Chapter 6 of 9
Sanitary Drainage
Drainage questions cover slope, fittings, cleanouts, fixture unit loads, sumps and backwater valves. Expect arithmetic on slope and fixture units.
Slope and fittings
Slope
2-1/2 inches and smaller: 1/4 inch per foot. 3 to 6 inches: 1/8 inch per foot. 8 inches and larger: 1/16 inch per foot.
IPC §704.1No reduction
Pipe size never reduces in the direction of flow; a 4-by-3 closet bend is not a reduction.
IPC §704.2Fittings
Sanitary tees only from horizontal to vertical; wyes and long sweeps for any direction.
IPC §706.3Prohibited joints
Cement, mastic, saddle fittings, solvent cement between different plastics.
IPC §707.1Cleanouts, loads and pumps
Cleanouts
Every 100 feet; at the building drain and sewer junction; at changes over 45 degrees (one per 40 feet); 18 inches of clearance for 6-inch and smaller pipe.
IPC §708.1Fixture units
Lavatory 1; tub, shower, kitchen sink 2; private 1.6 gpf water closet 3; continuous flow 2 dfu per gpm.
IPC §§709.1, 709.3Sumps
Pit 18 inches across and 24 inches deep; check valve and full-open valve on the discharge.
IPC §712Backwater valve
Required for fixtures below the next upstream manhole cover; fixtures above it do not drain through the valve.
IPC §714.1