Chapter 9 of 14

Piping

Piping covers condensate drains, refrigerant lines and the limited fuel gas piping a Texas air conditioning licensee may install.

Condensate, refrigerant and gas

Condensate lines slope to the outlet, are not reduced in size, and need a trap on draw-through units. ACR tubing is sized by outside diameter and brazed while nitrogen flows through it. Undersized suction lines cost capacity; oversized ones return oil poorly. Gas piping work by a licensee stops at the existing shut-off valve.

Condensate slope and size
Not less than 1/8 inch per foot; not less than 3/4 inch.
IMC §307.2.1, §307.2.2
Sediment trap
Downstream of the appliance shutoff valve, as close to the appliance inlet as practical.
IFGC §408.4
Gas pressure test
At least 1.5 times working pressure and not less than 3 psig, using air or an inert gas.
IFGC §406.4