Controls questions cover the 24-volt thermostat circuit, operating controls and the safeties that protect equipment and people.

Operating controls and safeties

R is the 24-volt supply, Y cooling, W heat, G fan, C common. A low-pressure switch opens on loss of charge; a high-pressure switch opens on high head pressure and is often manual reset. On a furnace the pressure switch proves the inducer, the flame sensor proves flame, and the limit switch opens on overheating. Pump-down systems use the thermostat to control a liquid line solenoid and the low-pressure control to cycle the compressor.

Transformer loading
Maximum secondary current is VA divided by secondary volts.
Modern Refrigeration and Air Conditioning