Texas Air Conditioning and Refrigeration Contractor Exam — All Questions
300 questions
Which ACCA manual is used to calculate the heating and cooling loads of a residence?
- a.Manual D
- b.Manual S
- c.Manual T
- d.Manual J✓
Manual J is residential load calculation, Manual S is equipment selection, Manual D is duct design, and Manual T covers air distribution outlets. PSI allows Manuals J, S and D at the Environmental Air exams.
Which ACCA manual is used to select equipment whose capacity matches the calculated loads?
- a.Manual N
- b.Manual D
- c.Manual J
- d.Manual S✓
Manual S takes the Manual J loads and the manufacturer's expanded performance data at design conditions to select equipment within sizing limits. Manual N is the commercial load manual.
A cooling load calculation shows 24,000 Btu/h sensible and 6,000 Btu/h latent. The sensible heat ratio of the load is:
- a.0.75
- b.1.25
- c.0.25
- d.0.80✓
Sensible heat ratio is sensible load divided by total load: 24,000 divided by 30,000 is 0.80. Dividing latent by sensible gives 0.25, which is not the ratio asked for.
Selected equipment must have enough latent capacity at design conditions. If the sensible heat ratio of the equipment is much higher than that of the load, the space will tend to be:
- a.Comfortable in all weather
- b.Dry enough but too warm
- c.Cool enough but too humid✓
- d.Too cold and too dry
A high equipment sensible heat ratio means little moisture removal. The thermostat is satisfied on temperature while humidity stays high, a common result of oversizing or excessive airflow.
Why does Manual S warn against substantially oversized cooling equipment?
- a.High airflow gives lower suction pressure and icing
- b.Long cycles give poor humidity removal and less wear
- c.Low airflow gives higher head pressure and less noise
- d.Short cycles give poor humidity removal and more wear✓
Oversized equipment satisfies the thermostat quickly, so the coil does not run long enough to remove moisture, and frequent starts add wear and noise. Sizing limits in Manual S keep capacity close to the calculated load.
A furnace has an input rating of 100,000 Btu/h and an efficiency of 80%. Its output is:
- a.100,000 Btu/h
- b.125,000 Btu/h
- c.80,000 Btu/h✓
- d.20,000 Btu/h
Output is input times efficiency: 100,000 times 0.80 is 80,000 Btu/h. The 20,000 Btu/h figure is the heat lost up the vent, and 125,000 divides instead of multiplying.
A 15 kW electric heat strip produces about how much heat?
- a.34,100 Btu/h
- b.51,200 Btu/h✓
- c.15,000 Btu/h
- d.180,000 Btu/h
One kilowatt is 3,413 Btu/h, so 15 kW is about 51,200 Btu/h. 34,100 Btu/h is the output of a 10 kW heater.
A unit nameplate lists a minimum circuit ampacity (MCA) of 23 amps and a maximum overcurrent protection (MOCP) of 40 amps. These two values are used to:
- a.Size the branch conductors from MCA and limit the breaker to MOCP✓
- b.Size the branch conductors from MOCP and limit the breaker to MCA
- c.Size the breaker from the running load amps and ignore both values
- d.Size the disconnect from MCA and the thermostat wire from MOCP
Conductors must have an ampacity of at least the MCA, and the fuse or breaker may not be larger than the MOCP. Reversing them undersizes the protection or oversizes the wire for no purpose.
A motor is rated 230 volts. Using the usual plus or minus 10% tolerance, the acceptable supply voltage range is:
- a.220 to 240 volts
- b.207 to 253 volts✓
- c.197 to 263 volts
- d.208 to 230 volts
Ten percent of 230 is 23 volts, giving 207 to 253. Equipment marked 208/230 has a wider stated range from the manufacturer, so the nameplate governs.
Three-phase voltages measure 220, 230 and 225 volts. Using percent imbalance = maximum deviation from average ÷ average × 100, the imbalance is about:
- a.10%
- b.4.4%
- c.2.2%✓
- d.1.0%
The average is 225 volts and the greatest deviation is 5 volts; 5 divided by 225 is about 2.2%. Manufacturers commonly limit voltage imbalance to 2%, because a small voltage imbalance produces a much larger current imbalance and winding heat.
The balance point of a heat pump is the outdoor temperature at which:
- a.Heat pump capacity equals the heat loss of the building✓
- b.Heat pump capacity equals the cooling load of the building
- c.The outdoor coil begins to frost and call for defrost
- d.The compressor is locked out and electric heat takes over
Above the balance point the heat pump alone carries the load; below it, supplemental heat is needed. It is found by plotting the building's heat loss line against the heat pump's capacity curve.
A heat pump delivers 36,000 Btu/h of heat while drawing 3.5 kW. Its coefficient of performance is about:
- a.10.3
- b.1.0
- c.3.5
- d.3.0✓
COP is heat output divided by energy input in the same units: 3.5 kW is about 11,950 Btu/h, and 36,000 divided by 11,950 is about 3.0. 10.3 is Btu/h per watt, which is an EER-style figure, not COP.
An air conditioner's EER is its:
- a.Cooling output in Btu/h divided by power input in watts✓
- b.Seasonal heating output divided by seasonal energy input
- c.Cooling output in tons divided by power input in kilowatts
- d.Power input in watts divided by cooling output in Btu/h
EER is Btu/h of cooling per watt at a single rating condition. SEER is the seasonal version, and HSPF is the heating seasonal measure for heat pumps.
Under IMC §306.1, the level working space in front of the control side of an appliance must be at least:
- a.36 inches deep and 30 inches wide
- b.30 inches deep and 22 inches wide
- c.30 inches deep and 30 inches wide✓
- d.24 inches deep and 24 inches wide
The code calls for a level working space not less than 30 inches by 30 inches in front of the control or service side. The appliance must also be removable without taking out permanent construction.IMC §306.1
An appliance is installed in an attic. Under IMC §306.3, the passageway to it may be no longer than:
- a.20 feet, measured along its centerline✓
- b.30 feet, measured from the appliance
- c.50 feet, measured along its centerline
- d.10 feet, measured from the appliance
The attic passageway is limited to 20 feet from the opening to the appliance, with solid flooring at least 24 inches wide and a clear opening large enough to remove the largest appliance. The code lists exceptions for taller, wider passageways.IMC §306.3
A gas furnace with an open ignition source is installed in a residential garage. Under IMC §304.3, the source of ignition must be elevated above the floor at least:
- a.24 inches
- b.6 inches
- c.18 inches✓
- d.12 inches
Ignition sources in garages are raised at least 18 inches so they sit above the layer where gasoline vapors collect. Appliances listed as flammable vapor ignition resistant are excepted.IMC §304.3
Rooftop equipment needing service is located 6 feet from the roof edge, and the roof is more than 30 inches above grade. Under IMC §304.11, what is required?
- a.A guard at least 42 inches high along the roof edge✓
- b.A permanent ladder fixed to the side of the equipment
- c.A warning line painted 24 inches from the roof edge
- d.A walkway pad between the roof hatch and the unit
Guards are required where equipment or components needing service are within 10 feet of a roof edge or open side more than 30 inches above the level below. The guard must be at least 42 inches high.IMC §304.11
An evaporator coil is installed above a finished ceiling where condensate overflow would damage the building. IMC §307.2.3 requires:
- a.A second cooling coil piped in series with the primary coil
- b.A larger primary drain line, at least one size above the minimum
- c.A condensate pump wired to run whenever the blower operates
- d.An auxiliary protection method, such as a secondary pan or drain✓
Where damage could result from a stopped primary drain, the code requires one of several secondary protections: an auxiliary pan with a separate drain, a separate overflow drain, or a water-level detection device that shuts the equipment off.IMC §307.2.3
An auxiliary drain pan installed under a coil per IMC §307.2.3 must be:
- a.At least 2 inches deep and 6 inches larger than the unit on each side
- b.At least 1.5 inches deep and 3 inches larger than the unit on each side✓
- c.At least 1 inch deep and the same size as the base of the unit
- d.At least 3 inches deep and 1.5 inches larger than the unit on each side
The pan depth is at least 1.5 inches, and it extends at least 3 inches beyond the unit or coil dimensions in width and length. The discharge from the pan's drain must be at a point where the occupants will notice it.IMC §307.2.3.1
When a duct system is designed with Manual D, the blower data used to set available static pressure comes from:
- a.The Manual J worksheet for the room with the largest heat gain
- b.The nameplate horsepower and full-load amperage of the blower motor
- c.The manufacturer's blower performance table for the selected unit✓
- d.The friction chart printed on the back of the duct calculator
The blower table shows how much external static pressure the fan can produce at the design airflow. Subtracting the pressure drops of coil, filter and other components gives the pressure available for the ducts.
In a Manual J calculation, outdoor design temperatures are taken from:
- a.The highest temperature ever recorded there
- b.The average annual temperature of the area
- c.Published design conditions for the location✓
- d.The owner's preferred thermostat settings
Manual J uses tabulated outdoor design conditions (for example the 1% cooling and 99% heating values) for the location. Designing for record extremes oversizes the equipment.
Infiltration adds to the cooling load of a house as:
- a.Radiant heat from the roof and nothing else
- b.Latent heat only
- c.Both sensible and latent heat✓
- d.Sensible heat only
Outdoor air leaking in is both warmer and more humid than indoor air in a Texas summer, so it brings sensible and latent load. Duct leakage on the return side in an attic has a similar effect.
Which internal load adds latent heat to a space?
- a.People✓
- b.Lighting
- c.Computers
- d.Motors
People give off both sensible heat and moisture. Lights, electronics and motors add sensible heat only, since they release no water vapor.
Natural gas is assumed to have a heating value of about 1,000 Btu per cubic foot. A furnace burns 1.5 cubic feet per minute. Its input is about:
- a.150,000 Btu/h
- b.15,000 Btu/h
- c.90,000 Btu/h✓
- d.60,000 Btu/h
1.5 cubic feet per minute is 90 cubic feet per hour, and 90 times 1,000 is 90,000 Btu/h. Clocking the meter this way checks the firing rate against the nameplate.
A condensing unit's nameplate states "Minimum circuit ampacity 18.5 A." The smallest acceptable branch conductor is one with an ampacity of at least:
- a.18.5 amps✓
- b.23.1 amps
- c.37.0 amps
- d.14.8 amps
MCA already includes the 125% factor on the largest motor, so the conductor only has to carry the MCA. Multiplying by 1.25 again or by 2 oversizes the wire, and 80% undersizes it.
Latent capacity of cooling equipment generally rises when the blower airflow per ton is:
- a.Raised, giving a warmer coil
- b.Held, with a larger filter
- c.Reduced, giving a colder coil✓
- d.Raised, giving a colder coil
Lower airflow per ton lowers coil temperature and raises moisture removal, at some cost in sensible capacity. Humid climates often use about 350 CFM per ton for this reason; too little airflow risks icing.
In a split system, which components are in the outdoor section?
- a.Metering device and evaporator
- b.Furnace and filter rack
- c.Evaporator coil and blower
- d.Compressor and condenser coil✓
The condensing unit outdoors holds the compressor, condenser coil and condenser fan. The evaporator, metering device and blower are indoors, joined by the liquid and suction lines.
A packaged rooftop unit differs from a split system in that:
- a.It cannot be equipped with gas heat
- b.It needs field-installed refrigerant lines
- c.All refrigeration components are in one cabinet✓
- d.The compressor is located indoors with the air handler
A package unit is factory charged and contains compressor, both coils and blower in one cabinet connected to the building by ducts. Many include gas heat.
In heating mode, the indoor coil of an air-source heat pump acts as the:
- a.Condenser✓
- b.Accumulator
- c.Evaporator
- d.Receiver
In heating the reversing valve sends hot discharge gas to the indoor coil, which rejects heat to the house and is therefore the condenser. The outdoor coil becomes the evaporator.
During the defrost cycle of an air-source heat pump, the system:
- a.Runs in heating mode with the outdoor fan on
- b.Runs the indoor blower with the compressor off
- c.Shuts the compressor off until the ice melts
- d.Runs in cooling mode with the outdoor fan off✓
Defrost reverses the cycle so hot gas goes to the outdoor coil, and the outdoor fan stops so the coil warms quickly. Auxiliary heat is energized to temper the cool air delivered indoors.
A suction line that rises vertically from an evaporator below the compressor needs an oil trap at the bottom of the riser to:
- a.Keep liquid refrigerant from reaching the evaporator
- b.Stop vibration from travelling along the suction line
- c.Help carry oil up the riser back to the compressor✓
- d.Hold a reserve of refrigerant for periods of high load
Oil collects at the base of a vertical suction riser; a trap lets vapor velocity pick the oil up and carry it upward. Without proper velocity and trapping, oil stays in the low side and the compressor runs short.
Horizontal suction lines are pitched slightly:
- a.Toward the compressor, to help oil return✓
- b.Upward at both ends, to form a liquid seal
- c.Level in all cases, to keep the velocity even
- d.Toward the evaporator, to drain the oil back
Sloping horizontal suction runs in the direction of flow lets gravity help move oil to the compressor. Pitching back to the evaporator would log oil in the coil.
Which line of a split system is insulated, and why?
- a.The suction line, to limit heat gain and stop sweating✓
- b.The liquid line, to limit heat loss and stop sweating
- c.The discharge line, to protect the outdoor fan motor
- d.The condensate line, to keep the trap from drying out
The cold suction line would pick up heat, raising superheat and compressor temperature, and would drip condensation. The liquid line is normally left bare unless it runs through a very hot space.
Which defrost method is commonly used on a medium-temperature walk-in cooler held at about 38°F?
- a.Off-cycle defrost using box air✓
- b.Electric defrost with a drain heater
- c.Hot gas defrost with a reversing valve
- d.Water defrost with a spray header
When the box is above freezing, simply stopping refrigeration with the evaporator fans running lets box air melt the frost. Low-temperature freezers need electric or hot gas defrost because the box air is below 32°F.
On a low-temperature freezer evaporator with electric defrost, the fan delay control:
- a.Keeps the fans on during defrost to speed the melting of ice
- b.Keeps the fans off until the coil is cold again after defrost✓
- c.Keeps the compressor off until the box reaches setpoint
- d.Keeps the heaters on until the fans have reached full speed
After defrost the coil is warm and wet. The fan delay holds the fans off until the coil drops below freezing so warm air and water droplets are not blown onto the product.
An evaporator pressure regulator (EPR) valve is installed to:
- a.Keep head pressure from falling during cold weather
- b.Keep liquid from flashing ahead of the metering device
- c.Keep evaporator pressure from falling below a set point✓
- d.Keep crankcase pressure from rising above a set point
An EPR sits in the suction line at the evaporator outlet and holds a minimum evaporator pressure, which lets a warmer evaporator share a compressor with colder ones. Limiting pressure at the compressor inlet is the job of a crankcase pressure regulator.
A crankcase pressure regulator (CPR) valve protects the compressor by:
- a.Limiting suction pressure at the compressor during a hot pull-down✓
- b.Limiting discharge pressure at the compressor during a high ambient
- c.Raising suction pressure at the compressor during a light load
- d.Raising oil pressure at the compressor during a cold start
The CPR throttles the suction line near the compressor so the motor is not overloaded by high suction pressure after defrost or on start-up with a warm box.
Hot gas bypass is used on some systems to:
- a.Keep head pressure down at high load and prevent tripping
- b.Recover heat from the discharge gas to warm domestic water
- c.Return oil from the oil separator to the compressor crankcase
- d.Keep suction pressure up at low load and prevent coil icing✓
Bypassing some discharge gas to the low side adds a false load so the compressor can keep running at light load without the evaporator dropping below freezing. It is a capacity control method.
In a chilled-water system, the chiller's evaporator cools:
- a.Water that is pumped to air handler coils✓
- b.Air that is ducted directly to the rooms
- c.Refrigerant returning from remote coils
- d.Water that is pumped to the cooling tower
The chiller evaporator (cooler) chills water, typically from about 54°F to 44°F, and pumps circulate it to coils in air handlers and fan coils. The cooling tower handles condenser water, a separate loop.
A cooling tower rejects heat mainly by:
- a.Radiating heat from the tower's metal casing
- b.Conducting heat to the makeup water supply
- c.Evaporating a small part of the condenser water✓
- d.Compressing water vapor inside the tower fill
Most of a tower's heat rejection is evaporative: as a small fraction of the water evaporates, it cools the rest. This is why tower performance depends on the entering air's wet-bulb temperature.
Water enters a cooling tower at 95°F and leaves at 85°F when the entering air wet-bulb temperature is 78°F. The tower's approach is:
- a.17°F
- b.7°F✓
- c.85°F
- d.10°F
Approach is leaving water temperature minus entering wet-bulb: 85 minus 78 is 7°F. The 10°F difference between entering and leaving water is the range.
A variable air volume (VAV) system controls space temperature by:
- a.Cycling the supply fan on and off for each individual zone
- b.Mixing hot and cold airstreams at each zone's terminal box
- c.Varying the temperature of supply air delivered to each zone
- d.Varying the amount of supply air delivered to each zone✓
A VAV box throttles airflow at a roughly constant supply air temperature. Varying supply temperature at constant volume describes a constant-volume reheat system, and mixing two airstreams describes a dual-duct system.
In a variable refrigerant flow (VRF) system, capacity is matched to load mainly by:
- a.Cycling a single-speed compressor on a room thermostat
- b.Varying chilled-water flow with two-way control valves
- c.Varying compressor speed and indoor unit refrigerant flow✓
- d.Opening outdoor air dampers on each indoor unit
VRF systems use inverter-driven compressors and electronic expansion valves at each indoor unit to modulate refrigerant flow. They are direct-expansion systems and use no chilled water.
A cascade refrigeration system is used to:
- a.Reach higher efficiency by putting two condensers in series
- b.Recover heat from one zone and deliver it to another
- c.Serve several evaporators from one large compressor
- d.Reach very low temperatures with two refrigerant circuits✓
In a cascade system the evaporator of the high-stage circuit cools the condenser of the low-stage circuit, so each compressor works at a reasonable compression ratio while reaching very low temperatures.
Liquid line sight glass shows bubbles on a system with a receiver and a thermostatic expansion valve. This may indicate:
- a.A high refrigerant charge or a dirty evaporator
- b.A low refrigerant charge or a restriction upstream✓
- c.A failed crankcase heater on the compressor
- d.A high superheat setting at the expansion valve
Bubbles mean vapor in the liquid line, from a short charge or a pressure drop such as a plugged drier ahead of the glass. The sight glass's moisture indicator separately shows whether the system is dry.
On a parallel-rack supermarket system, the compressors are staged to maintain:
- a.A common discharge temperature
- b.A common suction pressure✓
- c.A common box temperature
- d.A common oil temperature
Rack compressors share suction and discharge headers and are cycled or unloaded to hold suction pressure for the coldest evaporators in the group. Individual cases use EPR valves or solenoids for their own temperature control.
After new refrigerant piping is brazed, why is the system evacuated before charging?
- a.To remove flux and oxide scale
- b.To test joints for strength
- c.To remove air and moisture✓
- d.To cool the brazed joints
A deep vacuum lowers the boiling point of water so moisture leaves as vapor and removes noncondensable air. Oxide scale is prevented by flowing nitrogen while brazing, and joint tightness is checked by a pressure test.
Why is dry nitrogen flowed through copper tubing at low pressure while brazing?
- a.To keep oxide scale from forming inside the tube✓
- b.To blow excess filler metal out of the fitting
- c.To test the completed joint for refrigerant leaks
- d.To raise the temperature of the joint more quickly
Heating copper in air forms black copper oxide on the inside wall, which later flakes off and plugs driers and metering devices. A slow nitrogen purge displaces the oxygen.
A hydronic heating system uses an expansion tank to:
- a.Separate dissolved air from the water as it circulates
- b.Absorb the increase in water volume as the water heats✓
- c.Raise system pressure enough to lift water to the top
- d.Store hot water for use at times of peak demand
Water expands when heated; the tank's air cushion takes up that volume so system pressure does not rise enough to open the relief valve. Air removal is the job of an air separator or vent.
In most single-zone ductless mini-splits, the electronic expansion valve that meters refrigerant to the indoor unit is located:
- a.In the outdoor unit, so both lines to the indoor unit are cold in cooling✓
- b.In the indoor unit, so the liquid line to the indoor unit stays warm
- c.At the service valve, so neither line needs to be insulated
- d.In the branch box, so that only the larger suction line needs to be insulated
Most mini-splits meter at the outdoor unit, so the "liquid" line leaving it is already cold, low-pressure refrigerant. That is why both lines of a mini-split line set are insulated.