This area joins load calculation, equipment selection, electrical ratings and the installation rules for appliances.

Loads and selection

Manual J calculates the load, Manual S selects equipment against it, and Manual D designs the ducts. Conduction is U times area times temperature difference, and U is one divided by R. Sensible heat ratio is sensible load over total load. Oversized cooling equipment short-cycles and removes less moisture.

Ratings and installation

Size branch conductors from the nameplate minimum circuit ampacity and limit the overcurrent device to the nameplate maximum. One kilowatt is 3,413 Btu/h. Installation rules cover working space, attic access, garage installations, roof guards and overflow protection for condensate.

Working space
A level space at least 30 inches by 30 inches in front of the service side.
IMC §306.1
Garage ignition sources
Elevated at least 18 inches above the floor unless the appliance is listed as flammable vapor ignition resistant.
IMC §304.3
Auxiliary drain pan
At least 1.5 inches deep and 3 inches larger than the unit.
IMC §307.2.3