Texas Air Conditioning and Refrigeration Contractor Exam — All Questions
300 questions
Superheat is the:
- a.Pressure of a vapor above its saturation pressure
- b.Temperature of a vapor above its saturation temperature✓
- c.Heat that turns a saturated liquid into a vapor
- d.Temperature of a liquid below its saturation temperature
Superheat is the sensible heat added to a vapor after all the liquid has boiled off, measured in degrees above saturation at that pressure. Liquid below saturation temperature is subcooled.
Suction pressure corresponds to a saturation temperature of 40°F, and the suction line at the evaporator outlet measures 52°F. The superheat is:
- a.40°F
- b.8°F
- c.92°F
- d.12°F✓
Superheat is the measured line temperature minus the saturation temperature for the measured pressure: 52 minus 40 is 12°F. Adding the two numbers or reporting the saturation temperature itself are the usual mistakes.
Head pressure corresponds to a condensing temperature of 110°F, and the liquid line at the condenser outlet measures 98°F. The subcooling is:
- a.12°F✓
- b.208°F
- c.22°F
- d.98°F
Subcooling is saturation (condensing) temperature minus the measured liquid line temperature: 110 minus 98 is 12°F. It shows how much liquid is stacked in the condenser.
As the pressure on a liquid refrigerant is lowered, its boiling point:
- a.Falls✓
- b.Stays constant
- c.Doubles
- d.Rises
Boiling point follows pressure: lower pressure, lower saturation temperature. This is how the metering device lets refrigerant boil at a low temperature in the evaporator, and why a pressure-temperature chart can convert a gauge reading into coil temperature.
A gauge reads 70 psig at sea level. The absolute pressure is about:
- a.99.4 psia
- b.70.0 psia
- c.55.3 psia
- d.84.7 psia✓
Absolute pressure is gauge pressure plus atmospheric pressure, 14.7 psi at sea level: 70 plus 14.7 is 84.7 psia. Subtracting gives 55.3, which is wrong for a positive gauge reading.
A perfect vacuum at sea level corresponds to about:
- a.30 psig on the low-side gauge, or 1,000 microns absolute
- b.14.7 inches of mercury vacuum, or 500 microns absolute
- c.0 inches of mercury vacuum, or 760,000 microns absolute
- d.29.92 inches of mercury vacuum, or 0 microns absolute✓
Standard atmospheric pressure supports a 29.92-inch mercury column, so a perfect vacuum is 29.92 inches of mercury below atmosphere, or zero microns absolute. Atmospheric pressure is about 760,000 microns.
What happens to refrigerant as it passes through the metering device?
- a.Pressure rises while temperature drops and the vapor is superheated
- b.Pressure drops while temperature rises and the liquid is subcooled
- c.Pressure and temperature drop and part of the liquid flashes to vapor✓
- d.Pressure and temperature rise and all of the vapor condenses to liquid
The restriction drops the pressure to evaporator pressure; some liquid flashes to vapor, cooling the rest to the evaporating temperature. No heat is added or removed in the device itself.
In the refrigeration cycle, where is most of the heat absorbed from the conditioned space?
- a.In the condenser, as latent heat of condensation
- b.In the evaporator, as latent heat of vaporization✓
- c.In the liquid line, as sensible subcooling
- d.In the compressor, as heat of compression
The refrigerant boils in the evaporator and takes up latent heat from the air or product. The condenser rejects that heat plus the heat of compression.
The compression ratio of a compressor is:
- a.Absolute discharge pressure divided by absolute suction pressure✓
- b.Gauge discharge pressure divided by gauge suction pressure
- c.Absolute suction pressure divided by absolute discharge pressure
- d.Gauge discharge pressure minus the gauge suction pressure
Compression ratio uses absolute pressures: discharge psia over suction psia. Using gauge readings gives a wrong, larger number, and subtracting the pressures gives the pressure difference, not a ratio.
A system runs at 260 psig discharge and 60 psig suction at sea level. Using 15 psi for atmospheric pressure, the compression ratio is about:
- a.5.0 to 1
- b.3.7 to 1✓
- c.200 to 1
- d.4.3 to 1
Convert to absolute: 275 psia over 75 psia is about 3.7. Dividing the gauge pressures gives 4.3, which is the common error, and 200 is the pressure difference in psi.
On a psychrometric chart, the temperature at which moisture begins to condense out of air is the:
- a.Wet-bulb temperature
- b.Dew point temperature✓
- c.Saturation pressure
- d.Dry-bulb temperature
At the dew point the air is saturated, and any further cooling condenses water. Wet-bulb temperature reflects evaporative cooling and total heat, and dry-bulb is the ordinary thermometer reading.
Air leaves a cooling coil at a lower dry-bulb temperature and a lower moisture content than it entered. The coil has removed:
- a.Neither sensible heat nor latent heat
- b.Sensible heat only
- c.Latent heat only
- d.Both sensible and latent heat✓
A drop in dry-bulb temperature is sensible cooling and a drop in moisture content is latent cooling. A coil surface below the air's dew point does both, and the condensate leaves through the drain.
The total heat content of air, shown on the psychrometric chart in Btu per pound of dry air, is called:
- a.Enthalpy✓
- b.Relative humidity
- c.Entropy
- d.Specific volume
Enthalpy is total heat, sensible plus latent. Total cooling capacity can be found from 4.5 times CFM times the enthalpy difference across the coil. Specific volume is cubic feet per pound, and relative humidity is a percentage.
A coil handles 2,000 CFM. Entering air enthalpy is 30 Btu/lb and leaving air enthalpy is 24 Btu/lb. Using Q = 4.5 × CFM × Δh, the total capacity is:
- a.54,000 Btu/h, or 4.5 tons✓
- b.108,000 Btu/h, or 9 tons
- c.36,000 Btu/h, or 3 tons
- d.12,000 Btu/h, or 1 ton
4.5 times 2,000 times 6 is 54,000 Btu/h, and dividing by 12,000 gives 4.5 tons. 12,000 comes from leaving out the 4.5 factor, and 108,000 from doubling the enthalpy difference.
In a standard 24-volt thermostat circuit, which terminal energizes the cooling contactor?
- a.W
- b.Y✓
- c.C
- d.G
Y is the cooling call that energizes the contactor coil. W is heat, G is the indoor fan, and C is the common side of the transformer; R is the 24-volt supply.
A thermostat's G terminal is energized. Which component should run?
- a.The compressor
- b.The gas valve
- c.The reversing valve
- d.The indoor blower✓
G brings on the indoor fan relay or the blower through the control board. The compressor answers to Y, the heat to W, and the reversing valve to O or B.
A low-pressure switch on an air conditioning system opens to protect the compressor when:
- a.Oil pressure falls too low, as with a failed oil pump
- b.Discharge pressure rises too high, as with a dirty coil
- c.Suction pressure falls too low, as with loss of charge✓
- d.Suction pressure rises too high, as with overcharge
The low-pressure control opens the control circuit when suction pressure drops, which happens with a refrigerant leak, a restriction, or a frozen coil. High discharge pressure is the high-pressure switch's job, and oil failure is handled by an oil safety control.
A high-pressure cutout that must be reset by hand after it trips is used so that:
- a.Someone finds and corrects the cause before a restart✓
- b.The thermostat is bypassed during the high load
- c.The compressor restarts as soon as the pressure falls
- d.The condenser fan cycles to control head pressure
A manual-reset safety forces a person to investigate, for example a failed condenser fan or blocked coil, before the system runs again. An automatic-reset control would let the compressor cycle repeatedly on a dangerous condition.
On a gas furnace, the high-limit switch opens when:
- a.Air temperature at the room thermostat rises too high
- b.Flue draft falls below the setting of the inducer switch
- c.Gas pressure in the manifold rises above the setting
- d.Air temperature in the heat exchanger area rises too high✓
The limit senses overheating at the heat exchanger, usually from low airflow such as a dirty filter or failed blower, and shuts the burners off. Draft is proved by the pressure switch, and the room thermostat is an operating control, not a safety.
What does the pressure switch on an induced-draft furnace prove?
- a.That the gas valve is supplying the correct manifold pressure
- b.That the inducer is moving combustion air through the vent✓
- c.That the igniter has reached its full ignition temperature
- d.That the main blower is moving air across the heat exchanger
The switch closes on the negative pressure created by the inducer, proving venting before ignition is allowed. A blocked flue, failed inducer, or cracked tubing keeps it open and locks out the burner.
A flame rectification sensor proves burner flame by:
- a.Passing a small DC current through the flame to ground✓
- b.Opening a bimetal contact when its tip is heated
- c.Generating a millivolt signal when its tip is heated
- d.Measuring ultraviolet light given off by the flame
The control applies AC to the flame rod, and the flame conducts and rectifies it into a microamp DC signal to the grounded burner. A thermocouple generates millivolts, which is a different and older method.
A thermocouple used on a standing-pilot gas valve produces about:
- a.120 volts
- b.24 volts
- c.30 millivolts✓
- d.750 millivolts
A single thermocouple heated by the pilot generates roughly 25 to 30 millivolts, enough to hold the safety magnet in. A thermopile (pilot generator) produces about 750 millivolts, and 24 volts comes from a transformer.
A contactor is used in a condensing unit to:
- a.Limit the starting current drawn by the compressor
- b.Let a line-voltage circuit switch the 24-volt control load
- c.Let a 24-volt control circuit switch the line-voltage load✓
- d.Protect the compressor windings from overheating
The low-voltage coil pulls in contacts that carry compressor and fan motor current. Overload protection and start assistance are done by other components.
A control transformer is rated 40 VA with a 24-volt secondary. What is the maximum secondary current?
- a.About 0.60 amps
- b.About 1.67 amps✓
- c.About 16.0 amps
- d.About 960 amps
Current equals volt-amperes divided by volts: 40 divided by 24 is about 1.67 amps. Dividing 24 by 40 gives 0.6, and multiplying the two gives 960, neither of which is a current.
A heat pump defrost cycle is normally ended by:
- a.The outdoor fan motor reaching full speed
- b.A coil temperature sensor or a maximum time limit✓
- c.The low-pressure switch opening the circuit
- d.A drop in indoor temperature at the thermostat
Defrost terminates when the outdoor coil sensor reaches its set temperature, with a timer as a backup limit. During defrost the outdoor fan is off and auxiliary heat tempers the indoor air.
An economizer on a rooftop unit is a control arrangement that:
- a.Uses return air to precool the outdoor condenser coil
- b.Uses stored chilled water to cool during peak hours
- c.Uses warm condenser air to reheat the supply air
- d.Uses cool outdoor air for cooling when conditions allow✓
An air-side economizer opens outdoor air dampers for free cooling when outdoor temperature or enthalpy is suitable, reducing compressor run time. It also provides minimum ventilation air at other times.
An enthalpy economizer control differs from a dry-bulb control because it also takes account of:
- a.Outdoor air velocity
- b.Return air volume
- c.Outdoor air humidity✓
- d.Supply duct pressure
Enthalpy is total heat, so the control considers moisture as well as temperature and will not bring in cool but humid air that would add latent load. A dry-bulb control looks at temperature only.
What is the purpose of the anti-short-cycle (time delay) control on a compressor?
- a.To let the crankcase heater turn off during operation
- b.To let the evaporator fan run after the compressor stops
- c.To let pressures equalize before the compressor restarts✓
- d.To let the thermostat reach its setpoint more quickly
A delay of a few minutes prevents a restart against a high pressure difference, which can stall the motor and trip its overload. Fan-off delay is a separate function.
Low-ambient head pressure control on an air-cooled condenser is commonly done by:
- a.Closing the liquid line solenoid
- b.Raising the thermostat setpoint
- c.Cycling or slowing the condenser fan✓
- d.Cycling the evaporator blower motor
In cold weather the condenser rejects heat too easily and head pressure drops, starving the metering device. Fan cycling, fan speed control, or condenser flooding keep head pressure up.
In a pump-down control arrangement, the thermostat directly controls the:
- a.Condenser fan motor relay
- b.Compressor contactor coil
- c.Liquid line solenoid valve✓
- d.Crankcase heater circuit
On a call for cooling the thermostat opens the liquid line solenoid; rising suction pressure closes the low-pressure control, which starts the compressor. When satisfied, the solenoid closes and the compressor pumps the low side down until the low-pressure control opens.
A thermostat's heat anticipator or cycle-rate setting is used to:
- a.Prevent the space temperature from overshooting the setpoint✓
- b.Prevent the blower from running after the burners shut off
- c.Prevent the furnace limit from opening on a long call for heat
- d.Prevent the compressor from starting under a locked rotor
The anticipator ends the call for heat slightly early so residual heat in the furnace brings the room to setpoint without overshoot. It is matched to the control circuit current or set as cycles per hour.
An oil pressure safety control on a commercial compressor acts on:
- a.Crankcase pressure alone, read at the suction service valve
- b.Total oil pressure, pump discharge plus crankcase pressure
- c.Discharge pressure alone, read at the discharge service valve
- d.Net oil pressure, pump discharge minus crankcase pressure✓
Useful oil pressure is the pump outlet pressure minus crankcase (suction) pressure. The control has a time delay so the compressor can build oil pressure at start-up and shuts it down if net pressure stays too low.
A normally open control contact is one that:
- a.Is open when its coil or sensor is de-energized✓
- b.Is open at all times unless reset by hand
- c.Is open when its coil or sensor is energized
- d.Is open only when the line voltage is low
Contacts are named for their position with no power or signal applied. A normally open contact closes when the relay coil is energized; a normally closed contact opens.
A two-stage cooling thermostat brings on the second stage when:
- a.The outdoor temperature falls below the balance point
- b.The first stage has run for less than one minute
- c.The indoor fan is switched to continuous operation
- d.The first stage cannot hold the space at setpoint✓
Second stage is called when the temperature keeps drifting from setpoint, by a set difference or after a time, showing that first-stage capacity is not enough for the load.
Under the standard method in IFGC §304.5.1, an indoor space supplies enough combustion air without added openings when it has at least how much volume?
- a.50 cubic feet per 10,000 Btu/h of total appliance input
- b.50 cubic feet per 1,000 Btu/h of total appliance input✓
- c.100 cubic feet per 1,000 Btu/h of total appliance input
- d.25 cubic feet per 1,000 Btu/h of total appliance input
The standard method requires 50 cubic feet of room volume for each 1,000 Btu/h of input for all appliances in the space. Less volume means air must be brought from adjoining spaces or outdoors.IFGC §304.5.1
A mechanical room holds a 100,000 Btu/h furnace and a 40,000 Btu/h water heater, both drawing combustion air from the room. By the IFGC standard method, the minimum room volume with no added openings is:
- a.7,000 cubic feet✓
- b.2,800 cubic feet
- c.14,000 cubic feet
- d.5,000 cubic feet
Total input is 140,000 Btu/h; at 50 cubic feet per 1,000 Btu/h that is 7,000 cubic feet. 5,000 counts only the furnace, and 14,000 doubles the factor.IFGC §304.5.1
An appliance closet is joined to the rest of the house by two permanent openings to supply combustion air from indoors. Under IFGC §304.5.3.1, each opening must have a free area of at least:
- a.1 square inch per 2,000 Btu/h, and not less than 50 square inches
- b.1 square inch per 1,000 Btu/h, and not less than 100 square inches✓
- c.1 square inch per 3,000 Btu/h, and not less than 200 square inches
- d.1 square inch per 4,000 Btu/h, and not less than 100 square inches
When spaces on the same story are combined, each of the two openings needs 1 square inch per 1,000 Btu/h of total input with a 100-square-inch minimum. The 4,000, 2,000 and 3,000 figures belong to the outdoor air methods.IFGC §304.5.3.1
Two combustion air openings communicate directly with the outdoors, one high and one low. Under IFGC §304.6.1, each must provide at least:
- a.1 square inch of free area per 2,000 Btu/h
- b.1 square inch of free area per 4,000 Btu/h✓
- c.1 square inch of free area per 1,000 Btu/h
- d.1 square inch of free area per 5,000 Btu/h
Direct openings or vertical ducts to outdoors require 1 square inch per 4,000 Btu/h for each of the two openings. The 2,000 figure applies when the air comes through horizontal ducts, and 1,000 applies to indoor openings.IFGC §304.6.1
Combustion air is brought to an appliance room through two horizontal ducts from outdoors. Under IFGC §304.6.1, each duct must provide free area of at least:
- a.1 square inch per 4,000 Btu/h
- b.1 square inch per 3,000 Btu/h
- c.1 square inch per 2,000 Btu/h✓
- d.1 square inch per 1,000 Btu/h
Horizontal ducts have more resistance than vertical ducts or direct openings, so the requirement doubles to 1 square inch per 2,000 Btu/h. The 3,000 figure is used for the single-opening method.IFGC §304.6.1
A furnace and water heater totaling 120,000 Btu/h get combustion air through two vertical ducts from a ventilated attic. Using IFGC §304.6.1, the minimum free area of each duct is:
- a.60 square inches
- b.120 square inches
- c.40 square inches
- d.30 square inches✓
Vertical ducts use 1 square inch per 4,000 Btu/h: 120,000 divided by 4,000 is 30 square inches each. Sixty square inches would be the horizontal-duct answer and 40 the one-opening answer.IFGC §304.6.1
Under the one-permanent-opening method in IFGC §304.6.2, the single opening to outdoors is sized at:
- a.1 square inch per 1,000 Btu/h, located within 18 inches of the top of the space
- b.1 square inch per 3,000 Btu/h, located within 12 inches of the bottom of the space
- c.1 square inch per 4,000 Btu/h, located at the midpoint of the appliance room wall
- d.1 square inch per 3,000 Btu/h, located within 12 inches of the top of the space✓
The single-opening method uses 1 square inch per 3,000 Btu/h, placed within 12 inches of the top of the enclosure, and not smaller than the combined area of the vent connectors. The low location and the other ratios do not match this method.IFGC §304.6.2
Where the upper and lower combustion air openings are used, the IFGC places them:
- a.Within 24 inches of the top and within 24 inches of the bottom
- b.Within 12 inches of the top and within 12 inches of the bottom✓
- c.Within 6 inches of the top and at the level of the burner
- d.At any height, provided they are on opposite walls
One opening starts within 12 inches of the top of the enclosure and the other within 12 inches of the bottom, which sets up a natural circulation of air through the space.IFGC §304.5.3.1, §304.6.1
A combustion air opening is covered by a metal louver and the manufacturer's free area is not known. IFGC §304.10 allows you to assume the free area is:
- a.50% of the gross louver area
- b.25% of the gross louver area
- c.75% of the gross louver area✓
- d.90% of the gross louver area
Without manufacturer data, metal louvers and grilles are taken as 75% free area and wood louvers as 25%. The opening must be enlarged so that the net free area meets the requirement.IFGC §304.10
An opening needs 100 square inches of free area and will be covered with a wood louver of unknown free area. Using the IFGC default for wood louvers, the gross opening must be at least:
- a.200 square inches
- b.133 square inches
- c.400 square inches✓
- d.125 square inches
Wood louvers are assumed to be 25% free area, so 100 divided by 0.25 is 400 square inches. 133 square inches would be right for a metal louver at 75%.IFGC §304.10
A direct-vent gas furnace takes its combustion air:
- a.Directly from outdoors through a sealed intake pipe✓
- b.From the equipment room through louvered doors
- c.From the return air duct just ahead of the main blower
- d.From the attic through an open vertical duct
A direct-vent appliance has a sealed combustion system: all combustion air comes from outdoors and all flue gas goes outdoors, so it does not rely on room air. Combustion air is never taken from the return duct.
Why may combustion air not be taken from a room where an exhaust fan or return leak creates negative pressure?
- a.Flame temperature can rise and overheat the primary heat exchanger
- b.Vent connector joints can loosen under the higher draft that results
- c.Gas pressure at the burner can rise above the rated manifold value
- d.Flue gases can be drawn back into the room instead of venting✓
Negative pressure in the appliance space can overcome natural draft and cause spillage or backdrafting, bringing carbon monoxide indoors. The code requires makeup air for exhaust systems so appliance operation is not affected.IFGC §304.4
Incomplete combustion from a shortage of air is indicated at a gas burner by:
- a.Lazy yellow flames, soot, and carbon monoxide✓
- b.Short blue flames lifting off the burner ports
- c.Sharp blue flames with a clear inner cone
- d.Flames that light quietly and burn steadily
Too little primary or secondary air gives soft, yellow-tipped flames, soot, and carbon monoxide. Flames lifting off the ports point to too much primary air or pressure, and a stable blue flame with a defined inner cone is normal.
Screens on outdoor combustion air openings must have mesh openings no smaller than:
- a.1/4 inch✓
- b.1/16 inch
- c.1/8 inch
- d.1/2 inch
The mesh may not be smaller than 1/4 inch so that it does not clog easily with lint and debris and choke off the air supply.IFGC §304.10
A wall has an R-value of 20. Its U-factor is:
- a.20.0 Btu/h per square foot per °F
- b.0.05 Btu/h per square foot per °F✓
- c.0.50 Btu/h per square foot per °F
- d.0.20 Btu/h per square foot per °F
U is the reciprocal of R: 1 divided by 20 is 0.05. A higher R-value means a lower U-factor and less heat flow.
A 200-square-foot wall has a U-factor of 0.05 and the design temperature difference is 60°F. The conduction heat loss is:
- a.6,000 Btu/h
- b.600 Btu/h✓
- c.240 Btu/h
- d.1,200 Btu/h
Heat flow equals U times area times temperature difference: 0.05 times 200 times 60 is 600 Btu/h. This is the basic envelope calculation behind a Manual J load.