Texas Air Conditioning and Refrigeration Contractor Exam — All Questions
14 questions
Under the standard method in IFGC §304.5.1, an indoor space supplies enough combustion air without added openings when it has at least how much volume?
- a.50 cubic feet per 10,000 Btu/h of total appliance input
- b.50 cubic feet per 1,000 Btu/h of total appliance input✓
- c.100 cubic feet per 1,000 Btu/h of total appliance input
- d.25 cubic feet per 1,000 Btu/h of total appliance input
The standard method requires 50 cubic feet of room volume for each 1,000 Btu/h of input for all appliances in the space. Less volume means air must be brought from adjoining spaces or outdoors.IFGC §304.5.1
A mechanical room holds a 100,000 Btu/h furnace and a 40,000 Btu/h water heater, both drawing combustion air from the room. By the IFGC standard method, the minimum room volume with no added openings is:
- a.7,000 cubic feet✓
- b.2,800 cubic feet
- c.14,000 cubic feet
- d.5,000 cubic feet
Total input is 140,000 Btu/h; at 50 cubic feet per 1,000 Btu/h that is 7,000 cubic feet. 5,000 counts only the furnace, and 14,000 doubles the factor.IFGC §304.5.1
An appliance closet is joined to the rest of the house by two permanent openings to supply combustion air from indoors. Under IFGC §304.5.3.1, each opening must have a free area of at least:
- a.1 square inch per 2,000 Btu/h, and not less than 50 square inches
- b.1 square inch per 1,000 Btu/h, and not less than 100 square inches✓
- c.1 square inch per 3,000 Btu/h, and not less than 200 square inches
- d.1 square inch per 4,000 Btu/h, and not less than 100 square inches
When spaces on the same story are combined, each of the two openings needs 1 square inch per 1,000 Btu/h of total input with a 100-square-inch minimum. The 4,000, 2,000 and 3,000 figures belong to the outdoor air methods.IFGC §304.5.3.1
Two combustion air openings communicate directly with the outdoors, one high and one low. Under IFGC §304.6.1, each must provide at least:
- a.1 square inch of free area per 2,000 Btu/h
- b.1 square inch of free area per 4,000 Btu/h✓
- c.1 square inch of free area per 1,000 Btu/h
- d.1 square inch of free area per 5,000 Btu/h
Direct openings or vertical ducts to outdoors require 1 square inch per 4,000 Btu/h for each of the two openings. The 2,000 figure applies when the air comes through horizontal ducts, and 1,000 applies to indoor openings.IFGC §304.6.1
Combustion air is brought to an appliance room through two horizontal ducts from outdoors. Under IFGC §304.6.1, each duct must provide free area of at least:
- a.1 square inch per 4,000 Btu/h
- b.1 square inch per 3,000 Btu/h
- c.1 square inch per 2,000 Btu/h✓
- d.1 square inch per 1,000 Btu/h
Horizontal ducts have more resistance than vertical ducts or direct openings, so the requirement doubles to 1 square inch per 2,000 Btu/h. The 3,000 figure is used for the single-opening method.IFGC §304.6.1
A furnace and water heater totaling 120,000 Btu/h get combustion air through two vertical ducts from a ventilated attic. Using IFGC §304.6.1, the minimum free area of each duct is:
- a.60 square inches
- b.120 square inches
- c.40 square inches
- d.30 square inches✓
Vertical ducts use 1 square inch per 4,000 Btu/h: 120,000 divided by 4,000 is 30 square inches each. Sixty square inches would be the horizontal-duct answer and 40 the one-opening answer.IFGC §304.6.1
Under the one-permanent-opening method in IFGC §304.6.2, the single opening to outdoors is sized at:
- a.1 square inch per 1,000 Btu/h, located within 18 inches of the top of the space
- b.1 square inch per 3,000 Btu/h, located within 12 inches of the bottom of the space
- c.1 square inch per 4,000 Btu/h, located at the midpoint of the appliance room wall
- d.1 square inch per 3,000 Btu/h, located within 12 inches of the top of the space✓
The single-opening method uses 1 square inch per 3,000 Btu/h, placed within 12 inches of the top of the enclosure, and not smaller than the combined area of the vent connectors. The low location and the other ratios do not match this method.IFGC §304.6.2
Where the upper and lower combustion air openings are used, the IFGC places them:
- a.Within 24 inches of the top and within 24 inches of the bottom
- b.Within 12 inches of the top and within 12 inches of the bottom✓
- c.Within 6 inches of the top and at the level of the burner
- d.At any height, provided they are on opposite walls
One opening starts within 12 inches of the top of the enclosure and the other within 12 inches of the bottom, which sets up a natural circulation of air through the space.IFGC §304.5.3.1, §304.6.1
A combustion air opening is covered by a metal louver and the manufacturer's free area is not known. IFGC §304.10 allows you to assume the free area is:
- a.50% of the gross louver area
- b.25% of the gross louver area
- c.75% of the gross louver area✓
- d.90% of the gross louver area
Without manufacturer data, metal louvers and grilles are taken as 75% free area and wood louvers as 25%. The opening must be enlarged so that the net free area meets the requirement.IFGC §304.10
An opening needs 100 square inches of free area and will be covered with a wood louver of unknown free area. Using the IFGC default for wood louvers, the gross opening must be at least:
- a.200 square inches
- b.133 square inches
- c.400 square inches✓
- d.125 square inches
Wood louvers are assumed to be 25% free area, so 100 divided by 0.25 is 400 square inches. 133 square inches would be right for a metal louver at 75%.IFGC §304.10
A direct-vent gas furnace takes its combustion air:
- a.Directly from outdoors through a sealed intake pipe✓
- b.From the equipment room through louvered doors
- c.From the return air duct just ahead of the main blower
- d.From the attic through an open vertical duct
A direct-vent appliance has a sealed combustion system: all combustion air comes from outdoors and all flue gas goes outdoors, so it does not rely on room air. Combustion air is never taken from the return duct.
Why may combustion air not be taken from a room where an exhaust fan or return leak creates negative pressure?
- a.Flame temperature can rise and overheat the primary heat exchanger
- b.Vent connector joints can loosen under the higher draft that results
- c.Gas pressure at the burner can rise above the rated manifold value
- d.Flue gases can be drawn back into the room instead of venting✓
Negative pressure in the appliance space can overcome natural draft and cause spillage or backdrafting, bringing carbon monoxide indoors. The code requires makeup air for exhaust systems so appliance operation is not affected.IFGC §304.4
Incomplete combustion from a shortage of air is indicated at a gas burner by:
- a.Lazy yellow flames, soot, and carbon monoxide✓
- b.Short blue flames lifting off the burner ports
- c.Sharp blue flames with a clear inner cone
- d.Flames that light quietly and burn steadily
Too little primary or secondary air gives soft, yellow-tipped flames, soot, and carbon monoxide. Flames lifting off the ports point to too much primary air or pressure, and a stable blue flame with a defined inner cone is normal.
Screens on outdoor combustion air openings must have mesh openings no smaller than:
- a.1/4 inch✓
- b.1/16 inch
- c.1/8 inch
- d.1/2 inch
The mesh may not be smaller than 1/4 inch so that it does not clog easily with lint and debris and choke off the air supply.IFGC §304.10