Texas Air Conditioning and Refrigeration Contractor Exam — All Questions
40 questions
A 4-ton residential cooling system is set up at the common nominal airflow of 400 CFM per ton. What total airflow should the blower deliver?
- a.1,600 CFM✓
- b.2,000 CFM
- c.1,400 CFM
- d.1,200 CFM
Four tons times 400 CFM per ton is 1,600 CFM. 1,200 CFM would be 300 CFM per ton and 1,400 CFM is 350 CFM per ton, both lower-airflow setups; 2,000 CFM is 500 CFM per ton.
A supply duct measures 12 inches by 12 inches and carries 1,000 CFM. What is the average air velocity in the duct?
- a.500 feet per minute
- b.144 feet per minute
- c.1,000 feet per minute✓
- d.1,200 feet per minute
Velocity equals airflow divided by area. A 12 by 12 inch duct has 1 square foot of area, so 1,000 CFM moves at 1,000 fpm. The 144 figure confuses square inches with velocity, and 500 and 1,200 fpm do not follow from the numbers given.
A rectangular duct is 24 inches by 12 inches and the measured average velocity is 700 feet per minute. What is the airflow?
- a.1,400 CFM✓
- b.700 CFM
- c.2,016 CFM
- d.1,050 CFM
The duct area is 24 times 12 divided by 144, or 2 square feet. Airflow is area times velocity: 2 times 700 is 1,400 CFM. 700 CFM forgets the area, and 2,016 uses square inches incorrectly.
A furnace delivers 64,800 Btu/h of sensible heat to the airstream and the temperature rise across it is 50°F. Using the standard-air sensible heat formula, about how much air is moving?
- a.1,200 CFM✓
- b.1,500 CFM
- c.1,000 CFM
- d.1,300 CFM
Sensible heat equals 1.08 times CFM times the temperature difference, so CFM is 64,800 divided by (1.08 times 50), which is 1,200. The other values come from dropping the 1.08 factor or misplacing the temperature rise.
In the sensible heat equation Q = 1.08 × CFM × ΔT, the factor 1.08 is valid for:
- a.Air leaving a cooling coil at 55°F dry bulb only
- b.Air at standard density, about 0.075 pounds per cubic foot✓
- c.Air at saturation, with relative humidity of 100%
- d.Air at any altitude or temperature, since the factor never changes
The 1.08 factor combines standard air density (0.075 lb per cubic foot), the specific heat of air (0.24), and 60 minutes per hour. At high altitude or very different temperatures the density changes and the factor must be corrected.
Total external static pressure for a furnace is found by:
- a.Adding the supply and return static pressures, ignoring signs✓
- b.Averaging the supply and the return static pressures
- c.Subtracting return static from the supply static pressure
- d.Reading the supply static pressure at the plenum alone
The blower works against the return (negative) and the supply (positive) resistance together, so the two readings are added as absolute values. Subtracting or averaging understates the load on the blower, and a supply-only reading leaves out the return side.
A technician measures +0.35 inches w.c. in the supply plenum and −0.25 inches w.c. in the return at the furnace. The total external static pressure is:
- a.0.60 inches w.c.✓
- b.0.10 inches w.c.
- c.0.35 inches w.c.
- d.0.30 inches w.c.
Add the absolute values: 0.35 plus 0.25 is 0.60 inches of water column. 0.10 is the result of subtracting, 0.30 is the average, and 0.35 is the supply side alone.
Total pressure in a duct equals:
- a.Static pressure times velocity pressure
- b.Static pressure minus velocity pressure
- c.Static pressure plus velocity pressure✓
- d.Velocity pressure divided by static pressure
Total pressure is the sum of static pressure, which pushes outward on the duct walls, and velocity pressure, which is the pressure of the moving air. A pitot tube reads total and static pressure, and the difference is velocity pressure.
A pitot tube traverse gives a velocity pressure of 0.25 inches w.c. in standard air. Using V = 4005 × √VP, the velocity is about:
- a.1,000 feet per minute
- b.4,000 feet per minute
- c.2,000 feet per minute✓
- d.500 feet per minute
The square root of 0.25 is 0.5, and 4005 times 0.5 is about 2,000 fpm. 1,000 fpm multiplies by 0.25 instead of its square root, and 4,000 fpm skips the square root altogether.
According to the fan laws, if blower speed is raised from 800 RPM to 880 RPM, a 10% increase, airflow will:
- a.Stay about the same
- b.Rise by about 33%
- c.Rise by about 21%
- d.Rise by about 10%✓
Airflow varies directly with fan speed, so a 10% speed increase gives about 10% more airflow. Static pressure rises with the square of speed (about 21%) and horsepower with the cube (about 33%), which is where the other figures come from.
A belt-drive blower's speed is doubled. By the fan laws, the brake horsepower required becomes about:
- a.Six times the original
- b.Eight times the original✓
- c.Four times the original
- d.Twice the original
Horsepower varies with the cube of the speed ratio: 2 cubed is 8. Four times is the change in static pressure (the square), and twice is the change in airflow.
In ACCA Manual D, the friction rate used to size a duct run is found from:
- a.Total effective length times 100, divided by available static pressure
- b.External static pressure, divided by the number of supply outlets
- c.Blower airflow in CFM, divided by the total effective length
- d.Available static pressure times 100, divided by total effective length✓
Manual D converts the pressure left for the ducts into a design friction rate per 100 feet: available static pressure times 100, divided by total effective length. Inverting the fraction gives a meaningless number, and airflow or outlet count is not part of this step.
A blower can deliver the design airflow at 0.50 inches w.c. external static pressure. The coil, filter, and grilles use 0.30 inches w.c. The total effective length of the longest circuit is 200 feet. The Manual D design friction rate is:
- a.0.04 inches w.c. per 100 feet
- b.0.25 inches w.c. per 100 feet
- c.0.15 inches w.c. per 100 feet
- d.0.10 inches w.c. per 100 feet✓
Available static pressure is 0.50 minus 0.30, or 0.20. Friction rate is 0.20 times 100 divided by 200, which is 0.10. The 0.25 answer forgets to subtract the component pressure drops.
In Manual D, the "total effective length" of a duct run is:
- a.Measured straight length of the supply trunk and every one of its branches
- b.Distance from the air handler to the farthest room outlet
- c.Measured straight length plus the equivalent length of all fittings✓
- d.Equivalent length of the fittings in the return side only
Total effective length adds the measured straight duct in the longest supply run and longest return run to the equivalent lengths of every fitting in them. Straight length alone ignores fittings, which usually account for most of the pressure loss.
Why does a duct fitting such as a sharp elbow get an "equivalent length" in duct design?
- a.Its air leakage is expressed as the length of unsealed duct with the same loss
- b.Its pressure loss is expressed as the length of straight duct with the same loss✓
- c.Its noise level is expressed as the length of lined duct needed to absorb it
- d.Its sheet metal area is expressed as the length of straight duct it replaces
Equivalent length states a fitting's pressure drop as feet of straight duct that would cause the same drop, so fittings and straight duct can be added together. It is not a measure of material, leakage, or noise.
Using a duct calculator at a friction rate of 0.10 inches w.c. per 100 feet, which round metal duct is the usual selection for 1,000 CFM?
- a.12-inch round
- b.10-inch round
- c.14-inch round✓
- d.18-inch round
At 0.10 inches per 100 feet, a duct calculator shows about 14 inches round for 1,000 CFM. A 10-inch duct carries roughly 400 CFM and a 12-inch about 650 CFM at that friction rate; an 18-inch is oversized. On the open-book exam, read this from the calculator rather than from memory.
Using a duct calculator at 0.10 inches w.c. per 100 feet, about how much air does a 6-inch round metal branch carry?
- a.About 200 CFM
- b.About 100 CFM✓
- c.About 50 CFM
- d.About 300 CFM
A 6-inch round duct at 0.10 inches per 100 feet carries roughly 100 CFM, which is why it is the common branch for a small bedroom. About 200 CFM calls for an 8-inch duct at the same friction rate.
Flexible duct is installed with long sags and is not pulled tight. Compared with the same duct fully extended, the airflow will be:
- a.Higher, because the longer air path lowers velocity
- b.Higher, because the inner liner becomes much smoother
- c.Unchanged, because the duct diameter stays the same
- d.Lower, because compression raises friction loss sharply✓
A compressed or sagging flexible duct has a corrugated inner surface and a longer path, both of which raise friction loss and cut airflow. Flexible duct should be cut to length, fully extended, and supported per the manufacturer's instructions.
Which return air location does the mechanical code prohibit for a residential forced-air system (IMC §601.5)?
- a.A living room
- b.A bathroom✓
- c.A dining room
- d.A hallway
Return air may not be taken from a bathroom, toilet room, kitchen, garage, closet, mechanical room, or boiler room, because odors, moisture, or combustion products would be spread through the building. Hallways and living areas are normal return locations.IMC §601.5
A furnace is installed in a closet that also holds a draft-hood gas water heater, and the return duct in the closet has a large gap at the filter rack. The main hazard is that the blower will:
- a.Pressurize the closet and push too much gas through the burner orifices
- b.Depressurize the closet and pull flue gases back down the draft hood✓
- c.Overheat the closet and cause the furnace high limit to open on each cycle
- d.Overcool the closet and cause the water heater thermostat to short cycle
A return leak in an appliance room puts the room under negative pressure, which can reverse the draft of a natural-draft appliance and spill carbon monoxide. This is why return air may not be drawn from a mechanical room and return ducts there must be sealed.IMC §601.5
Under IMC §606.2.1, a smoke detector is required in the return air of an air distribution system when its design capacity exceeds:
- a.5,000 CFM
- b.15,000 CFM
- c.2,000 CFM✓
- d.1,000 CFM
The trigger for a return air smoke detector is a design capacity greater than 2,000 CFM. The detector shuts the fan down so the system does not spread smoke. 15,000 CFM is the threshold in the separate rule for return air risers serving two or more stories.IMC §606.2.1
Exposed materials inside a plenum must generally have what maximum flame spread and smoke-developed indexes (IMC §602.2.1)?
- a.Flame spread 200 and smoke-developed 450
- b.Flame spread 25 and smoke-developed 50✓
- c.Flame spread 75 and smoke-developed 450
- d.Flame spread 50 and smoke-developed 25
Materials exposed in plenums are limited to a flame spread index of not more than 25 and a smoke-developed index of not more than 50. The other pairs reverse the numbers or use limits that apply to ordinary interior finishes.IMC §602.2.1
What is the purpose of a fire damper where a duct passes through a fire-resistance-rated wall?
- a.It closes on heat to keep fire from passing through the duct opening✓
- b.It opens on heat to relieve the pressure built up inside the duct
- c.It closes on a call for cooling to isolate zones that are satisfied
- d.It modulates to balance airflow between the two sides of the wall
A fire damper has a fusible link or similar device that closes the damper when heated, restoring the wall's fire rating at the duct opening. Balancing and zone dampers have different jobs and are not rated for this use.IMC §607
Pressure-sensitive tape used to seal joints in flexible air ducts and connectors must be:
- a.Standard cloth-backed tape with a rubber adhesive
- b.Any foil tape at least two inches in overall width
- c.Listed and labeled to UL 181B and marked accordingly✓
- d.Electrical vinyl tape rated for 600-volt service
The mechanical code requires tapes and mastics used on flexible ducts to be listed to UL 181B and marked (181B-FX for tape, 181B-M for mastic). Ordinary cloth duct tape is not listed for this use and fails with heat and age.IMC §603.9
A filter's MERV rating describes its:
- a.Resistance to airflow when it is clean
- b.Ability to capture particles of stated sizes✓
- c.Expected service life in a normal home
- d.Maximum allowed face velocity in service
MERV (minimum efficiency reporting value) rates how well a filter captures particles in set size ranges; a higher number captures smaller particles. Pressure drop, face velocity limits and service life are separate data from the manufacturer.
A customer replaces a 1-inch fiberglass filter with a 1-inch high-MERV pleated filter in the same rack. With no other change, the most likely effect is:
- a.Lower pressure drop and higher system airflow
- b.No change in pressure drop or in airflow
- c.Higher pressure drop and lower system airflow✓
- d.Higher airflow and a lower temperature rise
A denser filter of the same size normally has more resistance, so static pressure rises and airflow falls, which can raise furnace temperature rise or cause coil icing. More filter area, such as a deeper media cabinet, is the way to add efficiency without that penalty.
A return air filter grille must handle 1,200 CFM at a face velocity of no more than 300 feet per minute. What is the minimum gross face area?
- a.2.5 square feet
- b.4 square feet✓
- c.6 square feet
- d.3 square feet
Area equals airflow divided by velocity: 1,200 divided by 300 is 4 square feet, for example a 24 by 24 inch grille. A smaller grille raises velocity, noise and pressure drop.
In register selection, "throw" is the:
- a.Distance the airstream falls below the outlet at the end of its travel
- b.Volume of room air pulled into the airstream as it leaves the outlet
- c.Distance the airstream travels before slowing to a stated terminal velocity✓
- d.Width the airstream reaches as it fans out from the face of the outlet
Throw is the horizontal or vertical distance air travels from the outlet until its velocity drops to a stated terminal value, often 50 fpm. Drop is how far it falls, spread is how wide it fans out, and induction or entrainment is the room air it pulls along.
For heating in a cold climate, perimeter floor supply outlets are placed under windows mainly to:
- a.Reduce the amount of return air that is needed
- b.Shorten the branch duct runs from the trunk
- c.Keep supply air away from the room thermostat
- d.Blanket the cold glass and offset downdrafts✓
Warm air rising from a perimeter outlet washes the coldest surface, offsetting the downdraft from glass and exterior walls. The location usually lengthens branch runs rather than shortening them, and it does not change return air requirements.
What is the purpose of turning vanes in a square duct elbow?
- a.To filter large particles out of the moving airstream
- b.To cut turbulence and pressure loss through the elbow✓
- c.To raise the velocity of the air leaving the elbow
- d.To stop sound from travelling along the duct wall
Turning vanes guide the air around a mitered elbow so it does not pile up against the outside wall, which greatly reduces the fitting's pressure loss. They are not filters or sound attenuators.
A manual volume damper in a branch duct is used to:
- a.Balance airflow to the outlet served by that branch✓
- b.Stop fire from spreading through the branch duct
- c.Shut the branch whenever the thermostat is satisfied
- d.Prevent backdraft when the blower is switched off
A manual balancing damper is set once to proportion air among branches. Fire dampers, backdraft dampers and motorized zone dampers are different devices with different functions.
A duct system is designed to the same friction rate throughout so that pressure loss per foot is constant. This is called the:
- a.Velocity reduction method
- b.Constant volume method
- c.Equal friction method✓
- d.Static regain method
The equal friction method sizes every section for the same pressure loss per 100 feet and is the usual residential and light commercial approach. Static regain sizes sections so that falling velocity recovers static pressure, and velocity reduction assigns velocities to each section.
Two round ducts are compared for the same airflow. If the diameter is cut in half, the velocity in the smaller duct is:
- a.Half as high
- b.Four times as high✓
- c.Twice as high
- d.Eight times as high
Area varies with the square of the diameter, so half the diameter is one quarter of the area, and the same airflow must move four times as fast. Friction loss rises far more steeply, which is why undersized ducts are so restrictive.
A system mixes 300 CFM of outdoor air at 95°F with 900 CFM of return air at 75°F. What is the mixed air dry-bulb temperature entering the coil?
- a.78°F
- b.85°F
- c.90°F
- d.80°F✓
Weight each stream by its airflow: (300 times 95 plus 900 times 75) divided by 1,200 is 80°F. 85°F is the simple average of the two temperatures, which ignores that three quarters of the air is return air.
Supply ducts in a vented attic are insulated and wrapped with a vapor retarder mainly to:
- a.Protect the duct from rodents and physical damage
- b.Add stiffness and prevent sagging between hangers
- c.Limit heat gain and stop condensation on the duct✓
- d.Limit air noise and stop vibration in the duct
Cold supply air in a hot, humid attic gains heat and can drop the duct surface below the attic air's dew point. Insulation cuts the heat gain and the outer vapor retarder keeps moist air from reaching the cold surface.
A high-velocity return grille whistles and the blower is starved for air. Which correction addresses the cause?
- a.Raise the blower speed to pull the air through faster
- b.Close several supply registers to reduce the airflow
- c.Add return grille and duct area to lower the velocity✓
- d.Add a denser filter to quiet the air at the grille
Noise and starvation at a return mean too little free area for the airflow, so the fix is more return area. A denser filter and closed registers add restriction, and a higher blower speed raises velocity and noise further.
When measuring airflow at a supply register with a flow capture hood, the reading is taken in:
- a.Pounds per square inch
- b.Cubic feet per minute✓
- c.Inches of water column
- d.Feet per minute
A capture hood channels all the air from the outlet across a sensing grid and reads volume flow directly in CFM. An anemometer reads velocity in fpm, and a manometer reads pressure in inches of water column.
A flexible vibration connector between the air handler and the metal supply plenum is installed to:
- a.Keep equipment vibration from passing into the duct system✓
- b.Keep the plenum from expanding when the heat is running
- c.Keep return air from bypassing the filter at the cabinet
- d.Keep conditioned air from leaking out at the plenum collar
The fabric connector breaks the metal-to-metal path so blower vibration and noise are not carried through the ductwork. It is not a seal, an expansion joint, or a filter bypass control.
A duct's aspect ratio is the ratio of its:
- a.Airflow to its friction loss
- b.Area to its air velocity
- c.Length to its perimeter
- d.Long side to its short side✓
Aspect ratio is width divided by height for a rectangular duct. As it rises, the duct has more surface for the same area, so friction and cost go up; designers try to keep it low, with a square duct at 1 to 1.
A cooling system has a measured airflow well below design. Which symptom is consistent with low airflow across the evaporator?
- a.High suction pressure with a warm coil that sweats
- b.High head pressure with a normal suction pressure
- c.Low suction pressure with a cold coil that may frost✓
- d.Normal pressures with a high supply air temperature
With too little air the coil cannot pick up enough heat, so evaporating pressure and temperature fall and the coil may ice. The temperature drop across the coil is larger than normal, not smaller.