Texas Air Conditioning and Refrigeration Contractor Exam — All Questions

300 questions

Texas Laws and Rules

A contractor holds a Class B license with the environmental air conditioning endorsement. Under Occupations Code §1302.253, which single cooling unit is the largest this contractor may install?

  • a.A unit of 50 tons cooling capacity
  • b.A unit of 15 tons cooling capacity
  • c.A unit of 25 tons cooling capacity✓
  • d.A unit of any cooling capacity

§1302.253 limits a Class B license to cooling systems of 25 tons or less and heating systems of 1.5 million Btu/h or less. Fifteen tons is allowed but is not the ceiling, 50 tons is beyond it, and work on a unit of any size is what a Class A license allows.Tex. Occ. Code §1302.253

Texas Laws and Rules

Under Occupations Code §1302.253, the heating limit for a Class B license is a system with an output of no more than:

  • a.1.0 million Btu per hour
  • b.1.5 million Btu per hour✓
  • c.2.5 million Btu per hour
  • d.500,000 Btu per hour

The Class B heating limit is 1.5 million Btu/h, paired with the 25-ton cooling limit. The other figures do not appear in the statute. A Class A license has no size limit.Tex. Occ. Code §1302.253

Texas Laws and Rules

A Class B contractor is asked to service an office park with six separate 20-ton rooftop units, 120 tons in total. Under 16 TAC §75.22, the contractor:

  • a.May do the work, because each complete unit is within 25 tons✓
  • b.May do the work only with a Class A subcontractor on site
  • c.May do the work only after a department waiver is issued
  • d.May not do the work, because the total exceeds 25 tons

§75.22(c) lets a Class B licensee work in a building or complex with several units even when the combined capacity exceeds 25 tons, as long as each complete individual unit stays within the Class B limits. The rule tests each unit, not the total, and it does not call for a waiver or a Class A subcontractor.16 TAC §75.22(c)

Texas Laws and Rules

In the license number format TACL/B/000000/R set out in 16 TAC §75.22, the final letter R tells you the license carries which endorsement?

  • a.Commercial refrigeration and process cooling or heating✓
  • b.Residential comfort cooling only, with no commercial work allowed
  • c.Environmental air conditioning only
  • d.Combined endorsements, both fields of work

§75.22 assigns E to environmental air conditioning, R to commercial refrigeration and process cooling or heating, and C to combined endorsements. There is no residential-only endorsement in the chapter.16 TAC §75.22(b)

Texas Laws and Rules

What is the minimum per-occurrence commercial general liability coverage a Class A licensee must carry under 16 TAC §75.40?

  • a.$500,000 per occurrence
  • b.$300,000 per occurrence✓
  • c.$600,000 per occurrence
  • d.$100,000 per occurrence

Class A requires at least $300,000 per occurrence, $600,000 aggregate, and $300,000 aggregate for products and completed operations. $100,000 is the Class B per-occurrence figure and $600,000 is the Class A aggregate, not the per-occurrence amount.16 TAC §75.40(a)

Texas Laws and Rules

A Class B licensee is reviewing a policy. Which set of limits just meets 16 TAC §75.40?

  • a.$100,000 per occurrence, $100,000 aggregate, $100,000 products and completed operations
  • b.$200,000 per occurrence, $200,000 aggregate, $50,000 products and completed operations
  • c.$50,000 per occurrence, $300,000 aggregate, $100,000 products and completed operations
  • d.$100,000 per occurrence, $200,000 aggregate, $100,000 products and completed operations✓

Class B minimums are $100,000 per occurrence, $200,000 aggregate, and $100,000 aggregate for products and completed operations. Each wrong choice falls short on one line: a $100,000 aggregate, a $50,000 products limit, or a $50,000 per-occurrence limit.16 TAC §75.40(b)

Texas Laws and Rules

A contractor holds two licenses, a Class A and a Class B, each with a different endorsement. Under 16 TAC §75.22, the insurance requirement may be met with:

  • a.Two policies, one written separately for each license
  • b.One policy with limits at least as high as Class A requires✓
  • c.One policy with limits at least as high as Class B requires
  • d.A surety bond filed in place of liability insurance

§75.22(g) allows a single policy when its limits are at least those required for a Class A license. Class B limits would leave the Class A license underinsured, separate policies are not required, and the chapter does not substitute a bond for liability insurance.16 TAC §75.22(g)

Texas Laws and Rules

A licensee who has received a waiver of the insurance requirement under 16 TAC §75.40 may not:

  • a.Perform or offer contracting work for the general public✓
  • b.Complete continuing education during the license term
  • c.Renew the license at the end of its one-year term
  • d.Take a Class A examination to upgrade an endorsement

The waiver exists for a license holder who does not contract with the public, so §75.40(f) bars a waived licensee from performing or offering contracting to the general public. The waiver does not affect renewal, upgrading, or continuing education.16 TAC §75.40(e)-(f)

Texas Laws and Rules

A company's only license holder dies on June 1. Under 16 TAC §75.23, the request for a temporary license must be made within:

  • a.10 business days of the date the license holder became unavailable
  • b.15 calendar days of the date the license holder became unavailable✓
  • c.60 calendar days of the date the license holder became unavailable
  • d.30 calendar days of the date the license holder became unavailable

§75.23(c) gives fifteen calendar days from the date the license holder became unavailable. Thirty calendar days is how long the temporary license lasts, not the window to request it; the other periods are not in the rule.16 TAC §75.23(c)

Texas Laws and Rules

How long is a temporary contractor license valid under 16 TAC §75.23, and can it be renewed?

  • a.30 calendar days from issuance, and it can be renewed once
  • b.30 calendar days from issuance, and it cannot be renewed✓
  • c.21 calendar days from issuance, and it can be renewed once
  • d.90 calendar days from issuance, and it cannot be renewed

A temporary license is non-renewable and valid for 30 calendar days from the date of issuance. The 21-day period belongs to a temporary technician registration under §75.27, not to a contractor's temporary license.16 TAC §75.23(d)

Texas Laws and Rules

Who may hold the temporary license issued under 16 TAC §75.23 after a company's only license holder becomes unavailable?

  • a.Any licensed contractor the firm hires after the event
  • b.An owner, partner, or employee already associated with the firm✓
  • c.The surviving spouse of the license holder, in every case
  • d.A registered technician recruited from another contracting company

The rule requires the temporary holder to be an owner, partner, or employee who was already associated with the firm. It does not allow bringing in an outsider after the fact, and a spouse qualifies only if already an owner, partner, or employee.16 TAC §75.23(b)

Texas Laws and Rules

To renew a contractor license, 16 TAC §75.25 requires how much continuing education, and how much of it on Texas law and rules?

  • a.4 hours, including 1 hour of Texas law and rules
  • b.12 hours, including 2 hours of Texas law and rules
  • c.8 hours, including 4 hours of Texas law and rules
  • d.8 hours, including 1 hour of Texas law and rules✓

The renewal requirement is eight hours of department-approved courses, one of which must cover the Texas law and rules that regulate licensees. The other combinations change one or both numbers.16 TAC §75.24, §75.25(b)

Texas Laws and Rules

Under 16 TAC §75.25, how long must a licensee keep the certificate of completion for a continuing education course?

  • a.Three years after the date of completion
  • b.Two years after the date of completion
  • c.One year after the date of completion✓
  • d.Until the next license is issued only

§75.25(e) sets one year after completion. Three years is the retention period for company job records under §75.71, a different requirement, and two years applies to training program providers' completion records under §75.123.16 TAC §75.25(e)

Texas Laws and Rules

A licensee attends the same approved continuing education course twice in one license term. Under 16 TAC §75.25, the second attendance:

  • a.Earns full credit toward the next term
  • b.Earns credit if a new instructor taught
  • c.Earns no continuing education credit✓
  • d.Earns half of the course credit hours

§75.25(d) says a licensee may not receive credit for attending the same course more than once. The rule has no half-credit, carry-forward, or new-instructor exception.16 TAC §75.25(d)

Texas Laws and Rules

Under 16 TAC §75.71, a contracting company must keep the records of business conducted through a permanent office available to the department for at least:

  • a.One year after completion of a job
  • b.Five years after completion of a job
  • c.Two years after the contract is signed
  • d.Three years after completion of a job✓

The retention period is at least three years after a job is completed. One year matches the continuing education certificate rule, five years is not in the chapter, and the clock runs from job completion rather than from contract signing.16 TAC §75.71(a)(6)

Texas Laws and Rules

What lettering does 16 TAC §75.71 require on vehicles used in air conditioning and refrigeration contracting?

  • a.License number and company name, at least 2 inches high, on both sides✓
  • b.Company name and phone number, at least 2 inches high, on both sides
  • c.License number only, at least 1 inch high, on the driver's side
  • d.License number and company name, at least 3 inches high, on the rear

§75.71(g) calls for the affiliated licensee's license number and the company name in letters not less than two inches high on both sides of each vehicle. A phone number does not replace the license number, and one side or the rear alone is not enough.16 TAC §75.71(g)

Texas Laws and Rules

Which advertisement must carry the affiliated licensee's license number under 16 TAC §75.71?

  • a.A sign on the contractor's permanent business location
  • b.A phone book listing with only name, address and number
  • c.A printed door hanger offering a spring tune-up special✓
  • d.A promotional ball cap handed out at a home show

All advertising designed to solicit business must show the license number unless it falls in a listed exception. Signs at the permanent business location, promotional items of nominal value, and name-address-number phone listings are listed exceptions; a door hanger is not.16 TAC §75.71(h)

Texas Laws and Rules

Under 16 TAC §75.71, the statement beginning "Regulated by The Texas Department of Licensing and Regulation" must appear on which documents?

  • a.Invoices and warranty cards only
  • b.Vehicle signs and employee badges
  • c.Permit applications and municipal inspection tags
  • d.Proposals, invoices and written contracts✓

§75.71(i) lists proposals and invoices, written contracts, and a sign at the place of business if consumers may visit it for service. Permit applications, warranty cards, vehicle signs and badges are not on the list.16 TAC §75.71(i)

Texas Laws and Rules

A licensee moves the company to a new address. Under 16 TAC §75.70, the department must be notified in writing within:

  • a.10 business days of the change
  • b.60 calendar days of the change
  • c.30 calendar days of the change✓
  • d.15 calendar days of the change

§75.70(h) gives thirty calendar days for a change in mailing address, company location, company telephone number, or assignment of license. Fifteen calendar days is the deadline for answering a department request to verify an applicant's experience.16 TAC §75.70(h)

Texas Laws and Rules

The department asks a licensee to verify the practical experience of a former employee who has applied for a license. Under 16 TAC §75.70, the licensee must respond within:

  • a.30 calendar days of the request
  • b.45 calendar days of the request
  • c.15 calendar days of the request✓
  • d.5 business days of the request

§75.70(a)(13) requires the information within fifteen calendar days of the request. Thirty calendar days is the notice period for address and assignment changes, which is the usual wrong answer here.16 TAC §75.70(a)(13)

Texas Laws and Rules

Under 16 TAC §75.70, which part of a job may never be subcontracted to an unlicensed person, firm or corporation?

  • a.The pulling of thermostat wire
  • b.The design of the system✓
  • c.The setting of equipment
  • d.The hanging of ductwork

Portions of licensed work may be subcontracted to unlicensed persons if the licensee actively takes part and stays responsible to the customer, but §75.70(c) says system design may not be. Installation tasks such as ductwork, equipment setting and low-voltage wire are not singled out.16 TAC §75.70(b)-(c)

Texas Laws and Rules

A licensee accepts a contract, schedules the job, and supervises an unlicensed subcontractor who does all of the installation. Under 16 TAC §75.70(b), this arrangement:

  • a.Is not allowed, because unlicensed persons may never perform any portion of work that requires a license
  • b.Is allowed, because the licensee remains ultimately responsible to the customer for the finished job
  • c.Is not allowed, because the licensee's own work must be more than contracting, scheduling and supervising✓
  • d.Is allowed, because supervision by a licensee satisfies the requirement to actively provide the work

Subcontracting to unlicensed persons is allowed only if the licensee, in person or with employees, actively provides licensed work that is more than accepting the contract, scheduling, and supervising. Responsibility to the customer is a separate condition, and the rule does not ban all unlicensed subcontracting.16 TAC §75.70(b)

Texas Laws and Rules

Under 16 TAC §75.10, a "full-time employee" of a contracting company is one who works:

  • a.At least 32 hours a week, or 50% of the hours the company offers services, whichever is less
  • b.At least 30 hours a week during every week in which the company is open to the public
  • c.At least 40 hours a week, or 80% of the hours the company offers services, whichever is more
  • d.At least 40 hours a week, or 80% of the hours the company offers services, whichever is less✓

The definition uses 40 hours a week or 80 percent of the time the company offers services to the public, whichever is less. "Whichever is more" reverses the test, and the 32-hour, 50 percent and 30-hour figures are not in the rule.16 TAC §75.10

Texas Laws and Rules

A company has two permanent offices, one in Dallas and one in Houston. Under Occupations Code §1302.252 and 16 TAC §75.71, the company must:

  • a.Employ a license holder in one office and a certified technician in the other
  • b.Employ a license holder in the office that has the larger annual sales
  • c.Employ a full-time license holder in each permanent office✓
  • d.Employ one license holder who divides time between the offices

Each permanent office needs its own full-time licensee, and a license may be used for only one business affiliation and one permanent office at a time. A shared licensee or a certified technician standing in does not satisfy the requirement.Tex. Occ. Code §1302.252; 16 TAC §75.71(e)

Texas Laws and Rules

A contracting company that does not employ a license holder as §1302.252 requires performs a job and is not paid. Under that section, the company:

  • a.May collect the fee if the work passed inspection
  • b.May collect only its documented material costs
  • c.May enforce the contract after obtaining a license
  • d.May not collect a fee or enforce the contract✓

The statute provides that a company that fails to employ a full-time license holder in each permanent office may not collect a fee or otherwise enforce a contract for the services performed. It makes no exception for materials, later licensing, or a passed inspection.Tex. Occ. Code §1302.252

Texas Laws and Rules

Which applicant meets the experience requirement for a contractor license under Occupations Code §1302.255 without relying on a technician certification?

  • a.36 months of practical experience within the preceding 48 months
  • b.60 months of practical experience within the preceding 120 months
  • c.24 months of practical experience within the preceding 36 months
  • d.48 months of practical experience within the preceding 72 months✓

The basic route is at least 48 months of practical experience in the preceding 72 months, and the applicant must be at least 18. The 36-in-48 route applies only to someone who has also held a technician certification for the preceding 12 months.Tex. Occ. Code §1302.255

Texas Laws and Rules

An applicant has held a technician certification for the preceding 12 months. Under Occupations Code §1302.255, how much practical experience is also needed for the contractor license?

  • a.24 months within the preceding 48 months
  • b.48 months within the preceding 72 months
  • c.12 months within the preceding 24 months
  • d.36 months within the preceding 48 months✓

The certified-technician route requires the certification for the preceding 12 months plus at least 36 months of practical experience in the preceding 48 months. The 48-in-72 figure is the route without certification.Tex. Occ. Code §1302.255

Texas Laws and Rules

Under Occupations Code Chapter 1302, a person must be at least what age to register as a technician, and what age to be certified as a technician?

  • a.16 to register and 18 to be certified✓
  • b.16 to register and 16 to be certified
  • c.18 to register and 18 to be certified
  • d.18 to register and 21 to be certified

Technician registration is open at 16 with no examination; technician certification and the contractor license both require age 18. A technician under 18 must work under in-person supervision.Tex. Occ. Code §§1302.5035, 1302.5036

Texas Laws and Rules

A 17-year-old registered technician is sent on a service call. Under 16 TAC §75.70, the licensee must provide:

  • a.Telephone supervision, directly or through a registered technician
  • b.A written job plan signed by the customer before work starts
  • c.In-person supervision, directly or through a certified technician✓
  • d.A weekly review of the technician's completed work orders

§75.70(a)(12) requires in-person supervision at all times of a technician younger than 18, given by the licensee directly or through a certified technician. Phone contact, paperwork and after-the-fact review do not meet it.16 TAC §75.70(a)(12)

Texas Laws and Rules

Under 16 TAC §75.73, how does the work a registered technician may perform compare with that of a certified technician?

  • a.A registered technician may perform maintenance only
  • b.A registered technician may perform residential work only
  • c.A registered technician may perform no refrigerant work
  • d.A registered technician may perform the same tasks✓

§75.73(f) states that a registered technician is not required to be certified and may perform the same tasks as a certified technician. Certification is a credential, and a route to the contractor license, not a wider scope of work. Both work under a licensed contractor.16 TAC §75.73(f)

Texas Laws and Rules

Which person is exempt from the licensing law under Occupations Code Chapter 1302 and 16 TAC §75.30?

  • a.An owner working on the system in the home the owner solely owns and lives in✓
  • b.A licensed plumber replacing a furnace as part of a water heater job
  • c.A friend helping the homeowner install a split system without pay
  • d.A landlord replacing the condensing unit at a rental house the landlord owns

The homeowner exemption covers only a person working in a building owned solely by that person as the person's home, and §75.30 says it does not extend to others who assist. Plumbers are not exempt under §1302.063, and a rental house is not the owner's home.Tex. Occ. Code §1302.053, §1302.063; 16 TAC §75.30(a)(2)

Texas Laws and Rules

A retailer delivers and installs a portable, self-contained ductless air conditioner. Under 16 TAC §75.30, no license is needed if the cooling capacity is not more than:

  • a.2 tons
  • b.3 tons✓
  • c.5 tons
  • d.10 tons

The exemption covers a portable or self-contained ductless air conditioning product with a cooling capacity of three tons or less. The other values are not in the rule.16 TAC §75.30(a)(5); Tex. Occ. Code §1302.058

Texas Laws and Rules

A kitchen equipment installer puts in a commercial vent hood and then runs the exhaust duct to the roof and sets the exhaust fan. Under 16 TAC §75.30:

  • a.All of the work is exempt, since it is one exhaust system
  • b.Only the fan is exempt, since it is listed equipment
  • c.None of the work is exempt, since the kitchen is commercial
  • d.Only the hood itself is exempt; the duct and fan work is not✓

The vent hood exemption applies as long as the person does not install, repair or remove any other part of the exhaust system. Duct and fan work falls outside it. The exemption covers residential and commercial kitchen hoods alike.16 TAC §75.30(a)(4)

Texas Laws and Rules

An unlicensed general contractor bids a tenant build-out that includes framing, electrical, and a new rooftop unit. Under 16 TAC §75.30(b), the general contractor:

  • a.May bid the job only if the air conditioning is under 25 tons of cooling capacity
  • b.May bid the job only after registering with the department as a technician
  • c.May not bid the job, since any air conditioning work requires its own license
  • d.May bid the job, since it does not consist solely of licensed air conditioning work✓

An unlicensed general contractor may bid or contract for a job that includes air conditioning or refrigeration if the job is not solely licensed work. The air conditioning itself must still be performed by a licensed contractor. Tonnage and technician registration are not part of the test.16 TAC §75.30(b)

Texas Laws and Rules

On a furnace replacement, how much fuel gas piping may a licensee install under 16 TAC §75.100?

  • a.The piping anywhere inside the building, but not in the yard
  • b.The piping between the appliance and an existing shut-off valve✓
  • c.The piping within six feet of the appliance in any direction
  • d.The piping between the appliance and the gas meter outlet

Fuel gas piping by a licensee is limited to the portion between the appliance and the existing piping system, connected at an existing shut-off valve, and the licensee may not alter existing piping, stops or valves. The rule sets no six-foot or indoor limit, and work back to the meter is beyond it.16 TAC §75.100(b)(1)

Texas Laws and Rules

Under 16 TAC §75.100, control wiring of what voltage may be installed and serviced by any licensee, regardless of endorsement?

  • a.24 volts or less
  • b.30 volts or less
  • c.120 volts or less
  • d.50 volts or less✓

§75.100(a)(3) allows a licensee to install and service control wiring of 50 volts or less. A licensee with the commercial refrigeration endorsement may also install control wiring of any voltage for that equipment on the equipment side of the disconnect.16 TAC §75.100(a)(3)

Air Distribution

A 4-ton residential cooling system is set up at the common nominal airflow of 400 CFM per ton. What total airflow should the blower deliver?

  • a.1,600 CFM✓
  • b.2,000 CFM
  • c.1,400 CFM
  • d.1,200 CFM

Four tons times 400 CFM per ton is 1,600 CFM. 1,200 CFM would be 300 CFM per ton and 1,400 CFM is 350 CFM per ton, both lower-airflow setups; 2,000 CFM is 500 CFM per ton.

Air Distribution

A supply duct measures 12 inches by 12 inches and carries 1,000 CFM. What is the average air velocity in the duct?

  • a.500 feet per minute
  • b.144 feet per minute
  • c.1,000 feet per minute✓
  • d.1,200 feet per minute

Velocity equals airflow divided by area. A 12 by 12 inch duct has 1 square foot of area, so 1,000 CFM moves at 1,000 fpm. The 144 figure confuses square inches with velocity, and 500 and 1,200 fpm do not follow from the numbers given.

Air Distribution

A rectangular duct is 24 inches by 12 inches and the measured average velocity is 700 feet per minute. What is the airflow?

  • a.1,400 CFM✓
  • b.700 CFM
  • c.2,016 CFM
  • d.1,050 CFM

The duct area is 24 times 12 divided by 144, or 2 square feet. Airflow is area times velocity: 2 times 700 is 1,400 CFM. 700 CFM forgets the area, and 2,016 uses square inches incorrectly.

Air Distribution

A furnace delivers 64,800 Btu/h of sensible heat to the airstream and the temperature rise across it is 50°F. Using the standard-air sensible heat formula, about how much air is moving?

  • a.1,200 CFM✓
  • b.1,500 CFM
  • c.1,000 CFM
  • d.1,300 CFM

Sensible heat equals 1.08 times CFM times the temperature difference, so CFM is 64,800 divided by (1.08 times 50), which is 1,200. The other values come from dropping the 1.08 factor or misplacing the temperature rise.

Air Distribution

In the sensible heat equation Q = 1.08 × CFM × ΔT, the factor 1.08 is valid for:

  • a.Air leaving a cooling coil at 55°F dry bulb only
  • b.Air at standard density, about 0.075 pounds per cubic foot✓
  • c.Air at saturation, with relative humidity of 100%
  • d.Air at any altitude or temperature, since the factor never changes

The 1.08 factor combines standard air density (0.075 lb per cubic foot), the specific heat of air (0.24), and 60 minutes per hour. At high altitude or very different temperatures the density changes and the factor must be corrected.

Air Distribution

Total external static pressure for a furnace is found by:

  • a.Adding the supply and return static pressures, ignoring signs✓
  • b.Averaging the supply and the return static pressures
  • c.Subtracting return static from the supply static pressure
  • d.Reading the supply static pressure at the plenum alone

The blower works against the return (negative) and the supply (positive) resistance together, so the two readings are added as absolute values. Subtracting or averaging understates the load on the blower, and a supply-only reading leaves out the return side.

Air Distribution

A technician measures +0.35 inches w.c. in the supply plenum and −0.25 inches w.c. in the return at the furnace. The total external static pressure is:

  • a.0.60 inches w.c.✓
  • b.0.10 inches w.c.
  • c.0.35 inches w.c.
  • d.0.30 inches w.c.

Add the absolute values: 0.35 plus 0.25 is 0.60 inches of water column. 0.10 is the result of subtracting, 0.30 is the average, and 0.35 is the supply side alone.

Air Distribution

Total pressure in a duct equals:

  • a.Static pressure times velocity pressure
  • b.Static pressure minus velocity pressure
  • c.Static pressure plus velocity pressure✓
  • d.Velocity pressure divided by static pressure

Total pressure is the sum of static pressure, which pushes outward on the duct walls, and velocity pressure, which is the pressure of the moving air. A pitot tube reads total and static pressure, and the difference is velocity pressure.

Air Distribution

A pitot tube traverse gives a velocity pressure of 0.25 inches w.c. in standard air. Using V = 4005 × √VP, the velocity is about:

  • a.1,000 feet per minute
  • b.4,000 feet per minute
  • c.2,000 feet per minute✓
  • d.500 feet per minute

The square root of 0.25 is 0.5, and 4005 times 0.5 is about 2,000 fpm. 1,000 fpm multiplies by 0.25 instead of its square root, and 4,000 fpm skips the square root altogether.

Air Distribution

According to the fan laws, if blower speed is raised from 800 RPM to 880 RPM, a 10% increase, airflow will:

  • a.Stay about the same
  • b.Rise by about 33%
  • c.Rise by about 21%
  • d.Rise by about 10%✓

Airflow varies directly with fan speed, so a 10% speed increase gives about 10% more airflow. Static pressure rises with the square of speed (about 21%) and horsepower with the cube (about 33%), which is where the other figures come from.

Air Distribution

A belt-drive blower's speed is doubled. By the fan laws, the brake horsepower required becomes about:

  • a.Six times the original
  • b.Eight times the original✓
  • c.Four times the original
  • d.Twice the original

Horsepower varies with the cube of the speed ratio: 2 cubed is 8. Four times is the change in static pressure (the square), and twice is the change in airflow.

Air Distribution

In ACCA Manual D, the friction rate used to size a duct run is found from:

  • a.Total effective length times 100, divided by available static pressure
  • b.External static pressure, divided by the number of supply outlets
  • c.Blower airflow in CFM, divided by the total effective length
  • d.Available static pressure times 100, divided by total effective length✓

Manual D converts the pressure left for the ducts into a design friction rate per 100 feet: available static pressure times 100, divided by total effective length. Inverting the fraction gives a meaningless number, and airflow or outlet count is not part of this step.

Air Distribution

A blower can deliver the design airflow at 0.50 inches w.c. external static pressure. The coil, filter, and grilles use 0.30 inches w.c. The total effective length of the longest circuit is 200 feet. The Manual D design friction rate is:

  • a.0.04 inches w.c. per 100 feet
  • b.0.25 inches w.c. per 100 feet
  • c.0.15 inches w.c. per 100 feet
  • d.0.10 inches w.c. per 100 feet✓

Available static pressure is 0.50 minus 0.30, or 0.20. Friction rate is 0.20 times 100 divided by 200, which is 0.10. The 0.25 answer forgets to subtract the component pressure drops.

Air Distribution

In Manual D, the "total effective length" of a duct run is:

  • a.Measured straight length of the supply trunk and every one of its branches
  • b.Distance from the air handler to the farthest room outlet
  • c.Measured straight length plus the equivalent length of all fittings✓
  • d.Equivalent length of the fittings in the return side only

Total effective length adds the measured straight duct in the longest supply run and longest return run to the equivalent lengths of every fitting in them. Straight length alone ignores fittings, which usually account for most of the pressure loss.