Chapter 9 of 9

Fuel Gas

Fuel gas questions come from the 2018 International Fuel Gas Code: materials, where pipe may run, burial, testing, shutoff valves, connectors and simple demand arithmetic.

Installation

Prohibited locations
Air ducts, clothes chutes, chimneys and vents, dumbwaiters, elevator shafts.
IFGC §404.3
Concealed fittings
No unions, bushings, compression couplings or swing joints.
IFGC §404.5
Burial
12 inches of cover; plastic pipe outdoors underground only, with an 18 AWG yellow tracer wire.
IFGC §§404.12, 404.17
CSST bonding
6 AWG copper bonding jumper.
IFGC §310
Support
Steel pipe 1/2 inch: 6 ft; 3/4 and 1 inch: 8 ft; 1-1/4 inch and larger: 10 ft.
IFGC §415.1

Testing and appliances

Pressure test
1-1/2 times working pressure, at least 3 psig, for at least 10 minutes; air, nitrogen, carbon dioxide or inert gas, never oxygen.
IFGC §406.4
Appliance shutoff
Same room, within 6 feet; connector no longer than 6 feet and not concealed.
IFGC §§409.5, 411.1
Sediment trap
At furnaces, water heaters and boilers; not at ranges, dryers, lights or grills.
IFGC §408.4
Demand
Cubic feet per hour equals Btu/h input divided by the heating value of the gas.
IFGC §402