Fuel Gas

A house gas system is pressure tested before the meter is set. Under IFGC §406.4.1, the test pressure must be at least 1-1/2 times the proposed maximum working pressure and never less than:

  • a.10 psig
  • b.60 psig
  • c.1 psig
  • d.3 psig✓

The test pressure is not less than one and one-half times the maximum working pressure and not less than 3 psig, whatever the design pressure. Many Texas cities amend this upward, so check the local ordinance.IFGC §406.4.1

Fuel Gas

Under IFGC §406.4.2, the pressure test of gas piping in a single-family dwelling is held for at least:

  • a.60 minutes
  • b.24 hours
  • c.2 minutes
  • d.10 minutes✓

The test duration is not less than 10 minutes for the piping in a one-family dwelling; larger systems are tested for longer based on volume. Two minutes will not show a small leak on a gauge.IFGC §406.4.2

Fuel Gas

Which medium may NOT be used to pressure test fuel gas piping under IFGC §406.1.2?

  • a.Nitrogen
  • b.Air
  • c.Carbon dioxide
  • d.Oxygen✓

The test medium is air, nitrogen, carbon dioxide or an inert gas. Oxygen is never used, because it reacts violently with oil and thread compound in the pipe.IFGC §406.1.2

Fuel Gas

Under IFGC §404.12, underground gas piping must be buried with a cover of at least:

  • a.36 inches
  • b.12 inches✓
  • c.24 inches
  • d.6 inches

Underground piping systems are installed at a minimum depth of 12 inches below grade; individual lines to outdoor lights, grills and similar appliances may be at 8 inches where protected from damage. Local amendments are often deeper.IFGC §404.12

Fuel Gas

Polyethylene plastic gas pipe may be installed, under IFGC §404.17:

  • a.Outdoors and underground only✓
  • b.Indoors in concealed walls only
  • c.Above ground on outdoor walls only
  • d.Anywhere steel pipe is permitted

Plastic pipe is installed outdoors, underground only, with limited exceptions such as anodeless risers. It is not run inside or under buildings or above ground, where it is exposed to heat, damage and sunlight.IFGC §404.17.1

Fuel Gas

A polyethylene gas yard line is buried from the meter to a pool heater. Under IFGC §404.17.3, the plumber must also install:

  • a.A magnesium anode, at least 5 pounds, at each end of the pipe run
  • b.A galvanized steel sleeve, two pipe sizes larger, for the full length
  • c.A red warning tape, at least 6 inches wide, laid on top of the pipe
  • d.A yellow insulated copper tracer wire, at least 18 AWG, beside the pipe✓

Plastic pipe cannot be found with a metal locator, so an insulated copper tracer wire (yellow, not smaller than 18 AWG) or other approved conductor is installed adjacent to it and brought above ground at each end. Anodes protect steel, not plastic.IFGC §404.17.3

Fuel Gas

Under IFGC §404.3, gas piping may NOT be installed in or through:

  • a.A ventilated crawl space beneath a pier-and-beam dwelling
  • b.A clothes chute, chimney, gas vent, dumbwaiter or elevator shaft✓
  • c.A wall cavity between the studs of an interior partition
  • d.An attic space above the ceiling insulation of a one-story dwelling

Piping is prohibited in or through ducted supply, return or exhaust air ducts, clothes chutes, chimneys or gas vents, dumbwaiters and elevator shafts. Attics, crawl spaces and stud cavities are permitted with proper protection.IFGC §404.3

Fuel Gas

Which fitting may be used in a concealed location in a gas piping system under IFGC §404.5?

  • a.A compression coupling
  • b.A threaded elbow✓
  • c.A union
  • d.A bushing

Concealed gas piping may contain threaded elbows, tees and couplings, brazed or welded fittings and listed fittings; unions, tubing fittings, right-and-left couplings, bushings, swing joints and compression couplings are not allowed where concealed.IFGC §404.5

Fuel Gas

Corrugated stainless steel tubing (CSST) gas piping runs through a bored hole in a stud less than 1-1/2 inches from the face of the stud. Under the IFGC, the piping must be protected by:

  • a.Steel shield plates that extend at least 4 inches beyond each side of the member✓
  • b.A wrap of pipe insulation at least 1/2 inch thick where it passes the member
  • c.Shield plates are not needed, because the rule applies only to water piping
  • d.Plastic sleeves that extend at least 2 inches beyond each side of the member

Where gas piping other than black or galvanized steel is installed less than 1-1/2 inches from the edge of a framing member, steel shield plates at least 0.0575 inch thick cover the area and extend 4 inches beyond the member on each side. Sleeves and insulation will not stop a nail.IFGC (2018) §404.7.1

Fuel Gas

Under IFGC §404.9, gas piping installed outdoors above ground must be elevated above the ground or roof surface by at least:

  • a.18-1/2 inches
  • b.1-1/2 inches
  • c.3-1/2 inches✓
  • d.12 inches

Above-ground outdoor piping is securely supported and elevated not less than 3-1/2 inches above ground and above roof surfaces, and protected against corrosion. The other heights are not the code value.IFGC §404.9

Fuel Gas

Under IFGC §404.14, gas piping may be installed underground beneath a building only where it is:

  • a.Coated with coal tar enamel and buried at least 12 inches deep
  • b.Made of copper tubing with brazed joints and no fittings at all
  • c.Encased in an approved conduit that is designed for the purpose✓
  • d.Laid in the same trench as the building's water service pipe

Piping is not installed in the ground beneath buildings unless it is in a conduit of wrought iron, plastic pipe, steel pipe or other approved material, sealed at the building and vented or terminated outdoors as the section describes. Coatings and brazed copper alone do not satisfy the section.IFGC §404.14

Fuel Gas

Corrugated stainless steel tubing (CSST) is installed in a house. Under IFGC §310.1.1, the CSST gas system must be bonded to the electrical service grounding electrode system with a conductor not smaller than:

  • a.6 AWG copper✓
  • b.2 AWG copper
  • c.14 AWG copper
  • d.10 AWG copper

CSST systems are bonded with a bonding jumper of not smaller than 6 AWG copper, connected at a point on rigid pipe or a fitting, so that lightning energy has a path other than arcing through the thin tubing wall. Smaller conductors are not accepted.IFGC §310.1.1

Fuel Gas

Under IFGC §411.1.3.1, a listed appliance connector to a gas range may not be longer than:

  • a.6 feet✓
  • b.10 feet
  • c.15 feet
  • d.3 feet

Appliance connectors are limited to an overall length of 6 feet and are measured along the centreline; only one connector is used per appliance. Rigid pipe is used where more distance is needed.IFGC §411.1.3.1

Fuel Gas

Under IFGC §411.1.3.3, an appliance connector may NOT:

  • a.Be installed in the same room as the appliance that it serves
  • b.Be concealed in, or pass through, a wall, floor, partition or ceiling✓
  • c.Be connected to the outlet of the appliance shutoff valve
  • d.Be made of corrugated stainless steel with a protective polymer coating

Connectors are not concealed within or extended through walls, floors, partitions, ceilings or appliance housings, apart from limited exceptions for listed fittings. The connector is located entirely in the same room, downstream of the shutoff valve.IFGC §411.1.3.3

Fuel Gas

Horizontal 3/4-inch steel gas pipe is supported, under IFGC §415.1, at intervals of no more than:

  • a.20 feet
  • b.4 feet
  • c.8 feet✓
  • d.12 feet

Steel pipe of 1/2 inch is supported every 6 feet, 3/4 inch and 1 inch every 8 feet, and 1-1/4 inch and larger horizontal pipe every 10 feet. The other spacings are not the table values.IFGC §415.1

Fuel Gas

A gas furnace is rated at 80,000 Btu/h, and the natural gas supplied has a heating value of 1,000 Btu per cubic foot. The gas demand of the furnace is:

  • a.800 cubic feet per hour
  • b.8,000 cubic feet per hour
  • c.80 cubic feet per hour✓
  • d.8 cubic feet per hour

Demand in cubic feet per hour equals input in Btu/h divided by the heating value per cubic foot: 80,000 ÷ 1,000 = 80 cfh. Pipe sizing tables are entered with this demand and the pipe length.IFGC §402.2

Fuel Gas

When sizing a gas piping system by the longest length method of IFGC §402.4.1, the length used for every section of pipe is:

  • a.The actual length of each individual section taken by itself
  • b.The distance from the point of delivery to the most remote outlet✓
  • c.The distance from the point of delivery to the nearest outlet
  • d.The total length of all the pipe in the system added together

The longest length method uses the length from the meter or regulator to the most remote outlet for sizing every section, with the load each section carries. The branch length method treats branches differently; the nearest outlet or total pipe is never the basis.IFGC §402.4.1

Fuel Gas

Natural gas has a specific gravity of about 0.60 and propane about 1.50. What does this mean for a leak in a basement?

  • a.Both gases settle in low areas, because both are heavier than air
  • b.Natural gas tends to rise; propane tends to settle in low areas✓
  • c.Natural gas tends to settle; propane tends to rise to the ceiling
  • d.Both gases rise to the ceiling, because both are lighter than air

Specific gravity compares a gas with air at 1.0. Natural gas is lighter and rises; propane is about one and a half times as heavy as air and pools in pits and basements, which is why LP-gas appliances face added restrictions below grade.IFGC §202

Fuel Gas

Under IFGC §402.6, the operating pressure of gas piping inside a building is generally limited to:

  • a.2 psig, with no exceptions for any type of building
  • b.5 psig, unless one of the listed conditions is met✓
  • c.60 psig, where the piping has welded joints
  • d.20 psig, unless the building is a dwelling unit

The maximum design operating pressure for piping inside buildings is 5 psig unless listed conditions apply, such as welded or brazed piping, a ventilated chase, or industrial occupancies. The other pressures are not the general limit.IFGC §402.6

Fuel Gas

Brazing filler used on copper gas tubing must, under IFGC §403.10.2, have a melting point above:

  • a.2,000°F
  • b.450°F
  • c.700°F
  • d.1,000°F✓

Brazing alloys for gas tubing joints melt above 1,000°F and may not contain more than 0.05 percent phosphorus. Soft solders that melt at lower temperatures are not permitted on gas tubing, since they fail early in a fire.IFGC §403.10.2

Fuel Gas

Exposed gas piping, other than steel pipe, must be identified under IFGC §401.5 by:

  • a.A band of yellow paint at the gas meter outlet only
  • b.A stamped brass tag on the appliance shutoff valve only
  • c.A red label marked "Danger" at intervals of 25 feet or less
  • d.A yellow label marked "Gas" at intervals of 5 feet or less✓

Exposed piping other than steel is identified by a yellow label marked "Gas" in black letters, spaced at intervals not exceeding 5 feet; pipe in the same room as the appliance served is excepted. A tag at one valve or the meter is not enough.IFGC §401.5

Fuel Gas

Why does IFGC §408.2 require gas piping to be sloped or fitted with drips where "wet" gas is supplied?

  • a.So that the gas reaches the most distant appliance at a higher pressure
  • b.So that air can be bled from the high points of the pipe during the test
  • c.So that the pipe can expand along its length when it is heated by the sun
  • d.So that condensate drains to a collection point and does not block the pipe✓

Where wet gas exists, a drip is provided at any point where condensate could collect, so liquid does not block the line or reach appliance controls. Slope has no effect on purging, expansion or delivery pressure.IFGC §408.2

Fuel Gas

A sediment trap is NOT required by IFGC §408.4 at which appliance?

  • a.A gas boiler
  • b.A gas range✓
  • c.A gas water heater
  • d.A gas furnace

Sediment traps are required at appliances such as furnaces, water heaters and boilers, but not at illuminating appliances, ranges, clothes dryers, decorative appliances, gas fireplaces and outdoor grills, which are manually operated or watched.IFGC §408.4

Fuel Gas

Before gas is turned on to a new piping system, IFGC §406.6.2 requires the installer to check that:

  • a.All outlets are closed, capped or plugged✓
  • b.All unions are loosened one quarter turn
  • c.All appliances are lit and the burners adjusted
  • d.All regulators are removed from the system

Before gas is introduced, the system is checked to be sure there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped. Immediately after turn-on, a leak check is made.IFGC §406.6.2

Fuel Gas

A branch gas outlet is left for a future dryer. Under IFGC §404.15, the outlet must be:

  • a.Closed with a shutoff valve only
  • b.Crimped flat and bent over
  • c.Capped or plugged gastight✓
  • d.Left open with a warning tag

Gas outlets that do not connect to appliances are capped or plugged gastight; a valve alone can be opened by accident. An open or crimped end is never acceptable.IFGC §404.15

Fuel Gas

Under IFGC §409.1.3, gas shutoff valves must be located:

  • a.Where they are accessible and protected from damage✓
  • b.Inside the appliance casing, behind the burner door
  • c.Above a ceiling that has no access panel
  • d.Behind the appliance, against the back wall

Shutoff valves are located in places that provide access for operation and are installed so as to be protected from damage. A valve hidden in a casing, above a closed ceiling or behind an appliance cannot be reached in an emergency.IFGC §409.1.3

Fuel Gas

A line pressure regulator is installed indoors on a 2 psi gas system. Under IFGC §410.3, the regulator must be:

  • a.Sealed at its vent opening so that no gas can escape indoors
  • b.Vented into the return air plenum of the nearest furnace
  • c.Vented to the outdoors, or fitted with a listed vent-limiting device✓
  • d.Vented into the appliance vent connector just above the draft hood

Regulators that need a vent are vented directly outdoors with an independent vent, or equipped with a listed leak-limiting device. Plugging the vent stops the regulator working, and venting into a flue or plenum is prohibited.IFGC §410.3

Fuel Gas

In Texas, a licensed plumber who installs piping for liquefied petroleum gas must also comply with the licensing rules of:

  • a.The Texas Commission on Environmental Quality
  • b.The Texas Department of Insurance
  • c.The Railroad Commission of Texas✓
  • d.The Public Utility Commission of Texas

LP-gas activities are regulated by the Railroad Commission of Texas under the Natural Resources Code and its LP-Gas Safety Rules; the Plumbing License Law coordinates with that programme. The other agencies do not license LP-gas installers.Tex. Occ. Code §1301.055; 22 TAC §367.6

Fuel Gas

Copper tubing may not be used for fuel gas under IFGC §403.4.3 where the gas contains more than an average of:

  • a.3.0 percent of nitrogen measured by volume of gas
  • b.3.0 grains of water vapour per 100 standard cubic feet
  • c.0.3 percent of carbon dioxide measured by the volume of gas
  • d.0.3 grains of hydrogen sulfide per 100 standard cubic feet✓

Copper and copper alloy tubing are not used where the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 standard cubic feet, because the sulfur compounds corrode copper and flake into controls.IFGC §403.4.3

Fuel Gas

A typical natural gas appliance in a dwelling is designed for a supply pressure, in inches of water column, of about:

  • a.70 inches w.c., with propane appliances at about 110 inches w.c.
  • b.7 inches w.c., with propane appliances at about 11 inches w.c.✓
  • c.28 inches w.c., with propane appliances at about 56 inches w.c.
  • d.1 inch w.c., with propane appliances at about 2 inches w.c.

Low-pressure natural gas systems deliver roughly 7 inches of water column (about 1/4 psi) to appliances; LP-gas appliances run at about 11 inches. One psi equals about 27.7 inches of water column, so the larger figures would be several psi.IFGC §402.4