Texas Air Conditioning and Refrigeration Contractor Exam — All Questions

28 questions

Service

On a fixed-orifice (piston or capillary tube) cooling system, the refrigerant charge is normally checked by:

  • a.Discharge temperature against the ambient
  • b.Liquid subcooling against the nameplate
  • c.Suction superheat against a charging chart✓
  • d.Compressor amperage against the nameplate

A fixed restriction cannot adjust to load, so target superheat from indoor wet-bulb and outdoor dry-bulb temperatures is the charging method. Subcooling is the method for expansion valve systems.

Service

On a system with a thermostatic expansion valve, the refrigerant charge is normally checked by:

  • a.Suction line superheat
  • b.Sight glass moisture color
  • c.Liquid line subcooling✓
  • d.Suction line pressure only

The expansion valve holds superheat nearly constant regardless of charge, so superheat tells little. Subcooling shows how much liquid is backed up in the condenser and is compared to the manufacturer's target.

Service

A fixed-orifice system has high superheat and low subcooling with low suction and low head pressure. The most likely fault is:

  • a.A dirty condenser coil
  • b.An undercharge of refrigerant✓
  • c.A dirty evaporator coil
  • d.An overcharge of refrigerant

With too little refrigerant the evaporator starves (high superheat) and little liquid is stored in the condenser (low subcooling), with both pressures low. An overcharge gives the opposite: low superheat and high subcooling.

Service

A system shows low suction pressure, high superheat, and high subcooling. This pattern points to:

  • a.A condenser fan motor that has failed
  • b.A restriction in the liquid line or metering device✓
  • c.A compressor with leaking discharge valves
  • d.A low refrigerant charge from a slow leak at a flare fitting

A restriction starves the evaporator, so superheat is high, while refrigerant backs up in the condenser, so subcooling is high. A low charge also gives high superheat but with low subcooling, which is how the two are told apart.

Service

A noticeable temperature drop across a liquid line filter-drier indicates that the drier is:

  • a.Fully saturated with moisture and must be baked
  • b.Installed backward against the direction of flow
  • c.Partly plugged and acting as a metering device✓
  • d.Working normally and removing heat from the liquid

A pressure drop through a restricted drier causes some liquid to flash, and the outlet feels cooler than the inlet or even sweats. The drier should be replaced.

Service

Both suction pressure and head pressure are higher than normal, superheat is low, and subcooling is high. The likely cause is:

  • a.An overcharge of refrigerant✓
  • b.An undercharge of refrigerant
  • c.Low indoor airflow
  • d.A restricted metering device

Excess refrigerant backs up in the condenser, raising head pressure and subcooling, and overfeeds a fixed-orifice evaporator, lowering superheat. Low airflow and restrictions produce low suction pressure.

Service

Air and other noncondensables trapped in a system show up as:

  • a.Suction pressure lower than the evaporator temperature would predict
  • b.Superheat of zero with frost on the compressor shell
  • c.Head pressure higher than the condensing temperature would predict✓
  • d.Subcooling of zero with bubbles in the liquid line sight glass

Noncondensable gas collects in the condenser and adds its own pressure, so head pressure is above the saturation pressure for the measured condensing temperature. The remedy is to recover the charge, evacuate, and recharge.

Service

Suction pressure is high, head pressure is low, and compressor amperage is below normal. The compressor most likely has:

  • a.A start winding that is grounded to the shell
  • b.Leaking valves or worn internal parts✓
  • c.A low oil level in the crankcase
  • d.A locked rotor

A compressor that cannot pump shows suction and discharge pressures drifting toward each other and draws low current because it is doing little work. A locked rotor draws very high current and trips the overload.

Service

Resistance readings on a single-phase compressor are 2 ohms, 4 ohms and 6 ohms between its three terminals. The run winding is between the two terminals that read:

  • a.2 ohms✓
  • b.4 ohms
  • c.6 ohms
  • d.0 ohms

The lowest reading is common to run, the middle reading is common to start, and the highest reading is run to start, which equals the sum of the other two. The run winding has heavier wire and lower resistance.

Service

An ohmmeter reads continuity between a compressor terminal and the copper suction line. The compressor motor is:

  • a.Normal
  • b.Grounded✓
  • c.Open
  • d.Overloaded

Any measurable continuity from a winding terminal to the shell or piping means the winding insulation has failed to ground. A megohmmeter gives a more sensitive check of insulation condition.

Service

A compressor is hot to the touch and all three terminals show an open circuit to common. The first step is to:

  • a.Bypass the overload and restart the compressor
  • b.Replace the compressor without further testing
  • c.Let the compressor cool, then recheck the windings✓
  • d.Add refrigerant until the suction line sweats

An internal overload opens the common connection when the motor overheats, which looks like open windings. It resets when the shell cools, which may take an hour or more; then the cause of overheating is found.

Service

A run capacitor is rated 40 microfarads with a tolerance of plus or minus 6%. Which measured value is out of tolerance?

  • a.41.5 microfarads
  • b.42.0 microfarads
  • c.38.0 microfarads
  • d.36.0 microfarads✓

Six percent of 40 is 2.4, so the acceptable range is 37.6 to 42.4 microfarads. A reading of 36.0 is below the range and the capacitor should be replaced.

Service

Compared with a run capacitor, a start capacitor:

  • a.Has lower capacitance and stays in the circuit only briefly
  • b.Has lower capacitance and stays in the circuit continuously
  • c.Has higher capacitance and stays in the circuit continuously
  • d.Has higher capacitance and stays in the circuit only briefly✓

A start capacitor gives a large phase shift for starting torque and is removed within about a second by a relay. It is not built for continuous duty; a run capacitor is oil-filled, lower in microfarads, and stays in the circuit.

Service

A 240-volt electric heater draws 20 amps. Its resistance and power are:

  • a.12 ohms and 4,800 watts✓
  • b.12 ohms and 2,400 watts
  • c.0.08 ohms and 4,800 watts
  • d.4,800 ohms and 12 watts

Resistance is voltage divided by current, 240 divided by 20, or 12 ohms. Power is voltage times current, 240 times 20, or 4,800 watts.

Service

Before a system is charged, a deep vacuum is normally pulled to at least:

  • a.5,000 microns
  • b.29 inches of mercury on a compound gauge
  • c.0 psig on the low-side gauge
  • d.500 microns✓

A vacuum of 500 microns or lower, measured with an electronic micron gauge, shows that moisture and air have been removed. A compound gauge cannot resolve this level of vacuum.

Service

After reaching 500 microns, the vacuum pump is valved off and the micron gauge rises steadily without stopping. This indicates:

  • a.A failed micron gauge
  • b.A completed evacuation
  • c.Moisture in the system
  • d.A leak in the system✓

A reading that keeps rising toward atmospheric pressure means air is leaking in. If it rises and then levels off at a moderate value, moisture or refrigerant is still boiling off; if it holds, the system is tight and dry.

Service

During evacuation, the vacuum pump should be connected with:

  • a.Long, small-diameter hoses and valve cores in place
  • b.Short, large-diameter hoses and valve cores removed✓
  • c.The refrigerant cylinder open to the manifold
  • d.A single hose on the liquid line service port only

Flow at deep vacuum is very sensitive to restriction. Large, short hoses and removing Schrader cores cut evacuation time dramatically, and the micron gauge goes at the system, away from the pump.

Service

Under EPA Section 608 rules, a technician who opens a refrigerant circuit on stationary equipment must:

  • a.Be certified and recover the refrigerant with certified equipment✓
  • b.Be certified and dilute the refrigerant with dry nitrogen
  • c.Be supervised and store the refrigerant in the receiver only
  • d.Be registered and vent the refrigerant in a ventilated area

Knowingly venting refrigerant is prohibited. Technicians must hold Section 608 certification for the equipment type and use recovery equipment certified for it.40 CFR Part 82, Subpart F

Service

Refrigerant that has been removed from a system and stored in an external container without being tested or processed in any way is said to be:

  • a.Recovered✓
  • b.Recycled
  • c.Reclaimed
  • d.Restored

Recovery is removing refrigerant and storing it without testing or processing. Recycling cleans it for reuse with oil separation and filter-driers; reclaiming reprocesses it to new-product purity, verified by analysis.40 CFR 82.152

Service

Polyolester (POE) oil must be kept sealed until use because it:

  • a.Hardens when it is exposed to light
  • b.Evaporates at normal room temperature
  • c.Absorbs moisture from the air very readily✓
  • d.Separates into layers when it is shaken

POE oil is hygroscopic and moisture it absorbs is hard to remove by evacuation, leading to acid formation. Containers are opened only when needed and systems are not left open.

Service

Which leak detection method pinpoints a refrigerant leak without adding anything to the system?

  • a.A compressor amperage reading
  • b.A standing vacuum test on the system
  • c.An electronic leak detector at the joints✓
  • d.A liquid line sight glass inspection for bubbles

An electronic detector senses refrigerant escaping at a specific point. A standing vacuum test can show that a leak exists but not where, and vacuum can pull joints closed that leak under pressure.

Service

Evaporator coil icing on a cooling system is most often caused by:

  • a.A dirty condenser or a hot outdoor day
  • b.Low airflow or a low refrigerant charge✓
  • c.High airflow or a high refrigerant charge
  • d.A stuck-open expansion valve or overfeed

Low airflow starves the coil of heat, and low charge lowers evaporating pressure; either drops coil temperature below freezing. A dirty condenser raises pressures and does not cause icing.

Service

A gas furnace cycles off on its high limit. Which condition is the most likely cause?

  • a.A weak flame sensor signal
  • b.A dirty filter restricting airflow✓
  • c.A gas manifold pressure that is too low
  • d.A thermostat set too low

The limit opens when the heat exchanger overheats, which is nearly always low airflow: dirty filter, closed registers, dirty coil or wrong blower speed. A weak flame signal causes ignition lockout, not a limit trip.

Service

A heat pump in heating mode has a thick layer of ice over the whole outdoor coil. Which component is a likely cause?

  • a.A failed defrost control or sensor✓
  • b.A failed auxiliary heat sequencer
  • c.A failed indoor blower capacitor
  • d.A failed thermostat anticipator

Light frost is normal, but a solid ice block means defrost is not being started or completed: a bad defrost board, sensor, or reversing valve, or a low charge. Auxiliary heat and indoor components do not clear the outdoor coil.

Service

A condensing unit's contactor is pulled in and 240 volts is measured across the load terminals, but the compressor does not run or hum. The next check is:

  • a.The contactor coil and its control fuse
  • b.The thermostat and the low-voltage transformer
  • c.The compressor windings and internal overload✓
  • d.The indoor blower relay and its wiring

Voltage at the load side of a closed contactor proves the control circuit is working. With power present and no response, the open is in the compressor wiring, the internal overload, or the windings.

Service

Suction line temperature is 50°F and suction pressure converts to 45°F saturation. On a fixed-orifice system with a target superheat of 15°F, the technician should:

  • a.Recover refrigerant, because superheat is too high
  • b.Add refrigerant, because superheat is too high
  • c.Add refrigerant, because superheat is too low
  • d.Recover refrigerant, because superheat is too low✓

Measured superheat is 5°F against a 15°F target. Low superheat means the evaporator is overfed, so refrigerant is removed, after confirming that airflow is correct. Adding refrigerant would lower superheat further.

Service

A liquid line temperature of 95°F is measured when head pressure converts to 105°F saturation, and the manufacturer's target subcooling is 10°F. The charge is:

  • a.Unknown
  • b.Correct✓
  • c.Too high
  • d.Too low

Subcooling is 105 minus 95, or 10°F, which matches the target. Lower subcooling would call for adding refrigerant and higher subcooling for removing it.

Service

When a compressor has burned out, the system cleanup should include:

  • a.Reusing the old driers and adding fresh oil
  • b.Charging with extra refrigerant to dilute the acid left
  • c.Replacing the driers and testing the oil for acid✓
  • d.Flushing the system with compressed air

A burnout leaves acid and sludge in the system. Cleanup uses new liquid and suction line filter-driers, often replaced again after a period of running, with an acid test of the oil. Compressed air adds moisture and oxygen.