Chapter 11 of 14

Service

Service is diagnosis: reading pressures, superheat and subcooling together, and testing electrical parts.

Reading the system

Fixed-orifice systems are charged by superheat; expansion valve systems by subcooling. Low charge gives high superheat with low subcooling. A liquid line restriction gives high superheat with high subcooling. Overcharge gives low superheat with high subcooling. Noncondensables raise head pressure above the saturation value. A compressor that cannot pump shows high suction, low head and low current.

Evacuation
Pull to 500 microns or lower on a micron gauge; a steady rise after isolation means a leak.
Modern Refrigeration and Air Conditioning
Recovery
Refrigerant is recovered with certified equipment by a certified technician and never vented.
40 CFR Part 82, Subpart F