Chapter 6 of 14
Combustion Air
Fuel-burning appliances need air for combustion, draft-hood dilution and ventilation. The fuel gas code gives several ways to supply it, each with its own ratio, and the exam expects you to pick the right one and do the arithmetic.
The methods
Indoor air by room volume, indoor air through openings to adjoining spaces, outdoor air through two openings, and outdoor air through one opening. The ratios differ, so read the question for where the air comes from and how it is ducted.
Standard method
50 cubic feet of room volume per 1,000 Btu/h of total input.
IFGC §304.5.1Openings to indoor spaces
Each of two openings: 1 square inch per 1,000 Btu/h, minimum 100 square inches.
IFGC §304.5.3.1Two openings to outdoors
1 square inch per 4,000 Btu/h direct or by vertical ducts; 1 square inch per 2,000 Btu/h by horizontal ducts.
IFGC §304.6.1One opening to outdoors
1 square inch per 3,000 Btu/h, within 12 inches of the top.
IFGC §304.6.2Louvers
Assume 75% free area for metal and 25% for wood when the free area is not known.
IFGC §304.10