Chapter 8 of 14

HVAC and HVACR Systems

System questions ask how whole systems are put together: split and packaged units, heat pumps, chilled water, VAV and VRF on the comfort side; walk-ins, racks, defrost and pressure regulators on the refrigeration side.

What to know

In heat pump heating the indoor coil is the condenser, and defrost is a temporary return to cooling with the outdoor fan off. Suction lines are insulated, pitched toward the compressor and trapped at the base of risers for oil return. Medium-temperature boxes can use off-cycle defrost; freezers need electric or hot gas defrost. An evaporator pressure regulator holds evaporator pressure up; a crankcase pressure regulator holds compressor suction pressure down.

Cooling tower terms
Range is entering minus leaving water temperature; approach is leaving water temperature minus entering wet-bulb.
Modern Refrigeration and Air Conditioning