Texas Air Conditioning and Refrigeration Contractor Exam — All Questions
28 questions
A wall has an R-value of 20. Its U-factor is:
- a.20.0 Btu/h per square foot per °F
- b.0.05 Btu/h per square foot per °F✓
- c.0.50 Btu/h per square foot per °F
- d.0.20 Btu/h per square foot per °F
U is the reciprocal of R: 1 divided by 20 is 0.05. A higher R-value means a lower U-factor and less heat flow.
A 200-square-foot wall has a U-factor of 0.05 and the design temperature difference is 60°F. The conduction heat loss is:
- a.6,000 Btu/h
- b.600 Btu/h✓
- c.240 Btu/h
- d.1,200 Btu/h
Heat flow equals U times area times temperature difference: 0.05 times 200 times 60 is 600 Btu/h. This is the basic envelope calculation behind a Manual J load.
Which ACCA manual is used to calculate the heating and cooling loads of a residence?
- a.Manual D
- b.Manual S
- c.Manual T
- d.Manual J✓
Manual J is residential load calculation, Manual S is equipment selection, Manual D is duct design, and Manual T covers air distribution outlets. PSI allows Manuals J, S and D at the Environmental Air exams.
Which ACCA manual is used to select equipment whose capacity matches the calculated loads?
- a.Manual N
- b.Manual D
- c.Manual J
- d.Manual S✓
Manual S takes the Manual J loads and the manufacturer's expanded performance data at design conditions to select equipment within sizing limits. Manual N is the commercial load manual.
A cooling load calculation shows 24,000 Btu/h sensible and 6,000 Btu/h latent. The sensible heat ratio of the load is:
- a.0.75
- b.1.25
- c.0.25
- d.0.80✓
Sensible heat ratio is sensible load divided by total load: 24,000 divided by 30,000 is 0.80. Dividing latent by sensible gives 0.25, which is not the ratio asked for.
Selected equipment must have enough latent capacity at design conditions. If the sensible heat ratio of the equipment is much higher than that of the load, the space will tend to be:
- a.Comfortable in all weather
- b.Dry enough but too warm
- c.Cool enough but too humid✓
- d.Too cold and too dry
A high equipment sensible heat ratio means little moisture removal. The thermostat is satisfied on temperature while humidity stays high, a common result of oversizing or excessive airflow.
Why does Manual S warn against substantially oversized cooling equipment?
- a.High airflow gives lower suction pressure and icing
- b.Long cycles give poor humidity removal and less wear
- c.Low airflow gives higher head pressure and less noise
- d.Short cycles give poor humidity removal and more wear✓
Oversized equipment satisfies the thermostat quickly, so the coil does not run long enough to remove moisture, and frequent starts add wear and noise. Sizing limits in Manual S keep capacity close to the calculated load.
A furnace has an input rating of 100,000 Btu/h and an efficiency of 80%. Its output is:
- a.100,000 Btu/h
- b.125,000 Btu/h
- c.80,000 Btu/h✓
- d.20,000 Btu/h
Output is input times efficiency: 100,000 times 0.80 is 80,000 Btu/h. The 20,000 Btu/h figure is the heat lost up the vent, and 125,000 divides instead of multiplying.
A 15 kW electric heat strip produces about how much heat?
- a.34,100 Btu/h
- b.51,200 Btu/h✓
- c.15,000 Btu/h
- d.180,000 Btu/h
One kilowatt is 3,413 Btu/h, so 15 kW is about 51,200 Btu/h. 34,100 Btu/h is the output of a 10 kW heater.
A unit nameplate lists a minimum circuit ampacity (MCA) of 23 amps and a maximum overcurrent protection (MOCP) of 40 amps. These two values are used to:
- a.Size the branch conductors from MCA and limit the breaker to MOCP✓
- b.Size the branch conductors from MOCP and limit the breaker to MCA
- c.Size the breaker from the running load amps and ignore both values
- d.Size the disconnect from MCA and the thermostat wire from MOCP
Conductors must have an ampacity of at least the MCA, and the fuse or breaker may not be larger than the MOCP. Reversing them undersizes the protection or oversizes the wire for no purpose.
A motor is rated 230 volts. Using the usual plus or minus 10% tolerance, the acceptable supply voltage range is:
- a.220 to 240 volts
- b.207 to 253 volts✓
- c.197 to 263 volts
- d.208 to 230 volts
Ten percent of 230 is 23 volts, giving 207 to 253. Equipment marked 208/230 has a wider stated range from the manufacturer, so the nameplate governs.
Three-phase voltages measure 220, 230 and 225 volts. Using percent imbalance = maximum deviation from average ÷ average × 100, the imbalance is about:
- a.10%
- b.4.4%
- c.2.2%✓
- d.1.0%
The average is 225 volts and the greatest deviation is 5 volts; 5 divided by 225 is about 2.2%. Manufacturers commonly limit voltage imbalance to 2%, because a small voltage imbalance produces a much larger current imbalance and winding heat.
The balance point of a heat pump is the outdoor temperature at which:
- a.Heat pump capacity equals the heat loss of the building✓
- b.Heat pump capacity equals the cooling load of the building
- c.The outdoor coil begins to frost and call for defrost
- d.The compressor is locked out and electric heat takes over
Above the balance point the heat pump alone carries the load; below it, supplemental heat is needed. It is found by plotting the building's heat loss line against the heat pump's capacity curve.
A heat pump delivers 36,000 Btu/h of heat while drawing 3.5 kW. Its coefficient of performance is about:
- a.10.3
- b.1.0
- c.3.5
- d.3.0✓
COP is heat output divided by energy input in the same units: 3.5 kW is about 11,950 Btu/h, and 36,000 divided by 11,950 is about 3.0. 10.3 is Btu/h per watt, which is an EER-style figure, not COP.
An air conditioner's EER is its:
- a.Cooling output in Btu/h divided by power input in watts✓
- b.Seasonal heating output divided by seasonal energy input
- c.Cooling output in tons divided by power input in kilowatts
- d.Power input in watts divided by cooling output in Btu/h
EER is Btu/h of cooling per watt at a single rating condition. SEER is the seasonal version, and HSPF is the heating seasonal measure for heat pumps.
Under IMC §306.1, the level working space in front of the control side of an appliance must be at least:
- a.36 inches deep and 30 inches wide
- b.30 inches deep and 22 inches wide
- c.30 inches deep and 30 inches wide✓
- d.24 inches deep and 24 inches wide
The code calls for a level working space not less than 30 inches by 30 inches in front of the control or service side. The appliance must also be removable without taking out permanent construction.IMC §306.1
An appliance is installed in an attic. Under IMC §306.3, the passageway to it may be no longer than:
- a.20 feet, measured along its centerline✓
- b.30 feet, measured from the appliance
- c.50 feet, measured along its centerline
- d.10 feet, measured from the appliance
The attic passageway is limited to 20 feet from the opening to the appliance, with solid flooring at least 24 inches wide and a clear opening large enough to remove the largest appliance. The code lists exceptions for taller, wider passageways.IMC §306.3
A gas furnace with an open ignition source is installed in a residential garage. Under IMC §304.3, the source of ignition must be elevated above the floor at least:
- a.24 inches
- b.6 inches
- c.18 inches✓
- d.12 inches
Ignition sources in garages are raised at least 18 inches so they sit above the layer where gasoline vapors collect. Appliances listed as flammable vapor ignition resistant are excepted.IMC §304.3
Rooftop equipment needing service is located 6 feet from the roof edge, and the roof is more than 30 inches above grade. Under IMC §304.11, what is required?
- a.A guard at least 42 inches high along the roof edge✓
- b.A permanent ladder fixed to the side of the equipment
- c.A warning line painted 24 inches from the roof edge
- d.A walkway pad between the roof hatch and the unit
Guards are required where equipment or components needing service are within 10 feet of a roof edge or open side more than 30 inches above the level below. The guard must be at least 42 inches high.IMC §304.11
An evaporator coil is installed above a finished ceiling where condensate overflow would damage the building. IMC §307.2.3 requires:
- a.A second cooling coil piped in series with the primary coil
- b.A larger primary drain line, at least one size above the minimum
- c.A condensate pump wired to run whenever the blower operates
- d.An auxiliary protection method, such as a secondary pan or drain✓
Where damage could result from a stopped primary drain, the code requires one of several secondary protections: an auxiliary pan with a separate drain, a separate overflow drain, or a water-level detection device that shuts the equipment off.IMC §307.2.3
An auxiliary drain pan installed under a coil per IMC §307.2.3 must be:
- a.At least 2 inches deep and 6 inches larger than the unit on each side
- b.At least 1.5 inches deep and 3 inches larger than the unit on each side✓
- c.At least 1 inch deep and the same size as the base of the unit
- d.At least 3 inches deep and 1.5 inches larger than the unit on each side
The pan depth is at least 1.5 inches, and it extends at least 3 inches beyond the unit or coil dimensions in width and length. The discharge from the pan's drain must be at a point where the occupants will notice it.IMC §307.2.3.1
When a duct system is designed with Manual D, the blower data used to set available static pressure comes from:
- a.The Manual J worksheet for the room with the largest heat gain
- b.The nameplate horsepower and full-load amperage of the blower motor
- c.The manufacturer's blower performance table for the selected unit✓
- d.The friction chart printed on the back of the duct calculator
The blower table shows how much external static pressure the fan can produce at the design airflow. Subtracting the pressure drops of coil, filter and other components gives the pressure available for the ducts.
In a Manual J calculation, outdoor design temperatures are taken from:
- a.The highest temperature ever recorded there
- b.The average annual temperature of the area
- c.Published design conditions for the location✓
- d.The owner's preferred thermostat settings
Manual J uses tabulated outdoor design conditions (for example the 1% cooling and 99% heating values) for the location. Designing for record extremes oversizes the equipment.
Infiltration adds to the cooling load of a house as:
- a.Radiant heat from the roof and nothing else
- b.Latent heat only
- c.Both sensible and latent heat✓
- d.Sensible heat only
Outdoor air leaking in is both warmer and more humid than indoor air in a Texas summer, so it brings sensible and latent load. Duct leakage on the return side in an attic has a similar effect.
Which internal load adds latent heat to a space?
- a.People✓
- b.Lighting
- c.Computers
- d.Motors
People give off both sensible heat and moisture. Lights, electronics and motors add sensible heat only, since they release no water vapor.
Natural gas is assumed to have a heating value of about 1,000 Btu per cubic foot. A furnace burns 1.5 cubic feet per minute. Its input is about:
- a.150,000 Btu/h
- b.15,000 Btu/h
- c.90,000 Btu/h✓
- d.60,000 Btu/h
1.5 cubic feet per minute is 90 cubic feet per hour, and 90 times 1,000 is 90,000 Btu/h. Clocking the meter this way checks the firing rate against the nameplate.
A condensing unit's nameplate states "Minimum circuit ampacity 18.5 A." The smallest acceptable branch conductor is one with an ampacity of at least:
- a.18.5 amps✓
- b.23.1 amps
- c.37.0 amps
- d.14.8 amps
MCA already includes the 125% factor on the largest motor, so the conductor only has to carry the MCA. Multiplying by 1.25 again or by 2 oversizes the wire, and 80% undersizes it.
Latent capacity of cooling equipment generally rises when the blower airflow per ton is:
- a.Raised, giving a warmer coil
- b.Held, with a larger filter
- c.Reduced, giving a colder coil✓
- d.Raised, giving a colder coil
Lower airflow per ton lowers coil temperature and raises moisture removal, at some cost in sensible capacity. Humid climates often use about 350 CFM per ton for this reason; too little airflow risks icing.