Texas Air Conditioning and Refrigeration Contractor Exam — All Questions
8 questions
The purpose of mechanical ventilation in an occupied building is to:
- a.Lower the relative humidity of the supply air
- b.Bring in outdoor air to dilute indoor contaminants✓
- c.Recirculate indoor air to even out temperatures
- d.Raise the static pressure in the return duct
Ventilation replaces a portion of indoor air with outdoor air to control odors, carbon dioxide and other contaminants. Recirculation alone does not ventilate.IMC Chapter 4
Under IMC §401.4, a mechanical outdoor air intake must be located at least how far from a hazardous or noxious contaminant source such as a plumbing vent or a chimney?
- a.25 feet horizontally
- b.3 feet horizontally
- c.5 feet horizontally
- d.10 feet horizontally✓
Intake openings are kept at least 10 feet from contaminant sources such as vents, chimneys, streets and loading docks, with listed exceptions. The separation keeps exhaust from being drawn back into the building.IMC §401.4
An energy recovery ventilator (ERV) differs from a heat recovery ventilator (HRV) in that an ERV transfers:
- a.Refrigerant between two separate coils
- b.Heat only between the two airstreams
- c.Moisture only between the two airstreams, with no heat
- d.Both heat and moisture between the airstreams✓
An ERV core exchanges sensible heat and water vapor between exhaust and incoming air, reducing the latent load of ventilation in a humid climate. An HRV exchanges sensible heat only.
A refrigeration machinery room is required to have a refrigerant detector that:
- a.Sounds an alarm and starts the mechanical ventilation✓
- b.Opens the relief valves on the pressure vessels
- c.Shuts the room lights off and locks the access door
- d.Starts the compressors to pump the system down
The detector, located where leaked refrigerant will concentrate, triggers audible and visual alarms and the ventilation system when its set concentration is reached.IMC §1105
Doors of a refrigeration machinery room are required to be:
- a.Removable, with an inside key lock
- b.Sliding, with a fusible-link closer
- c.Louvered, held open during operation, and opening inward
- d.Tight-fitting, self-closing, and opening outward✓
Machinery room doors are tight-fitting and self-closing so leaked refrigerant stays in the room, and they swing outward for escape. Openings that would let refrigerant pass to other parts of the building are not allowed.International Mechanical Code, refrigeration machinery room requirements
Machinery room exhaust ventilation must discharge:
- a.Into an adjoining corridor or stairway
- b.Outdoors, away from air intakes and openings✓
- c.Into the attic space above the room
- d.Into the return air plenum of the building it serves
Refrigerant-laden air is discharged to the outdoors where it will not cause a nuisance or re-enter the building. Sending it into plenums, corridors or attics spreads the hazard.IMC §1105
A commercial kitchen hood over a fryer that produces grease-laden vapor must be a:
- a.Type II hood
- b.Residential range hood
- c.Type I hood✓
- d.Recirculating fan
Type I hoods are for grease and smoke and have grease filters and a liquid-tight exhaust duct. Type II hoods handle only heat, steam and odors, as over a dishwasher.IMC §507
When a large exhaust fan is added to a tight building without makeup air, the likely result is:
- a.Lower humidity because less outdoor air leaks inward
- b.Negative pressure that can backdraft fuel-burning appliances✓
- c.Higher airflow through the exhaust fan than its rating
- d.Positive pressure that pushes conditioned air out of the doors
Exhaust without makeup air depressurizes the building, pulling air down vents and chimneys and reducing the fan's own airflow. The code requires makeup air roughly equal to the exhaust.IMC §501