Texas Journeyman Plumber Exam — All Questions
20 questions
Under IPC §1002.1, the vertical distance from a fixture outlet to the trap weir may not exceed:
- a.12 inches
- b.36 inches
- c.48 inches
- d.24 inches✓
The tailpiece length from fixture outlet to trap weir is limited to 24 inches, because falling water gains enough velocity over a longer drop to siphon the trap. The horizontal offset is limited to 30 inches.IPC §1002.1
Under IPC §1002.4, a fixture trap must have a liquid seal of:
- a.At least 1 inch and not more than 2 inches
- b.At least 4 inches and not more than 8 inches
- c.At least 2 inches and not more than 4 inches✓
- d.At least 6 inches and not more than 12 inches
Trap seals are not less than 2 inches and not more than 4 inches, unless a deeper seal is needed for a special design. A shallow seal evaporates or blows out; an overly deep seal slows flow and collects solids.IPC §1002.4
Which trap is prohibited by IPC §1002.3?
- a.A bell trap✓
- b.An integral water closet trap
- c.A deep-seal P-trap
- d.A P-trap
Prohibited traps include bell traps, S-traps, crown-vented traps, drum traps, traps that depend on moving parts to hold the seal, and separate fixture traps with interior partitions. P-traps and integral traps are the approved types.IPC §1002.3
A plumber finds a lavatory drained through an S-trap that drops straight through the floor. The S-trap is prohibited because it:
- a.Cannot be taken apart to clear a stoppage
- b.Holds too much water and slows the fixture drain
- c.Needs a cleanout that the floor would cover
- d.Siphons its own seal when the fixture discharges✓
The downstream leg of an S-trap runs full and acts as a siphon, pulling the seal out of the trap. Capacity, disassembly and cleanouts are not why the code bans it.IPC §1002.3
A three-compartment sink in a restaurant has outlets 24 inches apart, and the compartments are the same depth. Under IPC §1002.1, the sink may be served by:
- a.One trap, only where each compartment has a separate vent
- b.Three traps, because every compartment must be separately trapped
- c.One trap, because the outlets are within 30 inches of each other✓
- d.Two traps, because one trap may serve at most two compartments
A combination fixture of up to three compartments may use a single trap where no compartment is more than 6 inches deeper than another and the waste outlets are not more than 30 inches apart. Separate vents are not a condition.IPC §1002.1
A floor drain in a rarely used mechanical room loses its trap seal by evaporation. Under IPC §1002.4.1, the trap must be protected by:
- a.An air admittance valve on the fixture drain serving the trap
- b.A second trap installed in series just downstream of the first
- c.A trap seal primer valve or another listed trap seal protection device✓
- d.A tight-fitting solid cover that is bolted down over the floor drain grate
Traps subject to evaporation are protected by a potable water or waste-supplied trap primer, or by a barrier-type trap seal protection device. Double trapping is prohibited, a solid cover defeats the drain, and an air admittance valve does not replace water.IPC §1002.4.1
Under IPC §1002.6, a building (house) trap on the building drain is:
- a.Required on sewers over 100 feet long
- b.Required where a backwater valve is used
- c.Required on every building
- d.Prohibited✓
Building traps are not installed, because they obstruct flow and the movement of air through the sewer and stack. They are not required for backwater valves or long sewers.IPC §1002.6
A clothes washer standpipe is roughed in. Under IPC §802.4.3, the standpipe must extend above the trap weir at least 18 inches and not more than:
- a.72 inches
- b.60 inches
- c.24 inches
- d.42 inches✓
Standpipes are individually trapped and extend 18 to 42 inches above the trap weir; the trap must be accessible. A short standpipe overflows when the washer pumps out; a very tall one can siphon the trap.IPC §802.4.3
Under IPC §1002.5, a fixture trap may not be:
- a.Smaller than the tailpiece of the fixture that it serves
- b.The same size as the drainage pipe into which it discharges
- c.Made of the same material as the fixture drain it joins
- d.Larger than the drainage pipe into which it discharges✓
A trap larger than its drain creates a reduction in size in the direction of flow and loses its self-scouring velocity. Equal size is normal, and material matching is not the issue.IPC §1002.5
Slip joints in a trap are permitted by IPC §1002.2 only:
- a.On the fixture drain between the trap and the vent fitting
- b.On the vent pipe, just above the flood rim of the fixture
- c.On the trap inlet, the trap outlet and within the trap seal✓
- d.On any concealed drain, where an elastomeric washer is used
Slip joints with an approved elastomeric gasket are allowed only on the trap inlet, trap outlet and within the trap seal, where they are accessible. They are not used on concealed drains or vents.IPC §§1002.2, 405.8
A restaurant's pot sink and dishwasher discharge fats, oils and grease. Under IPC §1003.3, the wastes must pass through:
- a.A grease interceptor✓
- b.A lint interceptor
- c.An oil separator
- d.A sand and grit interceptor
Grease interceptors receive drainage from fixtures and equipment with grease-laden waste in food preparation areas. Oil separators serve garages, sand interceptors serve car washes and similar uses, and lint interceptors serve laundries.IPC §1003.3.1
Under IPC §1003.3.2, a food waste disposer in a commercial kitchen that discharges to a grease interceptor must first pass through:
- a.A sewage ejector
- b.A backwater valve
- c.A neutralising dilution tank
- d.A solids interceptor✓
Where a food waste disposer discharges to a grease interceptor, a solids interceptor separates the solids first so they do not fill the interceptor. Backwater valves, neutralisers and ejectors serve other purposes.IPC §1003.3.2
An oil separator is installed for the floor drains of a vehicle repair garage. Under IPC §1003.4.2.1, the separator must have a depth of at least how far below the invert of the discharge drain?
- a.1 foot
- b.6 inches
- c.2 feet✓
- d.5 feet
Oil separators have a depth of not less than 2 feet below the invert of the discharge drain, and the outlet opening has a water seal of at least 18 inches. The other depths are not the code figure.IPC §1003.4.2.1
An oil separator serves a repair garage with 300 square feet of floor area drained. Under IPC §1003.4.2.2, the minimum capacity is 6 cubic feet for the first 100 square feet plus 1 cubic foot for each additional 100 square feet, a total of:
- a.9 cubic feet
- b.18 cubic feet
- c.6 cubic feet
- d.8 cubic feet✓
Six cubic feet covers the first 100 square feet; the remaining 200 square feet adds 2 cubic feet, for 8. Eighteen would be 6 cubic feet for every 100 square feet, which is not the rule.IPC §1003.4.2.2
A commercial laundry discharges to the sanitary sewer. Under IPC §1003.6, its interceptor must have a wire basket or similar device that stops solids of what size from passing to the drain?
- a.2 inches or larger
- b.1/16 inch or larger
- c.4 inches or larger
- d.1/2 inch or larger✓
Laundry interceptors prevent strings, rags, buttons and other solids 1/2 inch or larger from entering the drainage system. A finer screen blinds quickly, and coarser screens pass damaging solids.IPC §1003.6
A walk-in cooler's floor drain and a food preparation sink in a restaurant must discharge, under IPC §802.1, through:
- a.A direct connection with a backwater valve
- b.An indirect waste pipe with an air gap✓
- c.A direct connection with a deep-seal trap
- d.A common vent shared with the hand sink
Equipment and fixtures used for storage, preparation and handling of food discharge through an indirect waste pipe by means of an air gap, so that a sewer backup cannot reach food. Traps and backwater valves on a direct connection do not give that protection.IPC §802.1.1
The air gap between an indirect waste pipe and the flood level rim of the waste receptor must be, under IPC §802.2.1, at least:
- a.Equal to the effective opening of the indirect waste pipe
- b.Half the effective opening of the indirect waste pipe
- c.Twice the effective opening of the indirect waste pipe✓
- d.Ten times the effective opening of the indirect waste pipe
The air gap on the drainage side is at least two times the effective opening of the indirect waste pipe. An air break, by contrast, lets the pipe end below the flood rim but above the trap seal.IPC §802.2.1
Which statement correctly distinguishes an air break from an air gap on the drainage side?
- a.With an air break the indirect pipe is solvent-welded into the receptor
- b.With an air break the indirect pipe must be vented through the roof
- c.With an air break the indirect pipe may end below the receptor's flood rim✓
- d.With an air break the indirect pipe must end 6 inches above the flood rim
An air break is a physical separation in which the indirect waste pipe discharges into a receptor at a point below the flood level rim but above the trap seal. An air gap ends above the flood rim. Neither is a sealed connection.IPC §§202, 802.2.2
Under IPC §802.4, a waste receptor such as a floor sink may NOT be installed in:
- a.A mechanical room, beneath an air handler's condensate outlet
- b.A janitor's closet, next to the mop sink that serves the floor
- c.A plenum, crawl space, attic or interstitial space above a ceiling✓
- d.A commercial kitchen, beside the equipment that drains into it
Waste receptors are not installed in plenums, crawl spaces, attics, interstitial spaces above ceilings or below floors; they must be readily accessible and in ventilated spaces. Kitchens, mechanical rooms and janitor closets are usual locations.IPC §802.4
A laboratory discharges acid waste. Under IPC §803, the waste must be:
- a.Discharged at night, when flow in the building drain is at its lowest level
- b.Neutralised or diluted in an approved device before entering the drainage system✓
- c.Discharged through a grease interceptor of at least 50 gallons capacity
- d.Piped in copper so that the acid cannot attack the building's plastic drains
Corrosive liquids, spent acids and similar wastes that could damage pipe or disrupt sewage treatment pass through an approved dilution or neutralising device first. Timing the discharge does nothing, copper is attacked by acid, and a grease interceptor is not a neutraliser.IPC §803.1