Chapter 9 of 9
Fuel Gas
Fuel gas questions come from the 2018 International Fuel Gas Code: materials, where pipe may run, burial, testing, shutoff valves, connectors and simple demand arithmetic.
Installation
Prohibited locations
Air ducts, clothes chutes, chimneys and vents, dumbwaiters, elevator shafts.
IFGC §404.3Concealed fittings
No unions, bushings, compression couplings or swing joints.
IFGC §404.5Burial
12 inches of cover; plastic pipe outdoors underground only, with an 18 AWG yellow tracer wire.
IFGC §§404.12, 404.17CSST bonding
6 AWG copper bonding jumper.
IFGC §310Support
Steel pipe 1/2 inch: 6 ft; 3/4 and 1 inch: 8 ft; 1-1/4 inch and larger: 10 ft.
IFGC §415.1Testing and appliances
Pressure test
1-1/2 times working pressure, at least 3 psig, for at least 10 minutes; air, nitrogen, carbon dioxide or inert gas, never oxygen.
IFGC §406.4Appliance shutoff
Same room, within 6 feet; connector no longer than 6 feet and not concealed.
IFGC §§409.5, 411.1Sediment trap
At furnaces, water heaters and boilers; not at ranges, dryers, lights or grills.
IFGC §408.4Demand
Cubic feet per hour equals Btu/h input divided by the heating value of the gas.
IFGC §402