Texas Air Conditioning and Refrigeration Contractor Exam — All Questions

300 questions

Air Distribution

Why does a duct fitting such as a sharp elbow get an "equivalent length" in duct design?

  • a.Its air leakage is expressed as the length of unsealed duct with the same loss
  • b.Its pressure loss is expressed as the length of straight duct with the same loss✓
  • c.Its noise level is expressed as the length of lined duct needed to absorb it
  • d.Its sheet metal area is expressed as the length of straight duct it replaces

Equivalent length states a fitting's pressure drop as feet of straight duct that would cause the same drop, so fittings and straight duct can be added together. It is not a measure of material, leakage, or noise.

Air Distribution

Using a duct calculator at a friction rate of 0.10 inches w.c. per 100 feet, which round metal duct is the usual selection for 1,000 CFM?

  • a.12-inch round
  • b.10-inch round
  • c.14-inch round✓
  • d.18-inch round

At 0.10 inches per 100 feet, a duct calculator shows about 14 inches round for 1,000 CFM. A 10-inch duct carries roughly 400 CFM and a 12-inch about 650 CFM at that friction rate; an 18-inch is oversized. On the open-book exam, read this from the calculator rather than from memory.

Air Distribution

Using a duct calculator at 0.10 inches w.c. per 100 feet, about how much air does a 6-inch round metal branch carry?

  • a.About 200 CFM
  • b.About 100 CFM✓
  • c.About 50 CFM
  • d.About 300 CFM

A 6-inch round duct at 0.10 inches per 100 feet carries roughly 100 CFM, which is why it is the common branch for a small bedroom. About 200 CFM calls for an 8-inch duct at the same friction rate.

Air Distribution

Flexible duct is installed with long sags and is not pulled tight. Compared with the same duct fully extended, the airflow will be:

  • a.Higher, because the longer air path lowers velocity
  • b.Higher, because the inner liner becomes much smoother
  • c.Unchanged, because the duct diameter stays the same
  • d.Lower, because compression raises friction loss sharply✓

A compressed or sagging flexible duct has a corrugated inner surface and a longer path, both of which raise friction loss and cut airflow. Flexible duct should be cut to length, fully extended, and supported per the manufacturer's instructions.

Air Distribution

Which return air location does the mechanical code prohibit for a residential forced-air system (IMC §601.5)?

  • a.A living room
  • b.A bathroom✓
  • c.A dining room
  • d.A hallway

Return air may not be taken from a bathroom, toilet room, kitchen, garage, closet, mechanical room, or boiler room, because odors, moisture, or combustion products would be spread through the building. Hallways and living areas are normal return locations.IMC §601.5

Air Distribution

A furnace is installed in a closet that also holds a draft-hood gas water heater, and the return duct in the closet has a large gap at the filter rack. The main hazard is that the blower will:

  • a.Pressurize the closet and push too much gas through the burner orifices
  • b.Depressurize the closet and pull flue gases back down the draft hood✓
  • c.Overheat the closet and cause the furnace high limit to open on each cycle
  • d.Overcool the closet and cause the water heater thermostat to short cycle

A return leak in an appliance room puts the room under negative pressure, which can reverse the draft of a natural-draft appliance and spill carbon monoxide. This is why return air may not be drawn from a mechanical room and return ducts there must be sealed.IMC §601.5

Air Distribution

Under IMC §606.2.1, a smoke detector is required in the return air of an air distribution system when its design capacity exceeds:

  • a.5,000 CFM
  • b.15,000 CFM
  • c.2,000 CFM✓
  • d.1,000 CFM

The trigger for a return air smoke detector is a design capacity greater than 2,000 CFM. The detector shuts the fan down so the system does not spread smoke. 15,000 CFM is the threshold in the separate rule for return air risers serving two or more stories.IMC §606.2.1

Air Distribution

Exposed materials inside a plenum must generally have what maximum flame spread and smoke-developed indexes (IMC §602.2.1)?

  • a.Flame spread 200 and smoke-developed 450
  • b.Flame spread 25 and smoke-developed 50✓
  • c.Flame spread 75 and smoke-developed 450
  • d.Flame spread 50 and smoke-developed 25

Materials exposed in plenums are limited to a flame spread index of not more than 25 and a smoke-developed index of not more than 50. The other pairs reverse the numbers or use limits that apply to ordinary interior finishes.IMC §602.2.1

Air Distribution

What is the purpose of a fire damper where a duct passes through a fire-resistance-rated wall?

  • a.It closes on heat to keep fire from passing through the duct opening✓
  • b.It opens on heat to relieve the pressure built up inside the duct
  • c.It closes on a call for cooling to isolate zones that are satisfied
  • d.It modulates to balance airflow between the two sides of the wall

A fire damper has a fusible link or similar device that closes the damper when heated, restoring the wall's fire rating at the duct opening. Balancing and zone dampers have different jobs and are not rated for this use.IMC §607

Air Distribution

Pressure-sensitive tape used to seal joints in flexible air ducts and connectors must be:

  • a.Standard cloth-backed tape with a rubber adhesive
  • b.Any foil tape at least two inches in overall width
  • c.Listed and labeled to UL 181B and marked accordingly✓
  • d.Electrical vinyl tape rated for 600-volt service

The mechanical code requires tapes and mastics used on flexible ducts to be listed to UL 181B and marked (181B-FX for tape, 181B-M for mastic). Ordinary cloth duct tape is not listed for this use and fails with heat and age.IMC §603.9

Air Distribution

A filter's MERV rating describes its:

  • a.Resistance to airflow when it is clean
  • b.Ability to capture particles of stated sizes✓
  • c.Expected service life in a normal home
  • d.Maximum allowed face velocity in service

MERV (minimum efficiency reporting value) rates how well a filter captures particles in set size ranges; a higher number captures smaller particles. Pressure drop, face velocity limits and service life are separate data from the manufacturer.

Air Distribution

A customer replaces a 1-inch fiberglass filter with a 1-inch high-MERV pleated filter in the same rack. With no other change, the most likely effect is:

  • a.Lower pressure drop and higher system airflow
  • b.No change in pressure drop or in airflow
  • c.Higher pressure drop and lower system airflow✓
  • d.Higher airflow and a lower temperature rise

A denser filter of the same size normally has more resistance, so static pressure rises and airflow falls, which can raise furnace temperature rise or cause coil icing. More filter area, such as a deeper media cabinet, is the way to add efficiency without that penalty.

Air Distribution

A return air filter grille must handle 1,200 CFM at a face velocity of no more than 300 feet per minute. What is the minimum gross face area?

  • a.2.5 square feet
  • b.4 square feet✓
  • c.6 square feet
  • d.3 square feet

Area equals airflow divided by velocity: 1,200 divided by 300 is 4 square feet, for example a 24 by 24 inch grille. A smaller grille raises velocity, noise and pressure drop.

Air Distribution

In register selection, "throw" is the:

  • a.Distance the airstream falls below the outlet at the end of its travel
  • b.Volume of room air pulled into the airstream as it leaves the outlet
  • c.Distance the airstream travels before slowing to a stated terminal velocity✓
  • d.Width the airstream reaches as it fans out from the face of the outlet

Throw is the horizontal or vertical distance air travels from the outlet until its velocity drops to a stated terminal value, often 50 fpm. Drop is how far it falls, spread is how wide it fans out, and induction or entrainment is the room air it pulls along.

Air Distribution

For heating in a cold climate, perimeter floor supply outlets are placed under windows mainly to:

  • a.Reduce the amount of return air that is needed
  • b.Shorten the branch duct runs from the trunk
  • c.Keep supply air away from the room thermostat
  • d.Blanket the cold glass and offset downdrafts✓

Warm air rising from a perimeter outlet washes the coldest surface, offsetting the downdraft from glass and exterior walls. The location usually lengthens branch runs rather than shortening them, and it does not change return air requirements.

Air Distribution

What is the purpose of turning vanes in a square duct elbow?

  • a.To filter large particles out of the moving airstream
  • b.To cut turbulence and pressure loss through the elbow✓
  • c.To raise the velocity of the air leaving the elbow
  • d.To stop sound from travelling along the duct wall

Turning vanes guide the air around a mitered elbow so it does not pile up against the outside wall, which greatly reduces the fitting's pressure loss. They are not filters or sound attenuators.

Air Distribution

A manual volume damper in a branch duct is used to:

  • a.Balance airflow to the outlet served by that branch✓
  • b.Stop fire from spreading through the branch duct
  • c.Shut the branch whenever the thermostat is satisfied
  • d.Prevent backdraft when the blower is switched off

A manual balancing damper is set once to proportion air among branches. Fire dampers, backdraft dampers and motorized zone dampers are different devices with different functions.

Air Distribution

A duct system is designed to the same friction rate throughout so that pressure loss per foot is constant. This is called the:

  • a.Velocity reduction method
  • b.Constant volume method
  • c.Equal friction method✓
  • d.Static regain method

The equal friction method sizes every section for the same pressure loss per 100 feet and is the usual residential and light commercial approach. Static regain sizes sections so that falling velocity recovers static pressure, and velocity reduction assigns velocities to each section.

Air Distribution

Two round ducts are compared for the same airflow. If the diameter is cut in half, the velocity in the smaller duct is:

  • a.Half as high
  • b.Four times as high✓
  • c.Twice as high
  • d.Eight times as high

Area varies with the square of the diameter, so half the diameter is one quarter of the area, and the same airflow must move four times as fast. Friction loss rises far more steeply, which is why undersized ducts are so restrictive.

Air Distribution

A system mixes 300 CFM of outdoor air at 95°F with 900 CFM of return air at 75°F. What is the mixed air dry-bulb temperature entering the coil?

  • a.78°F
  • b.85°F
  • c.90°F
  • d.80°F✓

Weight each stream by its airflow: (300 times 95 plus 900 times 75) divided by 1,200 is 80°F. 85°F is the simple average of the two temperatures, which ignores that three quarters of the air is return air.

Air Distribution

Supply ducts in a vented attic are insulated and wrapped with a vapor retarder mainly to:

  • a.Protect the duct from rodents and physical damage
  • b.Add stiffness and prevent sagging between hangers
  • c.Limit heat gain and stop condensation on the duct✓
  • d.Limit air noise and stop vibration in the duct

Cold supply air in a hot, humid attic gains heat and can drop the duct surface below the attic air's dew point. Insulation cuts the heat gain and the outer vapor retarder keeps moist air from reaching the cold surface.

Air Distribution

A high-velocity return grille whistles and the blower is starved for air. Which correction addresses the cause?

  • a.Raise the blower speed to pull the air through faster
  • b.Close several supply registers to reduce the airflow
  • c.Add return grille and duct area to lower the velocity✓
  • d.Add a denser filter to quiet the air at the grille

Noise and starvation at a return mean too little free area for the airflow, so the fix is more return area. A denser filter and closed registers add restriction, and a higher blower speed raises velocity and noise further.

Air Distribution

When measuring airflow at a supply register with a flow capture hood, the reading is taken in:

  • a.Pounds per square inch
  • b.Cubic feet per minute✓
  • c.Inches of water column
  • d.Feet per minute

A capture hood channels all the air from the outlet across a sensing grid and reads volume flow directly in CFM. An anemometer reads velocity in fpm, and a manometer reads pressure in inches of water column.

Air Distribution

A flexible vibration connector between the air handler and the metal supply plenum is installed to:

  • a.Keep equipment vibration from passing into the duct system✓
  • b.Keep the plenum from expanding when the heat is running
  • c.Keep return air from bypassing the filter at the cabinet
  • d.Keep conditioned air from leaking out at the plenum collar

The fabric connector breaks the metal-to-metal path so blower vibration and noise are not carried through the ductwork. It is not a seal, an expansion joint, or a filter bypass control.

Air Distribution

A duct's aspect ratio is the ratio of its:

  • a.Airflow to its friction loss
  • b.Area to its air velocity
  • c.Length to its perimeter
  • d.Long side to its short side✓

Aspect ratio is width divided by height for a rectangular duct. As it rises, the duct has more surface for the same area, so friction and cost go up; designers try to keep it low, with a square duct at 1 to 1.

Air Distribution

A cooling system has a measured airflow well below design. Which symptom is consistent with low airflow across the evaporator?

  • a.High suction pressure with a warm coil that sweats
  • b.High head pressure with a normal suction pressure
  • c.Low suction pressure with a cold coil that may frost✓
  • d.Normal pressures with a high supply air temperature

With too little air the coil cannot pick up enough heat, so evaporating pressure and temperature fall and the coil may ice. The temperature drop across the coil is larger than normal, not smaller.

Basic Refrigeration Components

In a vapor-compression system, the refrigerant leaves the compressor as a:

  • a.High-pressure, low-temperature subcooled liquid
  • b.Low-pressure, low-temperature saturated vapor
  • c.Low-pressure, high-temperature superheated liquid
  • d.High-pressure, high-temperature superheated vapor✓

The compressor raises the pressure and temperature of vapor, so discharge gas is high-pressure superheated vapor. Subcooled liquid is found leaving the condenser, and low-pressure vapor is what enters the compressor.

Basic Refrigeration Components

The main job of the condenser is to:

  • a.Raise the pressure of the vapor leaving the evaporator
  • b.Drop the pressure of the liquid ahead of the evaporator
  • c.Reject heat so the high-pressure vapor becomes a liquid✓
  • d.Absorb heat so the low-pressure liquid becomes a vapor

The condenser desuperheats, condenses and usually subcools the refrigerant by rejecting heat to air or water. Absorbing heat is the evaporator's job, dropping pressure is the metering device's, and raising pressure is the compressor's.

Basic Refrigeration Components

Which metering device modulates refrigerant flow to hold a set superheat at the evaporator outlet?

  • a.Thermostatic expansion valve✓
  • b.Capillary tube
  • c.Automatic (constant-pressure) expansion valve
  • d.Fixed-bore piston

A thermostatic expansion valve senses suction line temperature with its bulb and adjusts flow to maintain superheat. Capillary tubes and pistons are fixed restrictions, and an automatic expansion valve holds a constant evaporator pressure rather than superheat.

Basic Refrigeration Components

Where is the sensing bulb of a thermostatic expansion valve mounted?

  • a.On the discharge line at the compressor
  • b.On the distributor at the evaporator inlet
  • c.On the liquid line at the condenser outlet
  • d.On the suction line at the evaporator outlet✓

The bulb reads the temperature of vapor leaving the evaporator so the valve can control superheat. It must be clamped tight to clean suction line and insulated; mounting it anywhere else gives the valve a false signal.

Basic Refrigeration Components

An externally equalized expansion valve is used on an evaporator that has:

  • a.A very small pressure drop, such as a short single-circuit coil
  • b.A significant pressure drop, such as a coil with a distributor✓
  • c.A flooded design with a low-side float and a surge drum
  • d.A capillary tube feeding each of its parallel circuits

The external equalizer line brings evaporator outlet pressure to the underside of the diaphragm so that pressure drop through the distributor and coil does not make the valve starve the coil. Small single-circuit coils work with internal equalization.

Basic Refrigeration Components

Which compressor type compresses vapor between one fixed and one orbiting spiral?

  • a.Rotary vane
  • b.Centrifugal
  • c.Reciprocating
  • d.Scroll✓

A scroll compressor traps gas in pockets between a stationary and an orbiting scroll and squeezes it toward the center. Reciprocating compressors use pistons, rotary compressors use a rolling piston or vanes, and centrifugal machines use impeller speed.

Basic Refrigeration Components

Why is liquid refrigerant returning to a reciprocating compressor harmful?

  • a.Liquid lowers the discharge pressure and stalls the motor at start-up
  • b.Liquid raises the superheat and overheats the windings
  • c.Liquid freezes in the cylinders and blocks the valves
  • d.Liquid cannot be compressed and it washes oil from the bearings✓

Liquid floodback dilutes and washes away oil, and a slug of liquid in a cylinder can break valves, rods or the crankshaft because liquid does not compress. Floodback shows up as low or zero superheat, not high superheat.

Basic Refrigeration Components

The purpose of a crankcase heater is to:

  • a.Warm the suction gas to raise the superheat at start-up
  • b.Dry any moisture out of the motor windings before start
  • c.Keep refrigerant from condensing in the oil during the off cycle✓
  • d.Keep the oil thin enough to be pumped back through the suction line

During the off cycle refrigerant migrates to the coldest part of the system, often the compressor crankcase. The heater keeps the oil warmer than the rest of the system so refrigerant does not collect there and cause foaming and a flooded start.

Basic Refrigeration Components

A filter-drier in the liquid line removes:

  • a.Moisture, acid and solid particles✓
  • b.Flash gas ahead of the metering device
  • c.Oil, wax and excess refrigerant
  • d.Air and other noncondensable gases

The desiccant core adsorbs moisture and acid and the filter traps solids. A drier does not remove noncondensables, which must be evacuated or purged, and it does not remove oil, which has to circulate.

Basic Refrigeration Components

Where does a suction line accumulator sit, and what does it do?

  • a.Between condenser and metering device; it stores liquid for varying loads
  • b.Between metering device and evaporator; it divides flow among circuits
  • c.Between compressor and condenser; it separates oil from discharge vapor
  • d.Between evaporator and compressor; it traps liquid so only vapor returns✓

The accumulator is in the suction line and catches liquid refrigerant, metering it back as vapor with oil. A receiver stores liquid after the condenser, an oil separator is in the discharge line, and a distributor feeds evaporator circuits.

Basic Refrigeration Components

A liquid receiver is normally found on systems that use:

  • a.A capillary tube
  • b.A thermostatic expansion valve✓
  • c.A fixed-orifice piston
  • d.A critically charged fixed-restriction coil

Expansion valve systems vary the amount of refrigerant in the evaporator with load, and the receiver stores the difference. Fixed-restriction systems are critically charged and normally have no receiver, since extra liquid would flood the evaporator.

Basic Refrigeration Components

In a heat pump, the component that changes the system between heating and cooling is the:

  • a.Four-way reversing valve✓
  • b.Check valve at the piston
  • c.Bi-flow filter-drier
  • d.Defrost control board

The reversing valve redirects discharge gas to either the outdoor or indoor coil, swapping which one is the condenser. Check valves and bi-flow driers let the system work in both directions, and the defrost board decides when to switch, but the valve does the switching.

Basic Refrigeration Components

R-410A is classed by ASHRAE Standard 34 as A1. What do the letter and number indicate?

  • a.Lower toxicity and no flame propagation✓
  • b.Higher toxicity and no flame propagation
  • c.Higher toxicity and higher flammability
  • d.Lower toxicity and lower flammability

In the safety classification, A means lower toxicity and B higher toxicity; 1 means no flame propagation, 2L and 2 lower flammability, and 3 higher flammability. A1 is therefore the least hazardous group.ASHRAE Standard 34

Basic Refrigeration Components

R-32 and R-454B, used in newer comfort cooling equipment, carry which ASHRAE Standard 34 safety classification?

  • a.A1
  • b.B2L
  • c.A3
  • d.A2L✓

R-32 and R-454B are A2L: lower toxicity with lower flammability and a low burning velocity. A1 refrigerants such as R-410A do not propagate flame, B2L includes ammonia, and A3 covers hydrocarbons such as propane.ASHRAE Standard 34

Basic Refrigeration Components

A blended refrigerant with a noticeable temperature glide should be charged into a system:

  • a.As a liquid or a vapor, since the blend does not separate
  • b.As a vapor, so the blend's composition does not change
  • c.As a vapor, so the compressor is not slugged at start-up
  • d.As a liquid, so the blend's composition does not change✓

Zeotropic blends fractionate: vapor leaving the cylinder is richer in the more volatile components. Removing liquid keeps the composition correct. Liquid is throttled into the suction side to protect the compressor.

Basic Refrigeration Components

What is the effect of a dirty air-cooled condenser coil?

  • a.Head pressure and compressor amperage both rise✓
  • b.Head pressure and compressor amperage both fall
  • c.Head pressure falls and suction pressure rises
  • d.Head pressure rises and compressor amperage falls

A dirty condenser cannot reject heat, so condensing temperature and pressure climb. The compressor works against a higher pressure, draws more current, and loses capacity.

Basic Refrigeration Components

An evaporator used for comfort cooling in which refrigerant boils inside the tubes and is fully vaporized before the outlet is called a:

  • a.Plate heat exchanger
  • b.Direct-expansion evaporator✓
  • c.Flooded evaporator
  • d.Shell-and-tube water-cooled condenser

A direct-expansion (dry) evaporator is fed by a metering device and has superheated vapor at its outlet. A flooded evaporator keeps the tubes wet with liquid and uses a float or level control.

Basic Refrigeration Components

On a water-cooled condensing unit, a water regulating valve controls flow in response to:

  • a.Suction pressure
  • b.Oil pressure
  • c.Water pressure
  • d.Head pressure✓

The valve opens as head pressure rises and closes as it falls, holding condensing pressure and saving water. It shuts when the compressor stops and head pressure drops.

Refrigeration Principles

One ton of refrigeration is a rate of heat removal equal to:

  • a.10,000 Btu per hour
  • b.2,000 Btu per hour
  • c.12,000 Btu per hour✓
  • d.24,000 Btu per hour

A ton is 12,000 Btu/h, or 200 Btu per minute, taken from the heat needed to melt one ton of ice in 24 hours (288,000 Btu per day). The other values are not standard definitions.

Refrigeration Principles

Heat that changes the temperature of a substance without changing its state is:

  • a.Superheat
  • b.Specific heat
  • c.Latent heat
  • d.Sensible heat✓

Sensible heat can be measured with a thermometer. Latent heat changes state at constant temperature, specific heat is a property (Btu per pound per degree), and superheat is temperature above saturation.

Refrigeration Principles

How much heat does it take to raise 10 pounds of water from 60°F to 100°F?

  • a.40 Btu
  • b.970 Btu
  • c.4,000 Btu
  • d.400 Btu✓

One Btu raises one pound of water one degree Fahrenheit, so 10 pounds times 40 degrees is 400 Btu. The 970 figure is the latent heat of vaporization of one pound of water at atmospheric pressure, which does not apply here.

Refrigeration Principles

The latent heat of fusion of water, the heat removed to freeze one pound of water at 32°F, is about:

  • a.1 Btu
  • b.180 Btu
  • c.144 Btu✓
  • d.970 Btu

Freezing or melting one pound of water at 32°F involves about 144 Btu. About 970 Btu per pound is the latent heat of vaporization at 212°F, and 1 Btu per pound per degree is water's specific heat.

Refrigeration Principles

Heat always flows naturally:

  • a.From a warmer substance to a cooler one✓
  • b.From a lower pressure to a higher one
  • c.From a cooler substance to a warmer one
  • d.From a liquid toward a nearby vapor

Heat moves from higher temperature to lower temperature. A refrigeration system does not reverse this; it makes the refrigerant colder than the space so heat flows into it, then hotter than the outdoors so heat flows out.

Refrigeration Principles

Heat transfer through a solid copper tube wall takes place by:

  • a.Evaporation
  • b.Radiation
  • c.Convection
  • d.Conduction✓

Conduction is heat transfer through a material or between materials in contact. Convection moves heat with a fluid, and radiation travels as waves without needing a medium.