Texas Air Conditioning and Refrigeration Contractor Exam Cheat Sheet (2026)
A free, printable Texas Air Conditioning and Refrigeration Contractor exam cheat sheet: the 35 highest-yield points to know, grouped into 14 sections that follow the exam's content areas.
- Free to read, print and keep — no signup, no email, no paywall.
- 35 of the 35 points carry a citation to the rule they come from.
- The real Texas Air Conditioning and Refrigeration Contractor exam: 120 questions · 230 minutes · 70% to pass.
- Prints from your browser (Ctrl-P, or Cmd-P on a Mac) — the navigation, buttons and links drop out of the printed copy.
- 300 free Texas Air Conditioning and Refrigeration Contractor practice questions on the same material, every one explained.
Texas Laws and Rules
- Class B limit
- A Class B licence covers cooling systems of 25 tons or less and heating systems of 1.5 million Btu/h or less; Class A has no size limit. Several units may exceed the total if each unit is within the limit.· Tex. Occ. Code §1302.253; 16 TAC §75.22(c)
- Insurance
- Class A: $300,000 per occurrence, $600,000 aggregate, $300,000 products and completed operations. Class B: $100,000, $200,000 and $100,000.· 16 TAC §75.40
- Experience
- 48 months of practical experience in the preceding 72 months, or a technician certification held for 12 months plus 36 months in the preceding 48.· Tex. Occ. Code §1302.255
- Temporary licence
- Requested within 15 calendar days after the only licence holder becomes unavailable through death or disability; valid 30 calendar days; not renewable.· 16 TAC §75.23
- Renewal
- One-year licence term; 8 hours of continuing education including 1 hour of Texas law and rules.· 16 TAC §§75.22, 75.24, 75.25
- Notice of changes
- A licensee tells the department in writing within 30 calendar days of a change of address, company location, telephone number or licence assignment.· 16 TAC §75.70(h)
- Scope limits
- Control wiring of 50 volts or less; fuel gas piping only between the appliance and an existing shut-off valve; indoor condensate connections only on the inlet side of a trap.· 16 TAC §75.100
Air Distribution
- Friction rate
- Available static pressure times 100, divided by total effective length. Available static pressure is the blower's external static pressure less the coil, filter, grille and other component drops.· ACCA Manual D
- Total effective length
- Measured straight length of the longest supply and return runs plus the equivalent length of every fitting in them.· ACCA Manual D
- Return air sources
- Prohibited locations are listed in the return air section.· IMC §601.5
- Smoke detection
- Required in return air systems with a design capacity greater than 2,000 CFM.· IMC §606.2.1
Basic Refrigeration Components
- Refrigerant safety groups
- Letter A or B is toxicity; 1, 2L, 2 or 3 is flammability. R-410A is A1; R-32 and R-454B are A2L. Texas reads the adopted codes with the 2024 editions of ASHRAE 15 and 34.· ASHRAE Standard 34; 16 TAC §75.110(c)
Refrigeration Principles
- Superheat and subcooling
- Both are read from a pressure-temperature chart plus a line temperature; neither can be read from a gauge alone.· Modern Refrigeration and Air Conditioning
Controls
- Transformer loading
- Maximum secondary current is VA divided by secondary volts.· Modern Refrigeration and Air Conditioning
Combustion Air
- Standard method
- 50 cubic feet of room volume per 1,000 Btu/h of total input.· IFGC §304.5.1
- Openings to indoor spaces
- Each of two openings: 1 square inch per 1,000 Btu/h, minimum 100 square inches.· IFGC §304.5.3.1
- Two openings to outdoors
- 1 square inch per 4,000 Btu/h direct or by vertical ducts; 1 square inch per 2,000 Btu/h by horizontal ducts.· IFGC §304.6.1
- One opening to outdoors
- 1 square inch per 3,000 Btu/h, within 12 inches of the top.· IFGC §304.6.2
- Louvers
- Assume 75% free area for metal and 25% for wood when the free area is not known.· IFGC §304.10
Equipment Requirements and Design
- Working space
- A level space at least 30 inches by 30 inches in front of the service side.· IMC §306.1
- Garage ignition sources
- Elevated at least 18 inches above the floor unless the appliance is listed as flammable vapor ignition resistant.· IMC §304.3
- Auxiliary drain pan
- At least 1.5 inches deep and 3 inches larger than the unit.· IMC §307.2.3
HVAC and HVACR Systems
- Cooling tower terms
- Range is entering minus leaving water temperature; approach is leaving water temperature minus entering wet-bulb.· Modern Refrigeration and Air Conditioning
Piping
- Condensate slope and size
- Not less than 1/8 inch per foot; not less than 3/4 inch.· IMC §307.2.1, §307.2.2
- Sediment trap
- Downstream of the appliance shutoff valve, as close to the appliance inlet as practical.· IFGC §408.4
- Gas pressure test
- At least 1.5 times working pressure and not less than 3 psig, using air or an inert gas.· IFGC §406.4
Safety
- Reporting
- Fatality within 8 hours; inpatient hospitalization, amputation or loss of an eye within 24 hours.· 29 CFR 1904.39
- Posting and retention
- Form 300A posted February 1 to April 30; records kept five years.· 29 CFR 1904.32, 1904.33
Service
- Evacuation
- Pull to 500 microns or lower on a micron gauge; a steady rise after isolation means a leak.· Modern Refrigeration and Air Conditioning
- Recovery
- Refrigerant is recovered with certified equipment by a certified technician and never vented.· 40 CFR Part 82, Subpart F
Testing
- Gas leak testing
- Use a noncorrosive leak detection fluid or a gas detector, never a flame.· IFGC §406.5
Ventilation
- Intake separation
- At least 10 feet from hazardous or noxious contaminant sources, with listed exceptions.· IMC §401.4
- Machinery rooms
- Detector, ventilation and door requirements.· IMC §1105
Venting
- Dryer exhaust length
- 35 feet by default, less fitting deductions, unless the dryer manufacturer's instructions allow more.· IMC §504
- Vent connector slope
- Upward at least 1/4 inch per foot.· IFGC §503.10
Now prove you know them
Reading an outline is not the same as recalling it under exam pressure. Drill the free Texas Air Conditioning and Refrigeration Contractor questions to find the areas you keep missing, then sit a full timed mock.
Study aid, not a substitute for the official material — always confirm the current rule with TDLR — ACR Contractor Exams.