Chapter 12 of 14

Testing

Testing covers the instruments and methods for airflow, combustion, electrical and gas measurements.

Methods

Temperature rise across a furnace is supply minus return and is compared with the nameplate range. Airflow through an electric furnace is kW times 3,413 divided by 1.08 times the temperature rise. Voltmeters connect in parallel, clamp ammeters around one conductor, and ohmmeters only with power off. Natural gas manifold pressure is about 3.5 inches of water column and propane about 10 to 11; the nameplate governs. Clocking the meter gives the firing rate.

Gas leak testing
Use a noncorrosive leak detection fluid or a gas detector, never a flame.
IFGC §406.5