Texas Air Conditioning and Refrigeration Contractor Exam — All Questions
22 questions
A furnace's nameplate gives a temperature rise range of 40°F to 70°F. Measured supply air is 135°F and return air is 70°F. The temperature rise is:
- a.205°F, above the range
- b.35°F, below the range
- c.65°F, above the range
- d.65°F, within the range✓
Temperature rise is supply minus return: 135 minus 70 is 65°F, inside the 40 to 70°F range. A rise above the range means low airflow or overfiring; below it means too much airflow or underfiring.
An electric furnace draws 20 kW and the temperature rise across it is 31.6°F. Using CFM = (kW × 3,413) ÷ (1.08 × ΔT), the airflow is about:
- a.2,000 CFM✓
- b.1,000 CFM
- c.3,000 CFM
- d.600 CFM
20 times 3,413 is 68,260 Btu/h; 1.08 times 31.6 is about 34.1; dividing gives about 2,000 CFM. The temperature rise method is a common field check of airflow.
Where should the supply air temperature be measured when using the temperature rise method on a gas furnace?
- a.In the supply duct, out of sight of the heat exchanger✓
- b.At the return grille, with the filter removed
- c.At the farthest supply register in the building
- d.In the supply plenum, directly above the heat exchanger
The probe must be shielded from radiant heat from the heat exchanger, which would give a falsely high reading, and close enough to the furnace that duct losses do not lower it.
A voltmeter is connected to a circuit:
- a.With the power turned off
- b.In parallel with the load✓
- c.In series with the load
- d.Around a single conductor
Voltage is measured across two points, so the meter leads go in parallel with the load or source. A clamp ammeter goes around a single conductor, and resistance is measured with power off.
A clamp-on ammeter is placed around both conductors of a 240-volt single-phase circuit at the same time. The reading will be:
- a.About zero✓
- b.The true current
- c.Half the true current
- d.Twice the true current
The currents in the two conductors are equal and opposite, so their magnetic fields cancel. The clamp must go around one conductor only.
Resistance and continuity measurements are made with:
- a.Power applied and the load disconnected at one lead
- b.Power applied and the load running
- c.The meter set to the AC volts range
- d.Power disconnected and the component isolated✓
An ohmmeter supplies its own small current. Applied power damages the meter and gives false readings, and parallel paths through other components must be removed by disconnecting at least one lead.
A voltmeter reads 24 volts across a set of control contacts that should be closed. The contacts are:
- a.Open✓
- b.Closed
- c.Shorted
- d.Grounded
A closed contact has almost no voltage across it. Reading full control voltage across a switch means the switch is open and the voltage is waiting there instead of at the load.
A megohmmeter is used to test:
- a.Insulation resistance of motor windings to ground✓
- b.Microamp signal of a flame sensor
- c.Capacitance of run capacitors and of start capacitors
- d.Voltage imbalance on three-phase power
A megohmmeter applies a high test voltage and reads insulation resistance in megohms, showing deterioration before a winding fails to ground. Flame signal is read with a microammeter in series with the sensor.
Typical manifold gas pressure for a natural gas furnace is about:
- a.7 psig
- b.0.5 inches w.c.
- c.11 inches w.c.
- d.3.5 inches w.c.✓
Natural gas furnaces usually run about 3.5 inches of water column at the manifold, and propane appliances about 10 to 11 inches. The nameplate value governs, and it is checked with a manometer at the gas valve outlet tap.
Typical manifold gas pressure for a propane (LP) furnace is about:
- a.1 to 2 inches w.c.
- b.20 to 25 inches w.c.
- c.3 to 4 inches w.c.
- d.10 to 11 inches w.c.✓
LP gas appliances commonly run 10 to 11 inches of water column at the manifold; natural gas runs about 3.5. Converting an appliance between fuels requires the manufacturer's orifice and regulator kit.
Which instrument measures gas manifold pressure?
- a.A psychrometer
- b.A megohmmeter
- c.A manometer✓
- d.A micron gauge
A U-tube or digital manometer reads low pressures in inches of water column. A micron gauge reads deep vacuum, and a psychrometer reads wet- and dry-bulb temperatures.
A combustion analyzer reads flue gas for oxygen or carbon dioxide, carbon monoxide, and stack temperature in order to determine:
- a.Heat exchanger airflow and blower motor load
- b.Combustion efficiency and safe burner operation✓
- c.Refrigerant charge and compressor efficiency
- d.Duct leakage and total external static pressure
Oxygen or carbon dioxide shows the amount of excess air, stack temperature shows how much heat is leaving, and carbon monoxide shows whether combustion is complete. Together they give efficiency and a safety check.
In a combustion test, a high oxygen reading in the flue gas with a low carbon dioxide reading indicates:
- a.A cracked heat exchanger only
- b.A large amount of excess air✓
- c.A shortage of combustion air
- d.A blocked vent or chimney
Oxygen that passes through unburned shows up in the flue gas and dilutes the carbon dioxide. Too much excess air carries heat up the vent and lowers efficiency; too little produces carbon monoxide.
Carbon monoxide in flue gas is a product of:
- a.High gas heating value
- b.Incomplete combustion✓
- c.Excess draft
- d.Complete combustion
Complete combustion of natural gas yields carbon dioxide and water vapor. Carbon monoxide forms when there is too little air, flame impingement, or poor mixing.
Draft in a natural-draft vent is measured with a draft gauge in:
- a.Degrees Fahrenheit, as a temperature rise
- b.Inches of water column, as a negative pressure✓
- c.Pounds per square inch, as a positive pressure
- d.Cubic feet per minute, as a volume flow
Draft is a very small negative pressure, typically a few hundredths of an inch of water column, that pulls flue gas up the vent.
A quick spillage test at the draft hood of a gas water heater or furnace is made by:
- a.Holding a smoke source or match at the hood opening after a few minutes of firing✓
- b.Reading the manifold pressure with the main burner switched off
- c.Holding a thermometer in the burner compartment during each trial for ignition
- d.Reading the gas meter dial while every other appliance is firing
After the appliance has run for several minutes, smoke at the draft hood relief opening should be drawn in. Smoke pushed out means flue gas is spilling, pointing to a blocked vent or a depressurized room.
Soap solution brushed on a gas piping joint is used to:
- a.Measure the gas pressure at the joint
- b.Locate leaks by the bubbles that form✓
- c.Protect the joint from corrosion
- d.Lubricate the threads for tightening
A noncorrosive leak detection fluid bubbles where gas escapes. An open flame must never be used to find leaks.IFGC §406.5
The firing rate of a gas appliance can be checked in the field by:
- a.Clocking the gas meter with other appliances off✓
- b.Reading the amperage of the inducer motor
- c.Counting the number of burner ports alight
- d.Measuring the flue pipe surface temperature at the collar
Timing one revolution of the meter's test dial gives cubic feet per hour, which is multiplied by the gas heating value to find Btu/h input and compared with the nameplate.
The 2 cubic foot test dial on a gas meter makes one revolution in 72 seconds with only the furnace firing. With gas at 1,000 Btu per cubic foot, the input is:
- a.50,000 Btu/h
- b.100,000 Btu/h✓
- c.144,000 Btu/h
- d.72,000 Btu/h
Cubic feet per hour equals 3,600 times the dial size divided by seconds: 3,600 times 2 divided by 72 is 100 cubic feet per hour, or 100,000 Btu/h.
Wet-bulb temperature is measured with:
- a.A psychrometer✓
- b.A pyrometer
- c.A manometer
- d.An anemometer
A sling or digital psychrometer reads dry-bulb and wet-bulb temperatures, from which relative humidity and enthalpy are found on the psychrometric chart. An anemometer reads air velocity.
Indoor wet-bulb temperature is needed when charging a fixed-orifice system because it:
- a.Reflects the pressure drop across the filter
- b.Sets the cut-in of the low-pressure switch
- c.Reflects the total heat load on the evaporator✓
- d.Sets the speed tap for the condenser fan
Wet-bulb temperature tracks the enthalpy of the air entering the coil. With outdoor dry-bulb temperature it gives the target superheat on the manufacturer's charging chart.
A standing pressure test of new refrigerant piping is made with dry nitrogen, and the pressure is recorded together with:
- a.The compressor oil level, since nitrogen dissolves in the oil
- b.The ambient temperature, since pressure changes with temperature✓
- c.The line voltage, since the test is made with the power on
- d.The barometric pressure, since nitrogen is lighter than air
Nitrogen pressure rises and falls with temperature, so a small change over a day may not be a leak. Recording temperature with pressure lets the two readings be compared fairly.