Texas Journeyman Electrician Exam Practice Test

Practice stays free. The full Texas Journeyman Electrician (TDLR / PSI, 2026 NEC) study guide is the material itself, taught start to finish — a downloadable PDF + EPUB you keep.
| Administering body | Texas Department of Licensing and Regulation (TDLR) — exam delivered by PSI |
|---|---|
| Questions | 85 questions (80 scored, 5 unscored pretest) |
| Time limit | 240 minutes |
| Passing score | 70% |
| Fees |
|
| Languages offered | English · Spanish |
Frequently asked questions
How many Texas Journeyman Electrician Exam practice questions are here?+
444 original Texas Journeyman Electrician Exam practice questions with explanations. Free, no signup.
What is the Texas Journeyman Electrician Exam exam like?+
About 85 questions, 240 minutes, and you need 70% to pass. Practice by topic here, then take a timed mock exam to gauge readiness.
Are these the real exam questions?+
No. Every question is 100% original, written from public primary sources with explanations. We never copy real exam questions or paid prep material.
What languages are the Texas Journeyman Electrician Exam practice questions in?+
English. The Texas Journeyman Electrician Exam practice questions here have not been translated yet.
Is there a study guide for the Texas Journeyman Electrician Exam?+
Yes. PrepPass sells Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC), a PDF + EPUB download, $14.99 one-time; the practice on this page stays free without it. See the study guide →
Sample practice questions
A few real questions from this free bank, with full explanations. Use the practice tool above for the whole set.
- 1. Definitions, Theory, and Plans
What is the line current of a balanced 45 kVA, three-phase, 208-volt load?
- a.216 amperes
- b.125 amperes
- c.72 amperes
- d.144 amperes
Answer: b
Explanation: For a three-phase load, I = VA / (1.732 x E) = 45,000 / (1.732 x 208) = 45,000 / 360.3, or about 125 A. The 216-ampere answer divides by the voltage alone as if the load were single-phase, 72 amperes divides by three times the voltage, and 144 amperes does not follow from the formula.
- 2. Definitions, Theory, and Plans
On a 4-wire, delta-connected system where the midpoint of one phase winding is grounded, the conductor with the higher voltage to ground must be durably and permanently marked with what color?
- a.Orange
- b.Purple
- c.Yellow
- d.Red
Answer: a
Explanation: Section 110.15 requires the high leg to be durably marked orange, by an outer finish or by other effective means that leave orange visible at all splices and terminations, at each point where a connection is made if the grounded conductor is also present. The other colors are common field choices for phase conductors but are not the color this section names.
Source: 2026 NEC §110.15
- 3. Electrical Services, Service Equipment, and Separately Derived Systems
A grounding electrode conductor connection to a ground rod buried in the earth must use what kind of fitting?
- a.A connector or clamp listed for direct burial in soil
- b.A tape-wrapped mechanical lug
- c.A solder joint
- d.Any indoor split-bolt connector
Answer: a
Explanation: A clamp or fitting used to connect to a rod, pipe or other electrode that is buried must be listed for direct soil burial. See NEC 250.70(A)(2).
Source: 2026 NEC §250.70(A)(2)
- 4. Electrical Feeders
A dwelling has a combined general lighting, small-appliance and laundry load of 3,600 volt-amperes. Applying the standard demand factors, what is the demand load?
- a.3,600 volt-amperes
- b.3,150 volt-amperes
- c.3,210 volt-amperes
- d.1,260 volt-amperes
Answer: c
Explanation: The first 3,000 VA is taken at 100 percent and the remainder at 35 percent: 3,000 + (600 x 0.35) = 3,210 VA. See NEC Table 120.45.
Source: 2026 NEC Table 120.45
- 5. Branch Circuits and Conductors
Using the standard method, what is the general lighting load for a 2,500-square-foot dwelling before demand factors?
- a.3,750 volt-amperes
- b.7,500 volt-amperes
- c.5,000 volt-amperes
- d.6,250 volt-amperes
Answer: c
Explanation: Under the standard method, dwelling general lighting is calculated at 2 volt-amperes per square foot: 2,500 x 2 = 5,000 VA. The 7,500 VA answer uses 3 volt-amperes per square foot, which is not the current value. See NEC 120.41.
Source: 2026 NEC §120.41
- 6. Electrical Wiring Methods and Electrical Materials
Conductors installed in an underground raceway in a wet location must have which characteristic?
- a.A nylon jacket, which by itself qualifies the conductor for wet locations
- b.Any thermoplastic insulation, since the raceway keeps water out
- c.Insulation rated 90 degrees C, regardless of wet-location listing
- d.Insulation listed for use in wet locations, such as THWN or THWN-2
Answer: d
Explanation: Raceways in underground and other wet locations are considered wet inside, so the conductors must carry a wet-location listing such as THWN, THWN-2 or XHHW. The W in the type designation is what matters; plain THHN without the dual THWN-2 marking is a dry- and damp-location conductor, and a temperature rating or nylon jacket alone does not confer a wet-location listing.
Source: 2026 NEC §310.10(C)
- 7. Electrical Equipment and Devices
A single hermetic refrigerant motor-compressor with a rated-load current of 22 amperes is supplied alone, and no larger branch-circuit selection current is marked. What minimum conductor ampacity is required?
- a.30 amperes
- b.22 amperes
- c.38.5 amperes
- d.27.5 amperes
Answer: d
Explanation: Branch-circuit conductors for a single motor-compressor must be at least 125 percent of the rated-load or branch-circuit selection current: 22 x 1.25 = 27.5 A, which calls for 10 AWG copper. See NEC 440.32.
Source: 2026 NEC §440.32
- 8. Motors and Generators
On a feeder supplying several motors, 125 percent is applied to which motor's full-load current?
- a.The highest-rated motor, meaning the one with the largest full-load current
- b.The smallest motor, meaning the one with the lowest full-load current
- c.Every motor on the feeder, each at 125 percent of its full-load current
- d.The motor with the highest horsepower nameplate regardless of current
Answer: a
Explanation: Feeder conductors are sized at 125 percent of the largest motor full-load current plus the sum of the full-load currents of the other motors, and the largest motor is the one with the highest rated full-load current per 430.17. Applying 125 percent to every motor over-sizes the feeder.
Source: 2026 NEC §430.24
- 9. Electrical Control Devices and Disconnecting Means
A motor disconnecting means has a current rating of 100 A. Applying the general current-rating rule for motor circuits rated 1000 volts or less, which of these is the highest motor full-load current it can serve?
- a.71 A
- b.77 A
- c.83 A
- d.88 A
Answer: c
Explanation: Section 430.110(A) requires the disconnect rating to be at least 115 percent of the motor full-load current. Working backward, 100 A / 1.15 = 86.96 A, so the motor current cannot exceed about 87 A. Check: 83 A x 1.15 = 95.45 A, which fits, while 88 A x 1.15 = 101.2 A, which is over 100 A.
Source: 2026 NEC §430.110(A)
- 10. Special Occupancies, Equipment, and Conditions
Service equipment for a floating dock must be located on land. What is the closest horizontal distance it may be to the structure it serves?
- a.10 ft
- b.20 ft
- c.50 ft
- d.5 ft
Answer: d
Explanation: The service equipment sits on land, adjacent to the structure, but no closer than 5 ft horizontally and not on or in the structure itself. The larger distances are more than the rule requires. See 555.17.
Source: 2026 NEC §555.17