Texas Air Conditioning and Refrigeration Contractor Exam — All Questions

20 questions

Controls

In a standard 24-volt thermostat circuit, which terminal energizes the cooling contactor?

  • a.W
  • b.Y✓
  • c.C
  • d.G

Y is the cooling call that energizes the contactor coil. W is heat, G is the indoor fan, and C is the common side of the transformer; R is the 24-volt supply.

Controls

A thermostat's G terminal is energized. Which component should run?

  • a.The compressor
  • b.The gas valve
  • c.The reversing valve
  • d.The indoor blower✓

G brings on the indoor fan relay or the blower through the control board. The compressor answers to Y, the heat to W, and the reversing valve to O or B.

Controls

A low-pressure switch on an air conditioning system opens to protect the compressor when:

  • a.Oil pressure falls too low, as with a failed oil pump
  • b.Discharge pressure rises too high, as with a dirty coil
  • c.Suction pressure falls too low, as with loss of charge✓
  • d.Suction pressure rises too high, as with overcharge

The low-pressure control opens the control circuit when suction pressure drops, which happens with a refrigerant leak, a restriction, or a frozen coil. High discharge pressure is the high-pressure switch's job, and oil failure is handled by an oil safety control.

Controls

A high-pressure cutout that must be reset by hand after it trips is used so that:

  • a.Someone finds and corrects the cause before a restart✓
  • b.The thermostat is bypassed during the high load
  • c.The compressor restarts as soon as the pressure falls
  • d.The condenser fan cycles to control head pressure

A manual-reset safety forces a person to investigate, for example a failed condenser fan or blocked coil, before the system runs again. An automatic-reset control would let the compressor cycle repeatedly on a dangerous condition.

Controls

On a gas furnace, the high-limit switch opens when:

  • a.Air temperature at the room thermostat rises too high
  • b.Flue draft falls below the setting of the inducer switch
  • c.Gas pressure in the manifold rises above the setting
  • d.Air temperature in the heat exchanger area rises too high✓

The limit senses overheating at the heat exchanger, usually from low airflow such as a dirty filter or failed blower, and shuts the burners off. Draft is proved by the pressure switch, and the room thermostat is an operating control, not a safety.

Controls

What does the pressure switch on an induced-draft furnace prove?

  • a.That the gas valve is supplying the correct manifold pressure
  • b.That the inducer is moving combustion air through the vent✓
  • c.That the igniter has reached its full ignition temperature
  • d.That the main blower is moving air across the heat exchanger

The switch closes on the negative pressure created by the inducer, proving venting before ignition is allowed. A blocked flue, failed inducer, or cracked tubing keeps it open and locks out the burner.

Controls

A flame rectification sensor proves burner flame by:

  • a.Passing a small DC current through the flame to ground✓
  • b.Opening a bimetal contact when its tip is heated
  • c.Generating a millivolt signal when its tip is heated
  • d.Measuring ultraviolet light given off by the flame

The control applies AC to the flame rod, and the flame conducts and rectifies it into a microamp DC signal to the grounded burner. A thermocouple generates millivolts, which is a different and older method.

Controls

A thermocouple used on a standing-pilot gas valve produces about:

  • a.120 volts
  • b.24 volts
  • c.30 millivolts✓
  • d.750 millivolts

A single thermocouple heated by the pilot generates roughly 25 to 30 millivolts, enough to hold the safety magnet in. A thermopile (pilot generator) produces about 750 millivolts, and 24 volts comes from a transformer.

Controls

A contactor is used in a condensing unit to:

  • a.Limit the starting current drawn by the compressor
  • b.Let a line-voltage circuit switch the 24-volt control load
  • c.Let a 24-volt control circuit switch the line-voltage load✓
  • d.Protect the compressor windings from overheating

The low-voltage coil pulls in contacts that carry compressor and fan motor current. Overload protection and start assistance are done by other components.

Controls

A control transformer is rated 40 VA with a 24-volt secondary. What is the maximum secondary current?

  • a.About 0.60 amps
  • b.About 1.67 amps✓
  • c.About 16.0 amps
  • d.About 960 amps

Current equals volt-amperes divided by volts: 40 divided by 24 is about 1.67 amps. Dividing 24 by 40 gives 0.6, and multiplying the two gives 960, neither of which is a current.

Controls

A heat pump defrost cycle is normally ended by:

  • a.The outdoor fan motor reaching full speed
  • b.A coil temperature sensor or a maximum time limit✓
  • c.The low-pressure switch opening the circuit
  • d.A drop in indoor temperature at the thermostat

Defrost terminates when the outdoor coil sensor reaches its set temperature, with a timer as a backup limit. During defrost the outdoor fan is off and auxiliary heat tempers the indoor air.

Controls

An economizer on a rooftop unit is a control arrangement that:

  • a.Uses return air to precool the outdoor condenser coil
  • b.Uses stored chilled water to cool during peak hours
  • c.Uses warm condenser air to reheat the supply air
  • d.Uses cool outdoor air for cooling when conditions allow✓

An air-side economizer opens outdoor air dampers for free cooling when outdoor temperature or enthalpy is suitable, reducing compressor run time. It also provides minimum ventilation air at other times.

Controls

An enthalpy economizer control differs from a dry-bulb control because it also takes account of:

  • a.Outdoor air velocity
  • b.Return air volume
  • c.Outdoor air humidity✓
  • d.Supply duct pressure

Enthalpy is total heat, so the control considers moisture as well as temperature and will not bring in cool but humid air that would add latent load. A dry-bulb control looks at temperature only.

Controls

What is the purpose of the anti-short-cycle (time delay) control on a compressor?

  • a.To let the crankcase heater turn off during operation
  • b.To let the evaporator fan run after the compressor stops
  • c.To let pressures equalize before the compressor restarts✓
  • d.To let the thermostat reach its setpoint more quickly

A delay of a few minutes prevents a restart against a high pressure difference, which can stall the motor and trip its overload. Fan-off delay is a separate function.

Controls

Low-ambient head pressure control on an air-cooled condenser is commonly done by:

  • a.Closing the liquid line solenoid
  • b.Raising the thermostat setpoint
  • c.Cycling or slowing the condenser fan✓
  • d.Cycling the evaporator blower motor

In cold weather the condenser rejects heat too easily and head pressure drops, starving the metering device. Fan cycling, fan speed control, or condenser flooding keep head pressure up.

Controls

In a pump-down control arrangement, the thermostat directly controls the:

  • a.Condenser fan motor relay
  • b.Compressor contactor coil
  • c.Liquid line solenoid valve✓
  • d.Crankcase heater circuit

On a call for cooling the thermostat opens the liquid line solenoid; rising suction pressure closes the low-pressure control, which starts the compressor. When satisfied, the solenoid closes and the compressor pumps the low side down until the low-pressure control opens.

Controls

A thermostat's heat anticipator or cycle-rate setting is used to:

  • a.Prevent the space temperature from overshooting the setpoint✓
  • b.Prevent the blower from running after the burners shut off
  • c.Prevent the furnace limit from opening on a long call for heat
  • d.Prevent the compressor from starting under a locked rotor

The anticipator ends the call for heat slightly early so residual heat in the furnace brings the room to setpoint without overshoot. It is matched to the control circuit current or set as cycles per hour.

Controls

An oil pressure safety control on a commercial compressor acts on:

  • a.Crankcase pressure alone, read at the suction service valve
  • b.Total oil pressure, pump discharge plus crankcase pressure
  • c.Discharge pressure alone, read at the discharge service valve
  • d.Net oil pressure, pump discharge minus crankcase pressure✓

Useful oil pressure is the pump outlet pressure minus crankcase (suction) pressure. The control has a time delay so the compressor can build oil pressure at start-up and shuts it down if net pressure stays too low.

Controls

A normally open control contact is one that:

  • a.Is open when its coil or sensor is de-energized✓
  • b.Is open at all times unless reset by hand
  • c.Is open when its coil or sensor is energized
  • d.Is open only when the line voltage is low

Contacts are named for their position with no power or signal applied. A normally open contact closes when the relay coil is energized; a normally closed contact opens.

Controls

A two-stage cooling thermostat brings on the second stage when:

  • a.The outdoor temperature falls below the balance point
  • b.The first stage has run for less than one minute
  • c.The indoor fan is switched to continuous operation
  • d.The first stage cannot hold the space at setpoint✓

Second stage is called when the temperature keeps drifting from setpoint, by a set difference or after a time, showing that first-stage capacity is not enough for the load.