Chapter 3 of 9

Plumbing Fixtures

Fixture questions ask for clearances, outlet sizes, shower dimensions and the temperature limits on bathing fixtures.

Clearances and sizes

A water closet, lavatory, urinal or bidet needs 15 inches from its centre to a side obstruction, 30 inches centre to centre and 21 inches in front. Waste outlets are 1-1/4 inches for lavatories, 1-1/2 inches for sinks, tubs and showers, and 2 inches for floor drains.

Fixture clearances
15 inches to the side, 30 inches centre to centre, 21 inches in front.
IPC §405.3.1
Shower size
900 square inches and 30 inches minimum dimension; or 25 inches with 1,300 square inches; 22-inch opening.
IPC §417.4
Shower liner
Turned up 2 inches above the threshold; sloped 1/4 inch per foot.
IPC §417.5.2

Scald protection and public fixtures

Shower valves are pressure-balancing or thermostatic and limited to 120°F. Tub fillers are limited to 120°F by an ASSE 1070 device. Public lavatories get tempered water through an ASSE 1070 device. Public water closets have elongated bowls and open-front seats.

Shower valves
ASSE 1016 type, 120°F maximum.
IPC §424.3
Urinal substitution
Up to 67% of water closets in assembly and educational occupancies; 50% elsewhere.
IPC §419.2
Toilet room location
Within 500 feet of travel and one story up or down.
IPC §403.3.3