Texas Air Conditioning and Refrigeration Contractor Exam — All Questions

300 questions

Piping

Under IMC §307.2.1, a horizontal condensate drain line must slope toward its discharge at a minimum of:

  • a.1/4 inch per foot
  • b.1/8 inch per foot✓
  • c.1/2 inch per foot
  • d.1/16 inch per foot

The minimum slope is one-eighth unit vertical in 12 units horizontal, about 1%. More slope is fine; less allows water to stand and the line to clog.IMC §307.2.1

Piping

Under IMC §307.2.2, the smallest condensate drain line allowed from an air conditioning coil is:

  • a.3/4 inch nominal✓
  • b.1 inch nominal
  • c.3/8 inch nominal
  • d.1/2 inch nominal

Condensate piping may not be smaller than 3/4 inch internal diameter and may not be reduced in size from the pan connection to the point of disposal. Larger loads use the sizing table in the same section.IMC §307.2.2

Piping

Under 16 TAC §75.100, an air conditioning licensee may connect a condensate drain that ends inside the building if the connection is made:

  • a.On the outlet side of a properly installed trap
  • b.Directly to the building sewer cleanout
  • c.Directly to a vent stack above the roof line
  • d.On the inlet side of a properly installed trap✓

The Texas rule lets a licensee install drain piping that ends outside the building, and make an indoor connection only on the inlet side of a properly installed trap. Work on the sanitary drainage side belongs to the plumbing trade.16 TAC §75.100(b)(2)

Piping

A condensate trap is required on a draw-through air handler because the drain pan is:

  • a.Under positive pressure, which would blow water up the drain
  • b.Below the coil, which would collect dirt from the filter
  • c.Under negative pressure, which would pull air up the drain✓
  • d.Above the blower, which would spray water on the motor

In a draw-through unit the pan is on the suction side of the blower. Without a trap deep enough to offset that negative pressure, air is drawn in through the drain and holds the water in the pan until it overflows.

Piping

ACR copper tubing is identified by its:

  • a.Weight per linear foot
  • b.Wall thickness in mils
  • c.Actual outside diameter✓
  • d.Nominal inside diameter

Refrigeration (ACR) tubing is sized by actual outside diameter, so 7/8-inch ACR tube measures 7/8 inch across. Plumbing tube is named by a nominal size that is about 1/8 inch less than its outside diameter.

Piping

ACR tubing is shipped cleaned, capped and charged with nitrogen in order to:

  • a.Keep the copper soft enough to be flared
  • b.Keep the tube from flattening when it is bent
  • c.Keep moisture and oxidation out of the tube✓
  • d.Show that the tube has passed a leak test

The nitrogen holding charge and caps keep air, moisture and dirt out until installation. Contaminants left in tubing end up in the compressor oil, the drier and the metering device.

Piping

Which filler metal is commonly used to braze copper-to-copper refrigerant joints without flux?

  • a.95/5 tin-antimony solder
  • b.50/50 tin-lead soft solder with flux
  • c.Phosphorus-copper alloy (BCuP)✓
  • d.Aluminum-silicon rod

BCuP alloys are self-fluxing on copper and melt above 1,100°F, giving joints strong enough for refrigerant pressures. Soft solders melt below 840°F and are used on water and condensate lines, and copper to brass or steel needs flux and a silver alloy.

Piping

The difference between brazing and soldering is that brazing filler metals melt:

  • a.Below 840°F
  • b.Above 840°F✓
  • c.Above 2,000°F
  • d.Below 450°F

By definition, soldering uses filler that melts below 840°F and brazing uses filler that melts above 840°F but below the melting point of the base metal.

Piping

A refrigerant flare fitting for ACR tubing is made with a flare angle of:

  • a.30 degrees
  • b.60 degrees
  • c.37 degrees
  • d.45 degrees✓

Refrigeration flares are 45 degrees. The 37-degree flare is used in hydraulic service and will not seal on a refrigeration fitting.

Piping

Under IMC Table 305.4, horizontal copper tubing 1-1/4 inches and smaller must be supported at intervals of no more than:

  • a.12 feet
  • b.6 feet✓
  • c.4 feet
  • d.10 feet

Small copper tubing is supported at least every 6 feet horizontally and 10 feet vertically; 1-1/2 inch and larger tubing may go to 10 feet horizontally. Hangers must not damage the tube or cause galvanic corrosion.IMC Table 305.4

Piping

An undersized suction line causes:

  • a.High suction pressure at the compressor
  • b.Liquid floodback to the compressor
  • c.Excess pressure drop and a loss of capacity✓
  • d.Low vapor velocity and poor oil return to the compressor

A suction line that is too small has a high pressure drop, which lowers pressure at the compressor, raises the compression ratio and cuts capacity. Poor oil return is the problem with an oversized line, where velocity is too low.

Piping

Excessive pressure drop in a liquid line, or a long vertical lift, can cause:

  • a.Liquid slugging at the compressor
  • b.High head pressure at the condenser outlet
  • c.Oil logging in the receiver
  • d.Flash gas ahead of the metering device✓

If liquid pressure falls below saturation for its temperature, some of it flashes to vapor, starving the metering device. Adequate subcooling and proper line sizing prevent it.

Piping

A service valve that is fully backseated:

  • a.Opens the line and the gauge port together
  • b.Closes the line and opens the gauge port
  • c.Closes the line and the gauge port together
  • d.Closes the gauge port and opens the line✓

Backseating (stem all the way out) shuts off the gauge port while leaving the line open to the system. Frontseating closes the line, and a mid position opens everything.

Piping

Under IFGC §408.4, a sediment trap on the gas supply to a furnace is installed:

  • a.At the lowest point of the building's gas piping system only
  • b.Downstream of the appliance gas valve, at the burner manifold inlet
  • c.Upstream of the gas meter, as close to the utility's service regulator as practical
  • d.Downstream of the shutoff valve, as close to the appliance inlet as practical✓

The sediment trap is a tee with a capped nipple at the bottom placed after the appliance shutoff valve and as close to the appliance inlet as practical, to catch debris before it reaches the gas control.IFGC §408.4

Piping

Under IFGC §409.5, the shutoff valve for a gas appliance must be in the same room as the appliance and within:

  • a.12 feet of it
  • b.3 feet of it
  • c.10 feet of it
  • d.6 feet of it✓

The appliance shutoff valve is located in the same room, within 6 feet of the appliance, upstream of the union or connector, and must be accessible.IFGC §409.5

Piping

A listed flexible gas appliance connector may not be:

  • a.Installed in the same room as the appliance
  • b.Used on an appliance with a draft hood
  • c.Run through a wall, floor or ceiling✓
  • d.Connected downstream of the shutoff valve

Connectors must be entirely in the same room as the appliance and may not be concealed in or pass through walls, floors, partitions or ceilings. They are limited in length and connect to the outlet of the shutoff valve.IFGC §411.1

Piping

Under IFGC §406.4.1, new gas piping is pressure tested at not less than 1.5 times the proposed maximum working pressure and never less than:

  • a.10 psig
  • b.1 psig
  • c.30 psig
  • d.3 psig✓

The test pressure is at least one and one-half times the maximum working pressure but not less than 3 psig, held on a gauge suited to that pressure. Appliances and their controls are isolated from the test.IFGC §406.4.1

Piping

What is used as the test medium for a pressure test of fuel gas piping?

  • a.The fuel gas at line pressure
  • b.Air, nitrogen or another inert gas✓
  • c.Water at city main pressure
  • d.Oxygen from a welding cylinder at low pressure

Gas piping is tested with air, nitrogen, carbon dioxide or an inert gas. Oxygen must never be used, since it can react explosively with oil and fuel residue.IFGC §406.4

Safety

Under 29 CFR 1904.39, an employer must report a work-related fatality to OSHA within:

  • a.8 hours✓
  • b.7 days
  • c.48 hours
  • d.24 hours

A fatality must be reported within 8 hours. Twenty-four hours is the deadline for an inpatient hospitalization, amputation or loss of an eye; seven calendar days is the time allowed to enter a recordable case on the log.29 CFR 1904.39

Safety

An employee is admitted to the hospital as an inpatient after a fall from a rooftop unit. Under 29 CFR 1904.39, the employer must report it to OSHA within:

  • a.24 hours✓
  • b.30 days
  • c.8 hours
  • d.72 hours

Inpatient hospitalization, amputation, and loss of an eye are reported within 24 hours of the employer learning of them. The 8-hour limit applies to a fatality.29 CFR 1904.39

Safety

Which OSHA form is the Log of Work-Related Injuries and Illnesses?

  • a.Form 170
  • b.Form 300✓
  • c.Form 301
  • d.Form 300A

Form 300 is the log, Form 300A is the annual summary that is posted, and Form 301 is the incident report completed for each recordable case.29 CFR 1904.29

Safety

Under 29 CFR 1904.32, the annual summary (Form 300A) must be posted in the workplace from:

  • a.January 1 through March 31
  • b.March 1 through May 31
  • c.January 1 through December 31
  • d.February 1 through April 30✓

The summary of the previous year's cases is posted from February 1 to April 30 where employee notices are normally placed, after a company executive certifies it.29 CFR 1904.32

Safety

Under 29 CFR 1904.33, the OSHA 300 log and related records must be kept for:

  • a.5 years after the year they cover✓
  • b.3 years after the year they cover
  • c.1 year after the year they cover
  • d.10 years after the year they cover

Records are saved for five years following the end of the calendar year they cover, and the log is updated during that time if cases change.29 CFR 1904.33

Safety

Under 29 CFR 1904.29, a recordable injury must be entered on the OSHA 300 log within:

  • a.7 calendar days of learning of it✓
  • b.8 hours of learning of it
  • c.30 calendar days of learning of it
  • d.24 hours of learning of it

The employer has seven calendar days after receiving information that a recordable case occurred. The 8-hour and 24-hour limits are reporting deadlines for severe events, not log entry deadlines.29 CFR 1904.29(b)(3)

Safety

Under 29 CFR 1904.1, a company is partially exempt from keeping OSHA injury and illness records if, at all times in the last calendar year, it had no more than:

  • a.50 employees
  • b.100 employees
  • c.10 employees✓
  • d.25 employees

Companies with ten or fewer employees at all times during the previous year need not keep the records unless OSHA or the Bureau of Labor Statistics asks in writing. They must still report fatalities and severe injuries.29 CFR 1904.1

Safety

Which case is recordable on the OSHA 300 log under 29 CFR 1904.7?

  • a.A cut that is cleaned and bandaged on site
  • b.A bruise treated with an ice pack at the shop
  • c.A visit to a doctor for observation only
  • d.A cut that requires stitches at a clinic✓

A work-related injury is recordable when it results in medical treatment beyond first aid, days away, restricted work, loss of consciousness, or death. Sutures are medical treatment; bandages, cold packs and observation visits are first aid or diagnostic.29 CFR 1904.7

Safety

A refillable recovery cylinder must not be filled beyond what percent of its capacity by weight?

  • a.100%
  • b.80%✓
  • c.90%
  • d.60%

Liquid refrigerant expands as it warms. Leaving 20% vapor space keeps the cylinder from becoming liquid-full and rupturing. A scale or a float switch is used to control the fill.

Safety

Which gas must never be used to pressurize a refrigeration system for leak testing?

  • a.Nitrogen
  • b.Oxygen✓
  • c.Helium
  • d.Carbon dioxide

Oxygen or compressed air mixed with refrigerant oil under pressure can explode. Dry nitrogen through a pressure regulator, with a relief valve downstream, is the standard test gas.

Safety

Why must a pressure regulator be used when charging a system with nitrogen from a cylinder?

  • a.Cylinder pressure is under 100 psi, too low for a system leak test
  • b.Nitrogen is flammable when it leaves the cylinder at full flow
  • c.Cylinder pressure is over 2,000 psi, far above system test pressure✓
  • d.Nitrogen is toxic when it is released in an open equipment room

A full nitrogen cylinder holds well over 2,000 psi, which would burst system components. The regulator, and a relief valve in the line, limit pressure to the test value. Nitrogen is neither flammable nor toxic, though it can displace oxygen.

Safety

Acetylene should never be used at a hose pressure above:

  • a.30 psig
  • b.50 psig
  • c.15 psig✓
  • d.5 psig

Acetylene becomes unstable above 15 psig and can decompose explosively. Cylinders are also kept upright so the acetone that stabilizes the gas is not drawn out.

Safety

A large refrigerant release in a closed mechanical room is dangerous mainly because the vapor:

  • a.Reacts with moisture to form carbon monoxide
  • b.Is heavier than air and displaces oxygen✓
  • c.Corrodes steel piping within a few minutes
  • d.Is lighter than air and collects at the ceiling

Most refrigerant vapors are heavier than air, settle in low areas and push out breathable air, causing asphyxiation without warning. Leave the space and ventilate it before returning.

Safety

When a halogenated refrigerant is exposed to an open flame or a very hot surface, it can break down into:

  • a.Liquid oil and solid carbon only
  • b.Toxic gases such as phosgene and acids✓
  • c.Harmless nitrogen, oxygen and water vapor
  • d.Pure carbon dioxide and oxygen

Chlorine- and fluorine-bearing refrigerants decompose in a flame into toxic and corrosive products, including hydrochloric and hydrofluoric acids and phosgene. Ventilate and purge lines before brazing.

Safety

Before working on the electrical components of a condensing unit, the technician should:

  • a.Remove the contactor cover and hold the contacts open
  • b.Open the disconnect, lock and tag it, and verify zero voltage✓
  • c.Open the thermostat circuit and remove the low-voltage fuse
  • d.Turn the thermostat to "off" and wait for the fan to stop

Lockout/tagout means opening the disconnect, applying a lock and tag, and checking with a meter that the circuit is dead. The thermostat only opens the control circuit; line voltage is still present at the contactor.

Safety

Before handling a run capacitor, it should be:

  • a.Cooled with compressed air
  • b.Tested with the power turned on
  • c.Discharged through a resistor✓
  • d.Shorted with a screwdriver blade

A capacitor can hold a charge after power is off. Bleeding it through a resistor is the safe method; shorting it with a screwdriver can damage the capacitor and injure the technician.

Safety

Liquid refrigerant sprayed on the skin causes:

  • a.Frostbite✓
  • b.An electric shock
  • c.A heat rash
  • d.A chemical burn

Liquid refrigerant boils at very low temperatures at atmospheric pressure and freezes tissue on contact. Gloves and eye protection are worn when connecting hoses and handling cylinders.

Safety

An extension ladder used to reach a roof should extend above the landing by at least:

  • a.18 inches
  • b.3 feet✓
  • c.6 feet
  • d.1 foot

The side rails extend at least 3 feet above the upper landing so there is something to hold while stepping off, and the ladder is set at about a 4 to 1 angle and secured.29 CFR 1926.1053

Ventilation

The purpose of mechanical ventilation in an occupied building is to:

  • a.Lower the relative humidity of the supply air
  • b.Bring in outdoor air to dilute indoor contaminants✓
  • c.Recirculate indoor air to even out temperatures
  • d.Raise the static pressure in the return duct

Ventilation replaces a portion of indoor air with outdoor air to control odors, carbon dioxide and other contaminants. Recirculation alone does not ventilate.IMC Chapter 4

Ventilation

Under IMC §401.4, a mechanical outdoor air intake must be located at least how far from a hazardous or noxious contaminant source such as a plumbing vent or a chimney?

  • a.25 feet horizontally
  • b.3 feet horizontally
  • c.5 feet horizontally
  • d.10 feet horizontally✓

Intake openings are kept at least 10 feet from contaminant sources such as vents, chimneys, streets and loading docks, with listed exceptions. The separation keeps exhaust from being drawn back into the building.IMC §401.4

Ventilation

An energy recovery ventilator (ERV) differs from a heat recovery ventilator (HRV) in that an ERV transfers:

  • a.Refrigerant between two separate coils
  • b.Heat only between the two airstreams
  • c.Moisture only between the two airstreams, with no heat
  • d.Both heat and moisture between the airstreams✓

An ERV core exchanges sensible heat and water vapor between exhaust and incoming air, reducing the latent load of ventilation in a humid climate. An HRV exchanges sensible heat only.

Ventilation

A refrigeration machinery room is required to have a refrigerant detector that:

  • a.Sounds an alarm and starts the mechanical ventilation✓
  • b.Opens the relief valves on the pressure vessels
  • c.Shuts the room lights off and locks the access door
  • d.Starts the compressors to pump the system down

The detector, located where leaked refrigerant will concentrate, triggers audible and visual alarms and the ventilation system when its set concentration is reached.IMC §1105

Ventilation

Doors of a refrigeration machinery room are required to be:

  • a.Removable, with an inside key lock
  • b.Sliding, with a fusible-link closer
  • c.Louvered, held open during operation, and opening inward
  • d.Tight-fitting, self-closing, and opening outward✓

Machinery room doors are tight-fitting and self-closing so leaked refrigerant stays in the room, and they swing outward for escape. Openings that would let refrigerant pass to other parts of the building are not allowed.International Mechanical Code, refrigeration machinery room requirements

Ventilation

Machinery room exhaust ventilation must discharge:

  • a.Into an adjoining corridor or stairway
  • b.Outdoors, away from air intakes and openings✓
  • c.Into the attic space above the room
  • d.Into the return air plenum of the building it serves

Refrigerant-laden air is discharged to the outdoors where it will not cause a nuisance or re-enter the building. Sending it into plenums, corridors or attics spreads the hazard.IMC §1105

Ventilation

A commercial kitchen hood over a fryer that produces grease-laden vapor must be a:

  • a.Type II hood
  • b.Residential range hood
  • c.Type I hood✓
  • d.Recirculating fan

Type I hoods are for grease and smoke and have grease filters and a liquid-tight exhaust duct. Type II hoods handle only heat, steam and odors, as over a dishwasher.IMC §507

Ventilation

When a large exhaust fan is added to a tight building without makeup air, the likely result is:

  • a.Lower humidity because less outdoor air leaks inward
  • b.Negative pressure that can backdraft fuel-burning appliances✓
  • c.Higher airflow through the exhaust fan than its rating
  • d.Positive pressure that pushes conditioned air out of the doors

Exhaust without makeup air depressurizes the building, pulling air down vents and chimneys and reducing the fan's own airflow. The code requires makeup air roughly equal to the exhaust.IMC §501

Venting

Under IMC §504, the maximum length of a 4-inch clothes dryer exhaust duct, before deductions for fittings and absent manufacturer's instructions that allow more, is:

  • a.50 feet
  • b.15 feet
  • c.25 feet
  • d.35 feet✓

The code's default limit is 35 feet from the dryer connection to the outlet terminal, reduced for each elbow. A longer run is allowed only where the dryer manufacturer's instructions permit it.IMC §504

Venting

Why may sheet metal screws not protrude into a dryer exhaust duct more than 1/8 inch?

  • a.They void the listing of the backdraft damper
  • b.They corrode quickly in the hot, moist exhaust air
  • c.They catch lint, which restricts flow and can ignite✓
  • d.They loosen from vibration and let the joints leak

Fasteners sticking into the airstream snag lint. Built-up lint cuts airflow, lengthens drying time and is a fire hazard. Joints run in the direction of airflow for the same reason.IMC §504

Venting

A dryer exhaust duct must terminate:

  • a.In the attic, at least 3 feet from the roof deck
  • b.Outdoors, with a backdraft damper and no screen✓
  • c.In the crawl space, with a lint trap at the end
  • d.Outdoors, with a fine screen over the opening

Dryer exhaust goes to the outdoors and the termination has a backdraft damper. Screens are prohibited because they clog with lint. Discharging into an attic or crawl space adds moisture and lint to the building.IMC §504

Venting

A flexible transition duct between a dryer and the exhaust duct must be:

  • a.A foil duct run through the floor to the crawl space vent
  • b.Any plastic duct that is no longer than twelve feet overall
  • c.Two listed lengths joined inside the wall behind the dryer
  • d.A single listed length that is not concealed in construction✓

The transition duct is one listed and labeled piece, limited in length, and it may not be concealed within construction. The concealed portion of the run must be rigid metal duct.IMC §504

Venting

A Category I gas appliance vents with:

  • a.Positive vent pressure and flue gas hot enough to avoid condensation
  • b.Non-positive vent pressure and flue gas cool enough to condense
  • c.Positive vent pressure and flue gas cool enough to condense
  • d.Non-positive vent pressure and flue gas hot enough to avoid condensation✓

Category I appliances, such as draft-hood and fan-assisted 80% furnaces, operate with non-positive vent static pressure and do not condense in the vent, so Type B vent is used. Category IV appliances are positive pressure and condensing.IFGC §202

Venting

A single-wall or Type B vent connector from a draft-hood appliance must slope:

  • a.Downward toward the vent at least 1/4 inch per foot
  • b.Level, with a drip tee at the base of the vent
  • c.Upward toward the vent at least 1/4 inch per foot✓
  • d.Upward toward the appliance at least 1/8 inch per foot

Vent connectors rise toward the vent or chimney at not less than 1/4 inch per foot with no dips or sags, so buoyant flue gas flows upward and condensate does not pool.IFGC §503.10