Texas Air Conditioning and Refrigeration Contractor Exam — All Questions

300 questions

Service

On a fixed-orifice (piston or capillary tube) cooling system, the refrigerant charge is normally checked by:

  • a.Discharge temperature against the ambient
  • b.Liquid subcooling against the nameplate
  • c.Suction superheat against a charging chart✓
  • d.Compressor amperage against the nameplate

A fixed restriction cannot adjust to load, so target superheat from indoor wet-bulb and outdoor dry-bulb temperatures is the charging method. Subcooling is the method for expansion valve systems.

Service

On a system with a thermostatic expansion valve, the refrigerant charge is normally checked by:

  • a.Suction line superheat
  • b.Sight glass moisture color
  • c.Liquid line subcooling✓
  • d.Suction line pressure only

The expansion valve holds superheat nearly constant regardless of charge, so superheat tells little. Subcooling shows how much liquid is backed up in the condenser and is compared to the manufacturer's target.

Service

A fixed-orifice system has high superheat and low subcooling with low suction and low head pressure. The most likely fault is:

  • a.A dirty condenser coil
  • b.An undercharge of refrigerant✓
  • c.A dirty evaporator coil
  • d.An overcharge of refrigerant

With too little refrigerant the evaporator starves (high superheat) and little liquid is stored in the condenser (low subcooling), with both pressures low. An overcharge gives the opposite: low superheat and high subcooling.

Service

A system shows low suction pressure, high superheat, and high subcooling. This pattern points to:

  • a.A condenser fan motor that has failed
  • b.A restriction in the liquid line or metering device✓
  • c.A compressor with leaking discharge valves
  • d.A low refrigerant charge from a slow leak at a flare fitting

A restriction starves the evaporator, so superheat is high, while refrigerant backs up in the condenser, so subcooling is high. A low charge also gives high superheat but with low subcooling, which is how the two are told apart.

Service

A noticeable temperature drop across a liquid line filter-drier indicates that the drier is:

  • a.Fully saturated with moisture and must be baked
  • b.Installed backward against the direction of flow
  • c.Partly plugged and acting as a metering device✓
  • d.Working normally and removing heat from the liquid

A pressure drop through a restricted drier causes some liquid to flash, and the outlet feels cooler than the inlet or even sweats. The drier should be replaced.

Service

Both suction pressure and head pressure are higher than normal, superheat is low, and subcooling is high. The likely cause is:

  • a.An overcharge of refrigerant✓
  • b.An undercharge of refrigerant
  • c.Low indoor airflow
  • d.A restricted metering device

Excess refrigerant backs up in the condenser, raising head pressure and subcooling, and overfeeds a fixed-orifice evaporator, lowering superheat. Low airflow and restrictions produce low suction pressure.

Service

Air and other noncondensables trapped in a system show up as:

  • a.Suction pressure lower than the evaporator temperature would predict
  • b.Superheat of zero with frost on the compressor shell
  • c.Head pressure higher than the condensing temperature would predict✓
  • d.Subcooling of zero with bubbles in the liquid line sight glass

Noncondensable gas collects in the condenser and adds its own pressure, so head pressure is above the saturation pressure for the measured condensing temperature. The remedy is to recover the charge, evacuate, and recharge.

Service

Suction pressure is high, head pressure is low, and compressor amperage is below normal. The compressor most likely has:

  • a.A start winding that is grounded to the shell
  • b.Leaking valves or worn internal parts✓
  • c.A low oil level in the crankcase
  • d.A locked rotor

A compressor that cannot pump shows suction and discharge pressures drifting toward each other and draws low current because it is doing little work. A locked rotor draws very high current and trips the overload.

Service

Resistance readings on a single-phase compressor are 2 ohms, 4 ohms and 6 ohms between its three terminals. The run winding is between the two terminals that read:

  • a.2 ohms✓
  • b.4 ohms
  • c.6 ohms
  • d.0 ohms

The lowest reading is common to run, the middle reading is common to start, and the highest reading is run to start, which equals the sum of the other two. The run winding has heavier wire and lower resistance.

Service

An ohmmeter reads continuity between a compressor terminal and the copper suction line. The compressor motor is:

  • a.Normal
  • b.Grounded✓
  • c.Open
  • d.Overloaded

Any measurable continuity from a winding terminal to the shell or piping means the winding insulation has failed to ground. A megohmmeter gives a more sensitive check of insulation condition.

Service

A compressor is hot to the touch and all three terminals show an open circuit to common. The first step is to:

  • a.Bypass the overload and restart the compressor
  • b.Replace the compressor without further testing
  • c.Let the compressor cool, then recheck the windings✓
  • d.Add refrigerant until the suction line sweats

An internal overload opens the common connection when the motor overheats, which looks like open windings. It resets when the shell cools, which may take an hour or more; then the cause of overheating is found.

Service

A run capacitor is rated 40 microfarads with a tolerance of plus or minus 6%. Which measured value is out of tolerance?

  • a.41.5 microfarads
  • b.42.0 microfarads
  • c.38.0 microfarads
  • d.36.0 microfarads✓

Six percent of 40 is 2.4, so the acceptable range is 37.6 to 42.4 microfarads. A reading of 36.0 is below the range and the capacitor should be replaced.

Service

Compared with a run capacitor, a start capacitor:

  • a.Has lower capacitance and stays in the circuit only briefly
  • b.Has lower capacitance and stays in the circuit continuously
  • c.Has higher capacitance and stays in the circuit continuously
  • d.Has higher capacitance and stays in the circuit only briefly✓

A start capacitor gives a large phase shift for starting torque and is removed within about a second by a relay. It is not built for continuous duty; a run capacitor is oil-filled, lower in microfarads, and stays in the circuit.

Service

A 240-volt electric heater draws 20 amps. Its resistance and power are:

  • a.12 ohms and 4,800 watts✓
  • b.12 ohms and 2,400 watts
  • c.0.08 ohms and 4,800 watts
  • d.4,800 ohms and 12 watts

Resistance is voltage divided by current, 240 divided by 20, or 12 ohms. Power is voltage times current, 240 times 20, or 4,800 watts.

Service

Before a system is charged, a deep vacuum is normally pulled to at least:

  • a.5,000 microns
  • b.29 inches of mercury on a compound gauge
  • c.0 psig on the low-side gauge
  • d.500 microns✓

A vacuum of 500 microns or lower, measured with an electronic micron gauge, shows that moisture and air have been removed. A compound gauge cannot resolve this level of vacuum.

Service

After reaching 500 microns, the vacuum pump is valved off and the micron gauge rises steadily without stopping. This indicates:

  • a.A failed micron gauge
  • b.A completed evacuation
  • c.Moisture in the system
  • d.A leak in the system✓

A reading that keeps rising toward atmospheric pressure means air is leaking in. If it rises and then levels off at a moderate value, moisture or refrigerant is still boiling off; if it holds, the system is tight and dry.

Service

During evacuation, the vacuum pump should be connected with:

  • a.Long, small-diameter hoses and valve cores in place
  • b.Short, large-diameter hoses and valve cores removed✓
  • c.The refrigerant cylinder open to the manifold
  • d.A single hose on the liquid line service port only

Flow at deep vacuum is very sensitive to restriction. Large, short hoses and removing Schrader cores cut evacuation time dramatically, and the micron gauge goes at the system, away from the pump.

Service

Under EPA Section 608 rules, a technician who opens a refrigerant circuit on stationary equipment must:

  • a.Be certified and recover the refrigerant with certified equipment✓
  • b.Be certified and dilute the refrigerant with dry nitrogen
  • c.Be supervised and store the refrigerant in the receiver only
  • d.Be registered and vent the refrigerant in a ventilated area

Knowingly venting refrigerant is prohibited. Technicians must hold Section 608 certification for the equipment type and use recovery equipment certified for it.40 CFR Part 82, Subpart F

Service

Refrigerant that has been removed from a system and stored in an external container without being tested or processed in any way is said to be:

  • a.Recovered✓
  • b.Recycled
  • c.Reclaimed
  • d.Restored

Recovery is removing refrigerant and storing it without testing or processing. Recycling cleans it for reuse with oil separation and filter-driers; reclaiming reprocesses it to new-product purity, verified by analysis.40 CFR 82.152

Service

Polyolester (POE) oil must be kept sealed until use because it:

  • a.Hardens when it is exposed to light
  • b.Evaporates at normal room temperature
  • c.Absorbs moisture from the air very readily✓
  • d.Separates into layers when it is shaken

POE oil is hygroscopic and moisture it absorbs is hard to remove by evacuation, leading to acid formation. Containers are opened only when needed and systems are not left open.

Service

Which leak detection method pinpoints a refrigerant leak without adding anything to the system?

  • a.A compressor amperage reading
  • b.A standing vacuum test on the system
  • c.An electronic leak detector at the joints✓
  • d.A liquid line sight glass inspection for bubbles

An electronic detector senses refrigerant escaping at a specific point. A standing vacuum test can show that a leak exists but not where, and vacuum can pull joints closed that leak under pressure.

Service

Evaporator coil icing on a cooling system is most often caused by:

  • a.A dirty condenser or a hot outdoor day
  • b.Low airflow or a low refrigerant charge✓
  • c.High airflow or a high refrigerant charge
  • d.A stuck-open expansion valve or overfeed

Low airflow starves the coil of heat, and low charge lowers evaporating pressure; either drops coil temperature below freezing. A dirty condenser raises pressures and does not cause icing.

Service

A gas furnace cycles off on its high limit. Which condition is the most likely cause?

  • a.A weak flame sensor signal
  • b.A dirty filter restricting airflow✓
  • c.A gas manifold pressure that is too low
  • d.A thermostat set too low

The limit opens when the heat exchanger overheats, which is nearly always low airflow: dirty filter, closed registers, dirty coil or wrong blower speed. A weak flame signal causes ignition lockout, not a limit trip.

Service

A heat pump in heating mode has a thick layer of ice over the whole outdoor coil. Which component is a likely cause?

  • a.A failed defrost control or sensor✓
  • b.A failed auxiliary heat sequencer
  • c.A failed indoor blower capacitor
  • d.A failed thermostat anticipator

Light frost is normal, but a solid ice block means defrost is not being started or completed: a bad defrost board, sensor, or reversing valve, or a low charge. Auxiliary heat and indoor components do not clear the outdoor coil.

Service

A condensing unit's contactor is pulled in and 240 volts is measured across the load terminals, but the compressor does not run or hum. The next check is:

  • a.The contactor coil and its control fuse
  • b.The thermostat and the low-voltage transformer
  • c.The compressor windings and internal overload✓
  • d.The indoor blower relay and its wiring

Voltage at the load side of a closed contactor proves the control circuit is working. With power present and no response, the open is in the compressor wiring, the internal overload, or the windings.

Service

Suction line temperature is 50°F and suction pressure converts to 45°F saturation. On a fixed-orifice system with a target superheat of 15°F, the technician should:

  • a.Recover refrigerant, because superheat is too high
  • b.Add refrigerant, because superheat is too high
  • c.Add refrigerant, because superheat is too low
  • d.Recover refrigerant, because superheat is too low✓

Measured superheat is 5°F against a 15°F target. Low superheat means the evaporator is overfed, so refrigerant is removed, after confirming that airflow is correct. Adding refrigerant would lower superheat further.

Service

A liquid line temperature of 95°F is measured when head pressure converts to 105°F saturation, and the manufacturer's target subcooling is 10°F. The charge is:

  • a.Unknown
  • b.Correct✓
  • c.Too high
  • d.Too low

Subcooling is 105 minus 95, or 10°F, which matches the target. Lower subcooling would call for adding refrigerant and higher subcooling for removing it.

Service

When a compressor has burned out, the system cleanup should include:

  • a.Reusing the old driers and adding fresh oil
  • b.Charging with extra refrigerant to dilute the acid left
  • c.Replacing the driers and testing the oil for acid✓
  • d.Flushing the system with compressed air

A burnout leaves acid and sludge in the system. Cleanup uses new liquid and suction line filter-driers, often replaced again after a period of running, with an acid test of the oil. Compressed air adds moisture and oxygen.

Testing

A furnace's nameplate gives a temperature rise range of 40°F to 70°F. Measured supply air is 135°F and return air is 70°F. The temperature rise is:

  • a.205°F, above the range
  • b.35°F, below the range
  • c.65°F, above the range
  • d.65°F, within the range✓

Temperature rise is supply minus return: 135 minus 70 is 65°F, inside the 40 to 70°F range. A rise above the range means low airflow or overfiring; below it means too much airflow or underfiring.

Testing

An electric furnace draws 20 kW and the temperature rise across it is 31.6°F. Using CFM = (kW × 3,413) ÷ (1.08 × ΔT), the airflow is about:

  • a.2,000 CFM✓
  • b.1,000 CFM
  • c.3,000 CFM
  • d.600 CFM

20 times 3,413 is 68,260 Btu/h; 1.08 times 31.6 is about 34.1; dividing gives about 2,000 CFM. The temperature rise method is a common field check of airflow.

Testing

Where should the supply air temperature be measured when using the temperature rise method on a gas furnace?

  • a.In the supply duct, out of sight of the heat exchanger✓
  • b.At the return grille, with the filter removed
  • c.At the farthest supply register in the building
  • d.In the supply plenum, directly above the heat exchanger

The probe must be shielded from radiant heat from the heat exchanger, which would give a falsely high reading, and close enough to the furnace that duct losses do not lower it.

Testing

A voltmeter is connected to a circuit:

  • a.With the power turned off
  • b.In parallel with the load✓
  • c.In series with the load
  • d.Around a single conductor

Voltage is measured across two points, so the meter leads go in parallel with the load or source. A clamp ammeter goes around a single conductor, and resistance is measured with power off.

Testing

A clamp-on ammeter is placed around both conductors of a 240-volt single-phase circuit at the same time. The reading will be:

  • a.About zero✓
  • b.The true current
  • c.Half the true current
  • d.Twice the true current

The currents in the two conductors are equal and opposite, so their magnetic fields cancel. The clamp must go around one conductor only.

Testing

Resistance and continuity measurements are made with:

  • a.Power applied and the load disconnected at one lead
  • b.Power applied and the load running
  • c.The meter set to the AC volts range
  • d.Power disconnected and the component isolated✓

An ohmmeter supplies its own small current. Applied power damages the meter and gives false readings, and parallel paths through other components must be removed by disconnecting at least one lead.

Testing

A voltmeter reads 24 volts across a set of control contacts that should be closed. The contacts are:

  • a.Open✓
  • b.Closed
  • c.Shorted
  • d.Grounded

A closed contact has almost no voltage across it. Reading full control voltage across a switch means the switch is open and the voltage is waiting there instead of at the load.

Testing

A megohmmeter is used to test:

  • a.Insulation resistance of motor windings to ground✓
  • b.Microamp signal of a flame sensor
  • c.Capacitance of run capacitors and of start capacitors
  • d.Voltage imbalance on three-phase power

A megohmmeter applies a high test voltage and reads insulation resistance in megohms, showing deterioration before a winding fails to ground. Flame signal is read with a microammeter in series with the sensor.

Testing

Typical manifold gas pressure for a natural gas furnace is about:

  • a.7 psig
  • b.0.5 inches w.c.
  • c.11 inches w.c.
  • d.3.5 inches w.c.✓

Natural gas furnaces usually run about 3.5 inches of water column at the manifold, and propane appliances about 10 to 11 inches. The nameplate value governs, and it is checked with a manometer at the gas valve outlet tap.

Testing

Typical manifold gas pressure for a propane (LP) furnace is about:

  • a.1 to 2 inches w.c.
  • b.20 to 25 inches w.c.
  • c.3 to 4 inches w.c.
  • d.10 to 11 inches w.c.✓

LP gas appliances commonly run 10 to 11 inches of water column at the manifold; natural gas runs about 3.5. Converting an appliance between fuels requires the manufacturer's orifice and regulator kit.

Testing

Which instrument measures gas manifold pressure?

  • a.A psychrometer
  • b.A megohmmeter
  • c.A manometer✓
  • d.A micron gauge

A U-tube or digital manometer reads low pressures in inches of water column. A micron gauge reads deep vacuum, and a psychrometer reads wet- and dry-bulb temperatures.

Testing

A combustion analyzer reads flue gas for oxygen or carbon dioxide, carbon monoxide, and stack temperature in order to determine:

  • a.Heat exchanger airflow and blower motor load
  • b.Combustion efficiency and safe burner operation✓
  • c.Refrigerant charge and compressor efficiency
  • d.Duct leakage and total external static pressure

Oxygen or carbon dioxide shows the amount of excess air, stack temperature shows how much heat is leaving, and carbon monoxide shows whether combustion is complete. Together they give efficiency and a safety check.

Testing

In a combustion test, a high oxygen reading in the flue gas with a low carbon dioxide reading indicates:

  • a.A cracked heat exchanger only
  • b.A large amount of excess air✓
  • c.A shortage of combustion air
  • d.A blocked vent or chimney

Oxygen that passes through unburned shows up in the flue gas and dilutes the carbon dioxide. Too much excess air carries heat up the vent and lowers efficiency; too little produces carbon monoxide.

Testing

Carbon monoxide in flue gas is a product of:

  • a.High gas heating value
  • b.Incomplete combustion✓
  • c.Excess draft
  • d.Complete combustion

Complete combustion of natural gas yields carbon dioxide and water vapor. Carbon monoxide forms when there is too little air, flame impingement, or poor mixing.

Testing

Draft in a natural-draft vent is measured with a draft gauge in:

  • a.Degrees Fahrenheit, as a temperature rise
  • b.Inches of water column, as a negative pressure✓
  • c.Pounds per square inch, as a positive pressure
  • d.Cubic feet per minute, as a volume flow

Draft is a very small negative pressure, typically a few hundredths of an inch of water column, that pulls flue gas up the vent.

Testing

A quick spillage test at the draft hood of a gas water heater or furnace is made by:

  • a.Holding a smoke source or match at the hood opening after a few minutes of firing✓
  • b.Reading the manifold pressure with the main burner switched off
  • c.Holding a thermometer in the burner compartment during each trial for ignition
  • d.Reading the gas meter dial while every other appliance is firing

After the appliance has run for several minutes, smoke at the draft hood relief opening should be drawn in. Smoke pushed out means flue gas is spilling, pointing to a blocked vent or a depressurized room.

Testing

Soap solution brushed on a gas piping joint is used to:

  • a.Measure the gas pressure at the joint
  • b.Locate leaks by the bubbles that form✓
  • c.Protect the joint from corrosion
  • d.Lubricate the threads for tightening

A noncorrosive leak detection fluid bubbles where gas escapes. An open flame must never be used to find leaks.IFGC §406.5

Testing

The firing rate of a gas appliance can be checked in the field by:

  • a.Clocking the gas meter with other appliances off✓
  • b.Reading the amperage of the inducer motor
  • c.Counting the number of burner ports alight
  • d.Measuring the flue pipe surface temperature at the collar

Timing one revolution of the meter's test dial gives cubic feet per hour, which is multiplied by the gas heating value to find Btu/h input and compared with the nameplate.

Testing

The 2 cubic foot test dial on a gas meter makes one revolution in 72 seconds with only the furnace firing. With gas at 1,000 Btu per cubic foot, the input is:

  • a.50,000 Btu/h
  • b.100,000 Btu/h✓
  • c.144,000 Btu/h
  • d.72,000 Btu/h

Cubic feet per hour equals 3,600 times the dial size divided by seconds: 3,600 times 2 divided by 72 is 100 cubic feet per hour, or 100,000 Btu/h.

Testing

Wet-bulb temperature is measured with:

  • a.A psychrometer✓
  • b.A pyrometer
  • c.A manometer
  • d.An anemometer

A sling or digital psychrometer reads dry-bulb and wet-bulb temperatures, from which relative humidity and enthalpy are found on the psychrometric chart. An anemometer reads air velocity.

Testing

Indoor wet-bulb temperature is needed when charging a fixed-orifice system because it:

  • a.Reflects the pressure drop across the filter
  • b.Sets the cut-in of the low-pressure switch
  • c.Reflects the total heat load on the evaporator✓
  • d.Sets the speed tap for the condenser fan

Wet-bulb temperature tracks the enthalpy of the air entering the coil. With outdoor dry-bulb temperature it gives the target superheat on the manufacturer's charging chart.

Testing

A standing pressure test of new refrigerant piping is made with dry nitrogen, and the pressure is recorded together with:

  • a.The compressor oil level, since nitrogen dissolves in the oil
  • b.The ambient temperature, since pressure changes with temperature✓
  • c.The line voltage, since the test is made with the power on
  • d.The barometric pressure, since nitrogen is lighter than air

Nitrogen pressure rises and falls with temperature, so a small change over a day may not be a leak. Recording temperature with pressure lets the two readings be compared fairly.