Texas Journeyman Plumber Exam — All Questions
30 questions
A water closet is set beside a bathtub. Under IPC §405.3.1, the centre of the bowl must be at least how far from the side of the tub?
- a.15 inches✓
- b.12 inches
- c.18 inches
- d.21 inches
A water closet, urinal, lavatory or bidet is set with its centre at least 15 inches from any side wall, partition, vanity or other obstruction. Twelve inches is too tight, 18 inches is an accessibility figure, and 21 inches is the front clearance.IPC §405.3.1
Two water closets are installed side by side in a toilet room with no partition between them. The minimum centre-to-centre spacing under IPC §405.3.1 is:
- a.24 inches
- b.42 inches
- c.36 inches
- d.30 inches✓
Adjacent fixtures are spaced at least 30 inches centre to centre, which is twice the 15-inch side clearance. Twenty-four inches is too close; 36 and 42 inches exceed the minimum.IPC §405.3.1
The minimum clear space in front of a water closet, measured to a wall or door under IPC §405.3.1, is:
- a.36 inches
- b.21 inches✓
- c.15 inches
- d.30 inches
At least 21 inches of clearance is required in front of a water closet, urinal, lavatory or bidet. Fifteen inches is the side clearance from the centreline and 30 inches is the centre-to-centre spacing.IPC §405.3.1
Under IPC §405.5, where a lavatory meets the wall it is mounted on, the joint must be:
- a.Covered with a wood trim strip
- b.Left open by 1/4 inch for cleaning
- c.Filled with dry cement grout only
- d.Sealed so that it is watertight✓
Joints formed where fixtures contact walls or floors are sealed watertight so that water and soil cannot collect behind the fixture. An open gap or wood trim harbours moisture, and dry grout is not a seal.IPC §405.5
A fixture with concealed slip-joint connections is being installed. Under IPC §405.8, the plumber must provide:
- a.A second trap downstream in case the slip joint has to be taken apart later
- b.A floor drain directly under the trap in case the connection leaks
- c.An access panel or utility space at least 12 inches in its smallest dimension✓
- d.A soldered cap over each slip nut so that it cannot loosen in service
Fixtures with concealed slip-joint connections need an access panel or utility space at least 12 inches in its smallest dimension so the joints can be inspected and repaired. Capping the nuts defeats the joint, and a floor drain or a second trap is not a substitute for access.IPC §405.8
A residential clothes washer drains into a standpipe. Under IPC §406.2, the washer's waste must discharge through:
- a.A vacuum breaker
- b.An air break✓
- c.A direct connection
- d.A check valve
Automatic clothes washers discharge through an air break into a standpipe or other receptor. A direct connection would let sewage back into the machine, and check valves and vacuum breakers are not the method the fixture section names for the drain side.IPC §406.2
Under IPC §407.2, the waste outlet and overflow of a bathtub must be at least what diameter?
- a.2 inches
- b.3 inches
- c.1-1/2 inches✓
- d.1-1/4 inches
Bathtubs have waste outlets and overflows of at least 1-1/2 inches, and the waste is fitted with a stopper. An outlet of 1-1/4 inches is the lavatory minimum; 2 and 3 inches are larger than required.IPC §407.2
Under IPC §416, the waste outlet of a lavatory must be at least what diameter?
- a.1-1/4 inches✓
- b.1 inch
- c.2 inches
- d.1-1/2 inches
Lavatories have waste outlets not less than 1-1/4 inches in diameter. One inch is too small, 1-1/2 inches is the minimum for sinks, tubs and showers, and 2 inches is not required.IPC §416.3
A shower compartment is built to the standard minimum in IPC §417.4. Its interior must be at least:
- a.900 square inches, with no dimension under 30 inches✓
- b.720 square inches, with no dimension under 24 inches
- c.1,024 square inches, with no dimension under 32 inches
- d.1,296 square inches, with no dimension under 36 inches
The usual minimum is 900 square inches of interior cross-section and 30 inches in the least dimension. A narrower 25-inch dimension is allowed only where the area is at least 1,300 square inches. The other pairs are not code minimums.IPC §417.4
IPC §417.4 allows a shower compartment with a minimum dimension of 25 inches where its interior cross-sectional area is at least:
- a.1,100 square inches
- b.900 square inches
- c.1,000 square inches
- d.1,300 square inches✓
The exception permits a 25-inch minimum dimension only if the compartment has at least 1,300 square inches of area. Nine hundred square inches is the standard minimum that goes with the 30-inch dimension.IPC §417.4
Under IPC §417.4.2, the access and egress opening of a shower compartment must have a clear width of at least:
- a.18 inches
- b.28 inches
- c.22 inches✓
- d.32 inches
Shower compartment openings must give a clear, unobstructed finished width of at least 22 inches. Eighteen inches is too narrow, and 28 and 32 inches exceed the plumbing code minimum (accessible showers follow other rules).IPC (2018) §421.4.2
A site-built shower pan liner is being installed on a wood subfloor. Under IPC §417.5.2, the liner must turn up on all sides to at least:
- a.1 inch above the finished threshold
- b.6 inches above the shower head outlet
- c.2 inches above the finished threshold✓
- d.2 inches below the finished threshold
The lining turns up on all sides at least 2 inches above the finished threshold level and is fastened to an approved backing. One inch is too little, a liner that stops below the threshold lets water over the top, and the shower head height is unrelated.IPC §417.5.2
Under IPC §417.5.2, the surface that supports a sheet-applied shower liner is sloped toward the drain at:
- a.1/16 inch per foot
- b.1/8 inch per foot
- c.1/4 inch per foot✓
- d.1 inch per foot
The liner is pitched 1/4 inch per foot to weep holes in the drain so that water under the tile bed drains away. Flatter slopes leave water standing on the liner, and 1 inch per foot is not required.IPC §417.5.2
A new individual shower valve is installed in a house. Under IPC §424.3 it must be a balanced-pressure, thermostatic or combination valve that limits water temperature to no more than:
- a.105°F
- b.130°F
- c.140°F
- d.120°F✓
Individual shower and tub-shower valves conform to ASSE 1016 or the equivalent ASME/CSA standard and have a limit stop adjusted to a maximum of 120°F. Water at 130 to 140°F scalds in seconds; 105°F is below the limit the code sets.IPC §424.3
A bathtub with no shower is supplied by a two-handle tub filler. Under IPC §424.5, hot water to the tub must be limited to 120°F by:
- a.A temperature-limiting device conforming to ASSE 1070✓
- b.An atmospheric vacuum breaker on the tub spout
- c.A pressure-reducing valve on the hot water branch
- d.The thermostat setting on the storage water heater alone
Bathtub and whirlpool tub valves need a water-temperature limiting device to ASSE 1070 (or the equivalent CSA standard), unless a compliant combination tub-shower valve does the job. A water heater thermostat is not an acceptable control, and pressure regulators and vacuum breakers do not limit temperature.IPC §424.5
Under IPC §419.2, in an assembly or educational occupancy, urinals may be substituted for what share of the required water closets?
- a.Not more than 67 percent✓
- b.Not more than 25 percent
- c.Not more than 50 percent
- d.Not more than 90 percent
Urinals may replace up to 67 percent of the required water closets in assembly and educational occupancies, and up to 50 percent in other occupancies. Twenty-five and 90 percent are not code figures.IPC §419.2
Water closets in a public restroom must, under IPC §420, have:
- a.Round bowls with closed-front seats
- b.Elongated bowls with closed-front seats
- c.Elongated bowls with open-front seats✓
- d.Round bowls with open-front seats
Water closets for public or employee use have elongated bowls, and their seats are of the hinged open-front type. Round bowls and closed-front seats are for dwelling use.IPC §§420.2, 420.3
Under IPC §410, a drinking fountain may NOT be installed in:
- a.A public restroom✓
- b.A school corridor
- c.An office break room
- d.A gymnasium lobby
Drinking fountains, water coolers and water dispensers are not permitted in public restrooms. Corridors, break rooms and lobbies are ordinary locations.IPC §410.5
Under IPC §412, a floor drain must have a removable strainer and a drain outlet of at least:
- a.2 inches in diameter✓
- b.3 inches in diameter
- c.1-1/2 inches in diameter
- d.1-1/4 inches in diameter
Floor drains have removable strainers and waste outlets not less than 2 inches in diameter. The smaller sizes are for lavatories and sinks, and 3 inches is more than the minimum.IPC §412.3
A commercial food waste disposer is installed in a restaurant kitchen. Under IPC §413, the disposer must be provided with:
- a.A supply of cold water✓
- b.A separate 4-inch vent stack
- c.A supply of hot water only
- d.A direct tie to a grease interceptor
Food waste disposers need an adequate supply of cold water so that the ground waste is carried away and grease stays solid enough to flush through. Hot water liquefies grease, and the fixture section does not call for a dedicated vent stack.IPC §413.4
Under IPC §413.1, a domestic food waste disposer connects to a drain of at least:
- a.2 inches
- b.1-1/4 inches
- c.1-1/2 inches✓
- d.3 inches
Domestic disposers connect to a drain not less than 1-1/2 inches in diameter; commercial units need at least 2 inches. An outlet of 1-1/4 inches is too small for ground food waste.IPC §413.1
A whirlpool bathtub is installed with its circulation pump 3 feet from the access opening. Under IPC §421.5, the access opening must be at least:
- a.18 inches by 18 inches✓
- b.12 inches by 12 inches
- c.24 inches by 30 inches
- d.8 inches by 8 inches
A 12-by-12-inch opening is enough where the pump is within 2 feet of it; where the pump is farther than 2 feet, the opening is at least 18 by 18 inches. The other sizes are not the code dimensions.IPC (2018) §426.5
Under IPC §403.3.3, required public toilet facilities in a building (other than a mall) must be within a travel distance of:
- a.500 feet, and not more than one story above or below the space served✓
- b.300 feet, and not more than two stories above or below the space
- c.100 feet, and on the same story as the space that is being served
- d.1,000 feet, and anywhere inside the building that is being served
Toilet facilities are located not more than one story above or below the space needing them, with a path of travel no longer than 500 feet. The other distances are not the general rule.IPC §403.3.3
Under IPC §403.2, separate toilet facilities for each sex are NOT required in a mercantile occupancy (a shop) where the maximum occupant load is:
- a.100 or fewer✓
- b.150 or fewer
- c.300 or fewer
- d.200 or fewer
Separate facilities are not required in dwelling units, in structures with a total occupant load of 15 or fewer, or in mercantile occupancies with an occupant load of 100 or fewer. The larger loads are not exceptions in the section.IPC §403.2
A flushometer valve is installed on a wall-hung urinal. Under IPC §425.2, the valve must be equipped with:
- a.A swing check valve
- b.A pressure-relief valve
- c.A thermostatic mixing valve
- d.An approved vacuum breaker✓
Flushometer valves and tanks have an approved vacuum breaker (backflow preventer) because the valve outlet sits below the fixture's flood rim. Relief, mixing and check valves do not protect against backsiphonage in this application.IPC §§425.2, 608.15.4
An emergency eyewash station is installed in a plating shop. Under IPC §411, the station must be installed in accordance with:
- a.ASSE 1016
- b.ISEA Z358.1✓
- c.NSF 61
- d.ASME A112.19.2
Emergency showers and eyewash stations conform to and are installed under ISEA Z358.1; a drain is not required for them. ASSE 1016 covers shower valves, NSF 61 covers drinking water components, and A112.19.2 covers ceramic fixtures.IPC §411.1
A domestic dishwasher drains to a kitchen sink tailpiece. Under IPC §802.1.6 (referenced from §409), the discharge hose must:
- a.Run level along the cabinet floor and connect below the trap weir
- b.Connect to the vent pipe above the flood rim of the kitchen sink
- c.Rise and be secured to the underside of the counter before connecting✓
- d.Drop into an open standpipe that is installed without a trap
The dishwasher waste line rises and is securely fastened to the underside of the sink rim or counter before connecting to a wye tailpiece or disposer, so sink waste cannot run back into the machine. A low level run, a vent connection or an untrapped standpipe would each be a violation.IPC §§409.2, 802.1.6
Public hand-washing lavatories must be supplied with tempered water under IPC §416.5 through a device conforming to:
- a.ASSE 1010
- b.ASSE 1001
- c.ASSE 1070✓
- d.ASSE 1013
Tempered water at public lavatories is delivered through a temperature-limiting device to ASSE 1070 or the equivalent CSA standard. ASSE 1013 is a reduced pressure backflow assembly, 1010 a water hammer arrester, and 1001 an atmospheric vacuum breaker.IPC §416.5
Under IPC §418, the waste outlet of a kitchen sink must be at least:
- a.1-1/2 inches in diameter✓
- b.2 inches in diameter
- c.1-1/4 inches in diameter
- d.2-1/2 inches in diameter
Sinks have waste outlets not less than 1-1/2 inches in diameter, with a strainer or crossbar to restrict the opening. The smaller size applies to lavatories; larger outlets are not required.IPC §418.2
A water closet is set on a floor flange. Under IPC §405.4, the flange must be:
- a.Set 1 inch below the finished floor and grouted to level
- b.Glued to the finished floor tile with a silicone sealant
- c.Left loose so that it can move with the closet bend below
- d.Secured to the structure with corrosion-resistant fasteners✓
Floor-outlet fixtures connect to a flange fastened to the building structure with corrosion-resistant screws or bolts, and the closet is sealed to the flange with a gasket or setting compound. A loose or recessed flange lets the bowl rock and the seal fail.IPC §405.4