas is not drawn out.

Safety

A large refrigerant release in a closed mechanical room is dangerous mainly because the vapor:

  • a.Reacts with moisture to form carbon monoxide
  • b.Is heavier than air and displaces oxygen✓
  • c.Corrodes steel piping within a few minutes
  • d.Is lighter than air and collects at the ceiling

Most refrigerant vapors are heavier than air, settle in low areas and push out breathable air, causing asphyxiation without warning. Leave the space and ventilate it before returning.

Safety

When a halogenated refrigerant is exposed to an open flame or a very hot surface, it can break down into:

  • a.Liquid oil and solid carbon only
  • b.Toxic gases such as phosgene and acids✓
  • c.Harmless nitrogen, oxygen and water vapor
  • d.Pure carbon dioxide and oxygen

Chlorine- and fluorine-bearing refrigerants decompose in a flame into toxic and corrosive products, including hydrochloric and hydrofluoric acids and phosgene. Ventilate and purge lines before brazing.

Safety

Before working on the electrical components of a condensing unit, the technician should:

  • a.Remove the contactor cover and hold the contacts open
  • b.Open the disconnect, lock and tag it, and verify zero voltage✓
  • c.Open the thermostat circuit and remove the low-voltage fuse
  • d.Turn the thermostat to "off" and wait for the fan to stop

Lockout/tagout means opening the disconnect, applying a lock and tag, and checking with a meter that the circuit is dead. The thermostat only opens the control circuit; line voltage is still present at the contactor.

Safety

Before handling a run capacitor, it should be:

  • a.Cooled with compressed air
  • b.Tested with the power turned on
  • c.Discharged through a resistor✓
  • d.Shorted with a screwdriver blade

A capacitor can hold a charge after power is off. Bleeding it through a resistor is the safe method; shorting it with a screwdriver can damage the capacitor and injure the technician.

Safety

Liquid refrigerant sprayed on the skin causes:

  • a.Frostbite✓
  • b.An electric shock
  • c.A heat rash
  • d.A chemical burn

Liquid refrigerant boils at very low temperatures at atmospheric pressure and freezes tissue on contact. Gloves and eye protection are worn when connecting hoses and handling cylinders.

Safety

An extension ladder used to reach a roof should extend above the landing by at least:

  • a.18 inches
  • b.3 feet✓
  • c.6 feet
  • d.1 foot

The side rails extend at least 3 feet above the upper landing so there is something to hold while stepping off, and the ladder is set at about a 4 to 1 angle and secured.29 CFR 1926.1053