Texas Air Conditioning and Refrigeration Contractor Exam — All Questions

20 questions

Refrigeration Principles

One ton of refrigeration is a rate of heat removal equal to:

  • a.10,000 Btu per hour
  • b.2,000 Btu per hour
  • c.12,000 Btu per hour✓
  • d.24,000 Btu per hour

A ton is 12,000 Btu/h, or 200 Btu per minute, taken from the heat needed to melt one ton of ice in 24 hours (288,000 Btu per day). The other values are not standard definitions.

Refrigeration Principles

Heat that changes the temperature of a substance without changing its state is:

  • a.Superheat
  • b.Specific heat
  • c.Latent heat
  • d.Sensible heat✓

Sensible heat can be measured with a thermometer. Latent heat changes state at constant temperature, specific heat is a property (Btu per pound per degree), and superheat is temperature above saturation.

Refrigeration Principles

How much heat does it take to raise 10 pounds of water from 60°F to 100°F?

  • a.40 Btu
  • b.970 Btu
  • c.4,000 Btu
  • d.400 Btu✓

One Btu raises one pound of water one degree Fahrenheit, so 10 pounds times 40 degrees is 400 Btu. The 970 figure is the latent heat of vaporization of one pound of water at atmospheric pressure, which does not apply here.

Refrigeration Principles

The latent heat of fusion of water, the heat removed to freeze one pound of water at 32°F, is about:

  • a.1 Btu
  • b.180 Btu
  • c.144 Btu✓
  • d.970 Btu

Freezing or melting one pound of water at 32°F involves about 144 Btu. About 970 Btu per pound is the latent heat of vaporization at 212°F, and 1 Btu per pound per degree is water's specific heat.

Refrigeration Principles

Heat always flows naturally:

  • a.From a warmer substance to a cooler one✓
  • b.From a lower pressure to a higher one
  • c.From a cooler substance to a warmer one
  • d.From a liquid toward a nearby vapor

Heat moves from higher temperature to lower temperature. A refrigeration system does not reverse this; it makes the refrigerant colder than the space so heat flows into it, then hotter than the outdoors so heat flows out.

Refrigeration Principles

Heat transfer through a solid copper tube wall takes place by:

  • a.Evaporation
  • b.Radiation
  • c.Convection
  • d.Conduction✓

Conduction is heat transfer through a material or between materials in contact. Convection moves heat with a fluid, and radiation travels as waves without needing a medium.

Refrigeration Principles

Superheat is the:

  • a.Pressure of a vapor above its saturation pressure
  • b.Temperature of a vapor above its saturation temperature✓
  • c.Heat that turns a saturated liquid into a vapor
  • d.Temperature of a liquid below its saturation temperature

Superheat is the sensible heat added to a vapor after all the liquid has boiled off, measured in degrees above saturation at that pressure. Liquid below saturation temperature is subcooled.

Refrigeration Principles

Suction pressure corresponds to a saturation temperature of 40°F, and the suction line at the evaporator outlet measures 52°F. The superheat is:

  • a.40°F
  • b.8°F
  • c.92°F
  • d.12°F✓

Superheat is the measured line temperature minus the saturation temperature for the measured pressure: 52 minus 40 is 12°F. Adding the two numbers or reporting the saturation temperature itself are the usual mistakes.

Refrigeration Principles

Head pressure corresponds to a condensing temperature of 110°F, and the liquid line at the condenser outlet measures 98°F. The subcooling is:

  • a.12°F✓
  • b.208°F
  • c.22°F
  • d.98°F

Subcooling is saturation (condensing) temperature minus the measured liquid line temperature: 110 minus 98 is 12°F. It shows how much liquid is stacked in the condenser.

Refrigeration Principles

As the pressure on a liquid refrigerant is lowered, its boiling point:

  • a.Falls✓
  • b.Stays constant
  • c.Doubles
  • d.Rises

Boiling point follows pressure: lower pressure, lower saturation temperature. This is how the metering device lets refrigerant boil at a low temperature in the evaporator, and why a pressure-temperature chart can convert a gauge reading into coil temperature.

Refrigeration Principles

A gauge reads 70 psig at sea level. The absolute pressure is about:

  • a.99.4 psia
  • b.70.0 psia
  • c.55.3 psia
  • d.84.7 psia✓

Absolute pressure is gauge pressure plus atmospheric pressure, 14.7 psi at sea level: 70 plus 14.7 is 84.7 psia. Subtracting gives 55.3, which is wrong for a positive gauge reading.

Refrigeration Principles

A perfect vacuum at sea level corresponds to about:

  • a.30 psig on the low-side gauge, or 1,000 microns absolute
  • b.14.7 inches of mercury vacuum, or 500 microns absolute
  • c.0 inches of mercury vacuum, or 760,000 microns absolute
  • d.29.92 inches of mercury vacuum, or 0 microns absolute✓

Standard atmospheric pressure supports a 29.92-inch mercury column, so a perfect vacuum is 29.92 inches of mercury below atmosphere, or zero microns absolute. Atmospheric pressure is about 760,000 microns.

Refrigeration Principles

What happens to refrigerant as it passes through the metering device?

  • a.Pressure rises while temperature drops and the vapor is superheated
  • b.Pressure drops while temperature rises and the liquid is subcooled
  • c.Pressure and temperature drop and part of the liquid flashes to vapor✓
  • d.Pressure and temperature rise and all of the vapor condenses to liquid

The restriction drops the pressure to evaporator pressure; some liquid flashes to vapor, cooling the rest to the evaporating temperature. No heat is added or removed in the device itself.

Refrigeration Principles

In the refrigeration cycle, where is most of the heat absorbed from the conditioned space?

  • a.In the condenser, as latent heat of condensation
  • b.In the evaporator, as latent heat of vaporization✓
  • c.In the liquid line, as sensible subcooling
  • d.In the compressor, as heat of compression

The refrigerant boils in the evaporator and takes up latent heat from the air or product. The condenser rejects that heat plus the heat of compression.

Refrigeration Principles

The compression ratio of a compressor is:

  • a.Absolute discharge pressure divided by absolute suction pressure✓
  • b.Gauge discharge pressure divided by gauge suction pressure
  • c.Absolute suction pressure divided by absolute discharge pressure
  • d.Gauge discharge pressure minus the gauge suction pressure

Compression ratio uses absolute pressures: discharge psia over suction psia. Using gauge readings gives a wrong, larger number, and subtracting the pressures gives the pressure difference, not a ratio.

Refrigeration Principles

A system runs at 260 psig discharge and 60 psig suction at sea level. Using 15 psi for atmospheric pressure, the compression ratio is about:

  • a.5.0 to 1
  • b.3.7 to 1✓
  • c.200 to 1
  • d.4.3 to 1

Convert to absolute: 275 psia over 75 psia is about 3.7. Dividing the gauge pressures gives 4.3, which is the common error, and 200 is the pressure difference in psi.

Refrigeration Principles

On a psychrometric chart, the temperature at which moisture begins to condense out of air is the:

  • a.Wet-bulb temperature
  • b.Dew point temperature✓
  • c.Saturation pressure
  • d.Dry-bulb temperature

At the dew point the air is saturated, and any further cooling condenses water. Wet-bulb temperature reflects evaporative cooling and total heat, and dry-bulb is the ordinary thermometer reading.

Refrigeration Principles

Air leaves a cooling coil at a lower dry-bulb temperature and a lower moisture content than it entered. The coil has removed:

  • a.Neither sensible heat nor latent heat
  • b.Sensible heat only
  • c.Latent heat only
  • d.Both sensible and latent heat✓

A drop in dry-bulb temperature is sensible cooling and a drop in moisture content is latent cooling. A coil surface below the air's dew point does both, and the condensate leaves through the drain.

Refrigeration Principles

The total heat content of air, shown on the psychrometric chart in Btu per pound of dry air, is called:

  • a.Enthalpy✓
  • b.Relative humidity
  • c.Entropy
  • d.Specific volume

Enthalpy is total heat, sensible plus latent. Total cooling capacity can be found from 4.5 times CFM times the enthalpy difference across the coil. Specific volume is cubic feet per pound, and relative humidity is a percentage.

Refrigeration Principles

A coil handles 2,000 CFM. Entering air enthalpy is 30 Btu/lb and leaving air enthalpy is 24 Btu/lb. Using Q = 4.5 × CFM × Δh, the total capacity is:

  • a.54,000 Btu/h, or 4.5 tons✓
  • b.108,000 Btu/h, or 9 tons
  • c.36,000 Btu/h, or 3 tons
  • d.12,000 Btu/h, or 1 ton

4.5 times 2,000 times 6 is 54,000 Btu/h, and dividing by 12,000 gives 4.5 tons. 12,000 comes from leaving out the 4.5 factor, and 108,000 from doubling the enthalpy difference.